SPEC 80215
35kV AL 100% TRXLPE One-Twelfth Concentric Neutral Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. Copper One-Twelfth Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied One-Twelfth Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
- Not recommended for use above 90ºC in wind farm applications
Specifications:
Sample Print Legend:
SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
TBA | 1/0 (19) | 0.351 | 1.079 | 345 | 1.189 | 6x14 | 0.438 | 50 | 1.417 | 837 | 9.9 | 633 |
TBA | 1/0 (19) | 0.361 | 1.089 | 345 | 1.199 | 6x14 | 0.438 | 50 | 1.427 | 846 | 9.9 | 633 |
TBA | 2/0 (19) | 0.395 | 1.123 | 345 | 1.233 | 7x14 | 0.375 | 50 | 1.461 | 910 | 10.2 | 798 |
TBA | 3/0 (19) | 0.443 | 1.171 | 345 | 1.281 | 9x14 | 0.292 | 50 | 1.509 | 1007 | 10.5 | 1006 |
662909 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 11x14 | 0.239 | 50 | 1.556 | 1049 | 10.8 | 1269 |
TBA | 250 (37) | 0.558 | 1.294 | 345 | 1.404 | 13x14 | 0.202 | 75 | 1.682 | 1317 | 11.7 | 1500 |
TBA | 350 (37) | 0.661 | 1.397 | 345 | 1.507 | 18x14 | 0.146 | 75 | 1.785 | 1563 | 12.4 | 2100 |
626324 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 15x16 | 0.278 | 75 | 1.884 | 1571 | 13.1 | 3000 |
622377 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 14x14 | 0.187 | 75 | 2.130 | 2105 | 14.9 | 4500 |
620891 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 12x12 | 0.138 | 75 | 2.312 | 2582 | 16.1 | 6000 |
621586 | 1250 (61) | 1.250 | 2.000 | 345 | 2.140 | 12x14 | 0.219 | 75 | 2.422 | 2804 | 16.9 | 7500 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ/1000ft | Ω/1000ft | A/1000ft | W/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (19) | 0.167 | 0.211 | 0.076 | 0.054 | 0.153 | 3.09 | 0.265 + j0.748 | 0.211 + j0.053 | 3103 | 160 | 195 |
1/0 (19) | 0.167 | 0.211 | 0.074 | 0.053 | 0.155 | 3.13 | 0.265 + j0.747 | 0.211 + j0.054 | 3103 | 160 | 195 |
2/0 (19) | 0.133 | 0.167 | 0.071 | 0.052 | 0.164 | 3.31 | 0.221 + j0.744 | 0.167 + j0.051 | 3621 | 185 | 220 |
3/0 (19) | 0.105 | 0.132 | 0.066 | 0.050 | 0.176 | 3.55 | 0.186 + j0.740 | 0.132 + j0.050 | 4655 | 210 | 250 |
4/0 (19) | 0.084 | 0.105 | 0.061 | 0.048 | 0.190 | 3.83 | 0.159 + j0.735 | 0.105 + j0.048 | 5690 | 235 | 285 |
250 (37) | 0.071 | 0.090 | 0.057 | 0.047 | 0.204 | 4.12 | 0.144 + j0.730 | 0.090 + j0.047 | 6724 | 257 | 302 |
350 (37) | 0.050 | 0.065 | 0.050 | 0.045 | 0.229 | 4.62 | 0.119 + j0.723 | 0.065 + j0.045 | 9311 | 315 | 370 |
500 (37) | 0.035 | 0.046 | 0.044 | 0.042 | 0.260 | 5.25 | 0.100 + j0.716 | 0.046 + j0.042 | 4870 | 380 | 445 |
750 (61) | 0.024 | 0.033 | 0.038 | 0.040 | 0.300 | 6.06 | 0.087 + j0.706 | 0.033 + j0.040 | 7242 | 470 | 530 |
1000 (61) | 0.018 | 0.026 | 0.034 | 0.038 | 0.335 | 6.76 | 0.080 + j0.699 | 0.026 + j0.038 | 9862 | 530 | 585 |
1250 (61) | 0.014 | 0.023 | 0.031 | 0.037 | 0.365 | 7.37 | 0.077 + j0.438 | 0.023 - j0.219 | 6207 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
TBA | 1/0 (19) | 8.92 | 27.41 | 8.76 | 30.20 | 6x14 | 1.44 | 1.27 | 35.99 | 1246 | 251.46 | 2817 |
TBA | 1/0 (19) | 9.17 | 27.66 | 8.76 | 30.45 | 6x14 | 1.44 | 1.27 | 36.25 | 1259 | 251.46 | 2817 |
TBA | 2/0 (19) | 10.03 | 28.52 | 8.76 | 31.32 | 7x14 | 1.23 | 1.27 | 37.11 | 1354 | 259.08 | 3551 |
TBA | 3/0 (19) | 11.25 | 29.74 | 8.76 | 32.54 | 9x14 | 0.96 | 1.27 | 38.33 | 1499 | 266.70 | 4477 |
662909 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 11x14 | 0.78 | 1.27 | 39.52 | 1561 | 274.32 | 5647 |
TBA | 250 (37) | 14.17 | 32.87 | 8.76 | 35.66 | 13x14 | 0.66 | 1.91 | 42.72 | 1960 | 297.18 | 6675 |
TBA | 350 (37) | 16.79 | 35.48 | 8.76 | 38.28 | 18x14 | 0.48 | 1.91 | 45.34 | 2326 | 314.96 | 9345 |
626324 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 15x16 | 0.91 | 1.91 | 47.85 | 2338 | 332.74 | 13350 |
622377 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 14x14 | 0.61 | 1.91 | 54.10 | 3133 | 378.46 | 20025 |
620891 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 12x12 | 0.45 | 1.91 | 58.72 | 3842 | 408.94 | 26700 |
621586 | 1250 (61) | 31.75 | 50.80 | 8.76 | 54.36 | 12x14 | 0.72 | 1.91 | 61.52 | 4173 | 429.26 | 33375 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | A/km | W/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (19) | 0.5479 | 0.69 | 0.0232 | 0.1772 | 0.502 | 10.1378 | 0.265 + j0.748 | 0.211 + j0.053 | 3103 | 160 | 195 |
1/0 (19) | 0.5479 | 0.69 | 0.0226 | 0.1739 | 0.509 | 10.2690 | 0.265 + j0.747 | 0.211 + j0.054 | 3103 | 160 | 195 |
2/0 (19) | 0.4364 | 0.55 | 0.0216 | 0.1706 | 0.538 | 10.8596 | 0.221 + j0.744 | 0.167 + j0.051 | 3621 | 185 | 220 |
3/0 (19) | 0.3445 | 0.43 | 0.0201 | 0.1640 | 0.577 | 11.6470 | 0.186 + j0.740 | 0.132 + j0.050 | 4655 | 210 | 250 |
4/0 (19) | 0.2756 | 0.34 | 0.0186 | 0.1575 | 0.623 | 12.5656 | 0.159 + j0.735 | 0.105 + j0.048 | 5690 | 235 | 285 |
250 (37) | 0.2329 | 0.30 | 0.0174 | 0.1542 | 0.669 | 13.5171 | 0.144 + j0.730 | 0.090 + j0.047 | 6724 | 257 | 302 |
350 (37) | 0.1640 | 0.21 | 0.0152 | 0.1476 | 0.751 | 15.1575 | 0.119 + j0.723 | 0.065 + j0.045 | 9311 | 315 | 370 |
500 (37) | 0.1148 | 0.15 | 0.0134 | 0.1378 | 0.853 | 17.2244 | 0.100 + j0.716 | 0.046 + j0.042 | 4870 | 380 | 445 |
750 (61) | 0.0787 | 0.11 | 0.0116 | 0.1312 | 0.984 | 19.8819 | 0.087 + j0.706 | 0.033 + j0.040 | 7242 | 470 | 530 |
1000 (61) | 0.0591 | 0.09 | 0.0104 | 0.1247 | 1.099 | 22.1785 | 0.080 + j0.699 | 0.026 + j0.038 | 9862 | 530 | 585 |
1250 (61) | 0.0459 | 0.08 | 0.0094 | 0.1214 | 1.198 | 24.1798 | 0.077 + j0.438 | 0.023 - j0.219 | 6207 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.003
Updated On: Sept. 21, 2023, 2:14 p.m. UTC