SPEC 45503

TCU 2000V NLEPR Insulation Thermoset LSZH-TS Jacket. RHH/RHW-2

Power Cable 2000 Volt Single Conductor Copper or Tinned Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Thermoset SOLONON® (LSZH-TS) Jacket

...

Construction:

  1. Conductor:Stranded tinned copper per ASTM B33
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR)
  4. Overall Jacket:Cross-linked/Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B173 Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (250kcmil & Larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    AWG Sizes
    {SQFTG} SOUTHWIRE {UL} XX AWG or KCMIL TINNED CU TYPE RHH OR RHW-2 XX MILS EPR XX MILS SOLONON{R} ST1 FOR CT USE SUN RES 2000V {YYYY}

    Kcmil Sizes
    {SQFTG} SOUTHWIRE{R} E30117 {UL} XXX KCMIL RHH OR RHW-2 XX MILS NL-EPR XX MILS SOLONON{R} PRI/PRII -40{D}C FT4 ST1 FOR CT USE SUN RES 2000V --- {CSA} 156205 XXX KCMIL RW90 XX MILS NL-EPR XX MILS SOLONON{R} 90{D}C DRY 90{D}C WET TC-ER 2KV -40{D}C PRI PRII FT4-ST1 SR

    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorMin. Avg. Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    6721851/0190.36265450.585326410
    TBA2/0190.40565450.625410511
    6728882/02590.44565450.678418538
    TBA3/0190.45665450.680518620
    TBA4/0190.51265450.732653775
    6729104/01330.59865650.873693883
    TBA250370.55875650.782771891
    6642782502590.61075650.9728111069
    TBA350370.66175650.94510811265
    TBA500370.78975651.06915441779
    5603055002590.85075651.15015481820
    6494175002590.89075651.25215791924
    TBA750610.96890651.27823162626
    6438817501270.96890651.30023152652
    TBA1000611.11790651.42730883440
    65313210001271.11890651.45030883468
    TBA20001271.583115952.00361756852
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    6721851/04.78450.1020.1220.044125150170
    TBA2/05.010650.0810.0970.043145175195
    6728882/05.410650.0810.0970.043145175195
    TBA3/05.413420.0640.0780.042165200225
    TBA4/05.916930.0510.0620.041195230260
    6729104/07.016930.0510.0620.041195230260
    TBA2506.320000.0430.0530.041215255290
    6642782507.820000.0430.0530.041215255290
    TBA3507.628000.0310.0390.040260310350
    TBA5008.640000.0220.0290.039320380430
    5603055009.240000.0220.0290.039320380430
    64941750010.040000.0220.0290.039320380430
    TBA75010.260000.0140.0220.038400475535
    64388175010.460000.0140.0220.038400475535
    TBA100011.480000.0110.0180.037455545615
    653132100011.680000.0110.0180.037455545615
    TBA200016.0100000.0050.0160.034555665750
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.002

    Updated On: Sept. 23, 2023, 4:36 p.m. UTC