SPEC 22061
1/C CU 600V RW90 SIMpull®
Copper Conductor, 600V, 90°C MAX - 40°C MIN, 1/0 AWG to 1000 KCMIL. Sizes 350 kcmil & Larger FT4 Rated. All Sizes and Colors Are Sunlight Resistant.
Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) SIMpull®
Applications and Features:
Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Standard sizes 1/0 AWG and larger utilize SIMpull ® technology. All sizes are Sunlight Resistant in all colors and packaging. This product meets the current RoHS requirements. No lead is added or used in manufacturing.
Specifications:
Sample Print Legend:
SOUTHWIRE® XXXX KCMIL NOLUBE® SIMpull RW90{TM} LL90458 {CSA} (XXXX.XX{mm2}) CU RW90 XLPE 600 VOLTS (-40°C) SR - MADE UNDER US PATENT NOS 7411129 & 7557301-RW90 XXXX KCMIL {MMM/DD/YYYY} - OPERATOR NAME SEQUENTIAL METER MARKS SEQ METERS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mil | inch | lb/1000ft | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | |
951749 | 12 | 7 | 30 | 0.153 | 25 | 0.6 | 32 | 1.662 | 2.002 | 0.054 | 30 |
951756 | 10 | 7 | 30 | 0.175 | 38 | 0.7 | 52 | 1.040 | 1.253 | 0.050 | 40 |
951764 | 8 | 7 | 45 | 0.238 | 64 | 0.9 | 132 | 0.653 | 0.786 | 0.052 | 55 |
951772 | 6 | 7 | 45 | 0.274 | 97 | 1.0 | 209 | 0.411 | 0.495 | 0.051 | 75 |
951780 | 4 | 7 | 45 | 0.321 | 149 | 1.2 | 333 | 0.258 | 0.310 | 0.048 | 95 |
951798 | 2 | 7 | 45 | 0.379 | 231 | 1.5 | 530 | 0.162 | 0.195 | 0.045 | 130 |
951806 | 1 | 19 | 55 | 0.438 | 292 | 1.7 | 669 | 0.128 | 0.154 | 0.046 | 145 |
951814 | 1/0 | 19 | 55 | 0.478 | 363 | 1.9 | 844 | 0.102 | 0.122 | 0.044 | 170 |
951822 | 2/0 | 19 | 55 | 0.520 | 452 | 2.0 | 1064 | 0.081 | 0.097 | 0.043 | 195 |
951830 | 3/0 | 19 | 55 | 0.570 | 564 | 2.2 | 1342 | 0.064 | 0.078 | 0.042 | 225 |
951848 | 4/0 | 19 | 55 | 0.626 | 707 | 2.5 | 1692 | 0.051 | 0.062 | 0.041 | 260 |
951855 | 250 | 37 | 65 | 0.680 | 828 | 2.7 | 2000 | 0.043 | 0.053 | 0.041 | 290 |
951871 | 350 | 37 | 65 | 0.799 | 1155 | 3.1 | 2800 | 0.031 | 0.039 | 0.040 | 350 |
951897 | 500 | 37 | 65 | 0.904 | 1618 | 3.6 | 4000 | 0.022 | 0.029 | 0.039 | 430 |
951905 | 600 | 61 | 80 | 1.036 | 1967 | 5.1 | 4800 | 0.018 | 0.025 | 0.039 | 475 |
951913 | 750 | 61 | 80 | 1.138 | 2442 | 5.6 | 6000 | 0.014 | 0.022 | 0.038 | 535 |
951921 | 1000 | 61 | 80 | 1.287 | 3232 | 6.4 | 8000 | 0.011 | 0.018 | 0.037 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
Table 2 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | kg/km | mm | newton | Ω/km | Ω/km | Ω/km | Amp | |
951749 | 12 | 7 | 0.76 | 3.89 | 37 | 15.24 | 142 | 5.45 | 6.57 | 0.1772 | 30 |
951756 | 10 | 7 | 0.76 | 4.44 | 57 | 17.78 | 231 | 3.41 | 4.11 | 0.1640 | 40 |
951764 | 8 | 7 | 1.14 | 6.05 | 95 | 22.86 | 587 | 2.14 | 2.58 | 0.1706 | 55 |
951772 | 6 | 7 | 1.14 | 6.96 | 144 | 25.40 | 930 | 1.35 | 1.62 | 0.1673 | 75 |
951780 | 4 | 7 | 1.14 | 8.15 | 222 | 30.48 | 1482 | 0.85 | 1.02 | 0.1575 | 95 |
951798 | 2 | 7 | 1.14 | 9.63 | 344 | 38.10 | 2359 | 0.53 | 0.64 | 0.1476 | 130 |
951806 | 1 | 19 | 1.40 | 11.13 | 435 | 43.18 | 2977 | 0.42 | 0.51 | 0.1509 | 145 |
951814 | 1/0 | 19 | 1.40 | 12.14 | 540 | 48.26 | 3756 | 0.33 | 0.40 | 0.1444 | 170 |
951822 | 2/0 | 19 | 1.40 | 13.21 | 673 | 50.80 | 4735 | 0.27 | 0.32 | 0.1411 | 195 |
951830 | 3/0 | 19 | 1.40 | 14.48 | 839 | 55.88 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
951848 | 4/0 | 19 | 1.40 | 15.90 | 1052 | 63.50 | 7529 | 0.17 | 0.20 | 0.1345 | 260 |
951855 | 250 | 37 | 1.65 | 17.27 | 1232 | 68.58 | 8900 | 0.14 | 0.17 | 0.1345 | 290 |
951871 | 350 | 37 | 1.65 | 20.29 | 1719 | 78.74 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
951897 | 500 | 37 | 1.65 | 22.96 | 2408 | 91.44 | 17800 | 0.07 | 0.10 | 0.1280 | 430 |
951905 | 600 | 61 | 2.03 | 26.31 | 2927 | 129.54 | 21360 | 0.06 | 0.08 | 0.1280 | 475 |
951913 | 750 | 61 | 2.03 | 28.91 | 3634 | 142.24 | 26700 | 0.05 | 0.07 | 0.1247 | 535 |
951921 | 1000 | 61 | 2.03 | 32.69 | 4810 | 162.56 | 35600 | 0.04 | 0.06 | 0.1214 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
Revision: 1.000.000
Updated On: Dec. 11, 2023, 9:29 p.m. UTC