SPEC 80213

35kV AL 100% TRXLPE One-Third Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
  • Not recommended for use above 90ºC in wind farm applications

Specifications:

  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6297751/0 (19)0.3511.0723451.1827x160.597501.3837429.6633
    TBA1/0 (19)0.3611.0893451.1996x140.438501.4278469.9633
    603763&2/0 (19)0.3951.1153451.2257x140.375501.45385310.1798
    TBA3/0 (19)0.4431.1713451.2819x140.292501.509100710.51006
    6188604/0 (19)0.4981.2183451.32813x140.202501.556107610.81269
    TBA250 (37)0.5581.2943451.40413x140.202751.682131711.71500
    662685350 (37)0.6611.3913451.50114x140.187751.783141012.42100
    600871^350 (37)0.6611.3913451.50116x140.164751.783143612.42100
    628391350 (37)0.6611.3913451.50114x140.187751.783141212.42100
    618570%500 (37)0.7891.5193451.62912x120.138751.944175713.63000
    626328500 (37)0.7891.5193451.62912x120.138751.944176413.63000
    662829^750 (61)0.9681.7083451.84824x120.069752.163244115.14500
    626338750 (61)0.9681.7083451.84818x120.092752.163232615.14500
    6075941000 (61)1.1171.8573451.99723x120.072752.312279116.16000
    6628181000 (61)1.1171.8573451.99720x100.052752.354302116.46000
    6628161250 (61)1.2502.0003452.14025x100.041752.497353417.47500
    663836^1250 (61)1.2502.0003452.14025x100.041752.497353417.47500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    & Super Smooth Insulation Shield
    § HiDri Plus - Water Blocking Powder. Black Jacket. CSA Listed
    ! Non-UL listed
    ^ Water Blocking Powder.
    % HI-DRI only (only moisture block on conductor, no water swellallable powder under jacket)
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.1670.2110.0760.0530.1533.090.265 + j0.7490.211 + j0.0532273160195
    1/0 (19)0.1670.2110.0740.0530.1553.130.265 + j0.7470.211 + j0.0543103160195
    2/0 (19)0.1330.1670.0710.0520.1643.310.221 + j0.7440.167 + j0.0513621185220
    3/0 (19)0.1050.1320.0660.0500.1763.550.186 + j0.7400.132 + j0.0504655210250
    4/0 (19)0.0840.1050.0610.0480.1903.830.159 + j0.7350.105 + j0.0486724235285
    250 (37)0.0710.0900.0570.0470.2044.120.144 + j0.730.090 + j0.0476724257302
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7230.065 + j0.0457242315370
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7230.065 + j0.0458276315370
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7230.065 + j0.0457242315370
    500 (37)0.0350.0460.0440.0430.2605.250.100 + j0.7140.046 + j0.0439862380445
    500 (37)0.0350.0460.0440.0430.2605.250.100 + j0.7140.046 + j0.0439862380445
    750 (61)0.0240.0330.0380.0400.3006.060.087 + j0.7050.033 + j0.04019725470530
    750 (61)0.0240.0330.0380.0400.3006.060.087 + j0.7050.033 + j0.04014794470530
    1000 (61)0.0180.0260.0340.0380.3356.760.080 + j0.6990.026 + j0.03818903530585
    1000 (61)0.0180.0260.0340.0390.3356.760.080 + j0.6980.026 + j0.03926129530585
    1250 (61)0.0140.0230.0310.0380.3657.370.077 + j0.4370.023 - j0.21832661
    1250 (61)0.0140.0230.0310.0380.3657.370.077 + j0.4370.023 - j0.21832661
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6297751/0 (19)8.9227.238.7630.027x161.961.2735.131104243.842817
    TBA1/0 (19)9.1727.668.7630.456x141.441.2736.251259251.462817
    603763&2/0 (19)10.0328.328.7631.127x141.231.2736.911269256.543551
    TBA3/0 (19)11.2529.748.7632.549x140.961.2738.331499266.704477
    6188604/0 (19)12.6530.948.7633.7313x140.661.2739.521601274.325647
    TBA250 (37)14.1732.878.7635.6613x140.661.9142.721960297.186675
    662685350 (37)16.7935.338.7638.1314x140.611.9145.292098314.969345
    600871^350 (37)16.7935.338.7638.1316x140.541.9145.292137314.969345
    628391350 (37)16.7935.338.7638.1314x140.611.9145.292101314.969345
    618570%500 (37)20.0438.588.7641.3812x120.451.9149.382615345.4413350
    626328500 (37)20.0438.588.7641.3812x120.451.9149.382625345.4413350
    662829^750 (61)24.5943.388.7646.9424x120.231.9154.943633383.5420025
    626338750 (61)24.5943.388.7646.9418x120.301.9154.943461383.5420025
    6075941000 (61)28.3747.178.7650.7223x120.241.9158.724153408.9426700
    6628181000 (61)28.3747.178.7650.7220x100.171.9159.794496416.5626700
    6628161250 (61)31.7550.808.7654.3625x100.131.9163.425259441.9633375
    663836^1250 (61)31.7550.808.7654.3625x100.131.9163.425259441.9633375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    & Super Smooth Insulation Shield
    § HiDri Plus - Water Blocking Powder. Black Jacket. CSA Listed
    ! Non-UL listed
    ^ Water Blocking Powder.
    % HI-DRI only (only moisture block on conductor, no water swellallable powder under jacket)
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.54790.690.02320.17390.50210.13780.265 + j0.7490.211 + j0.0532273160195
    1/0 (19)0.54790.690.02260.17390.50910.26900.265 + j0.7470.211 + j0.0543103160195
    2/0 (19)0.43640.550.02160.17060.53810.85960.221 + j0.7440.167 + j0.0513621185220
    3/0 (19)0.34450.430.02010.16400.57711.64700.186 + j0.7400.132 + j0.0504655210250
    4/0 (19)0.27560.340.01860.15750.62312.56560.159 + j0.7350.105 + j0.0486724235285
    250 (37)0.23290.300.01740.15420.66913.51710.144 + j0.730.090 + j0.0476724257302
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7230.065 + j0.0457242315370
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7230.065 + j0.0458276315370
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7230.065 + j0.0457242315370
    500 (37)0.11480.150.01340.14110.85317.22440.100 + j0.7140.046 + j0.0439862380445
    500 (37)0.11480.150.01340.14110.85317.22440.100 + j0.7140.046 + j0.0439862380445
    750 (61)0.07870.110.01160.13120.98419.88190.087 + j0.7050.033 + j0.04019725470530
    750 (61)0.07870.110.01160.13120.98419.88190.087 + j0.7050.033 + j0.04014794470530
    1000 (61)0.05910.090.01040.12471.09922.17850.080 + j0.6990.026 + j0.03818903530585
    1000 (61)0.05910.090.01040.12801.09922.17850.080 + j0.6980.026 + j0.03926129530585
    1250 (61)0.04590.080.00940.12471.19824.17980.077 + j0.4370.023 - j0.21832661
    1250 (61)0.04590.080.00940.12471.19824.17980.077 + j0.4370.023 - j0.21832661
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.

    Revision: 1.000.001