SPEC 10033

Romex® Brand SIMpull® NM-B-PCS DUO™ Cable

Nonmetallic-Sheathed Cable with both Power Conductors and Control/Signal Conductors. 600 Volts. Copper Conductors. PVC Insulation/Nylon Sheath. Color-Coded PVC Jacket with SIMpull® Technology for Easier Pulling.

...

Construction:

  1. Conductor: Solid copper per ASTM B3
  2. Insulation: All phases and neutral are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
  3. Ground: Solid soft drawn bare copper with kraft paper wrap
  4. Binder: Kraft paper
  5. Control/Signal Conductors:16 AWG Copper TFN Insulated Singles Colored Pink, Purple. Overall light blue jacket over the signal conductors
  6. Jacket: Polyvinyl Chloride (PVC) jacket utilizing SIMpull® Technology.
    Color Code: White 14 AWG, Yellow 12 AWG, Orange 10 AWG. Blue stripe over control/signal component

Applications and Features:

Southwire® Romex® Brand SIMpull® NM-B-PCS DUO™ nonmetallic-sheathed cable may be used for both exposed and concealed work in dry locations at temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified in the National Electrical Code®. NM-B-PCS cable is primarily used in residential wiring for SMART home applications such as 0-10V DC dimming controls for LED lighting. NM-B-PCS cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B-PCS cable is 600 volts. All conductors are rated 600 volts. Complies with the Class 2/Class 3 circuit separation requirements of NEC 725.136(I)(1) and 725.136(I)(2)."

CAUTION: Do note use the control/signal component to make connections to 120V AC line voltage.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 719 Nonmetallic-Sheathed Cables
  • REACH/RoHS Compliant
  • Federal Specification A-A-59544
  • Sample Print Legend:

    E18679 (UL) ROMEX{R} SIMpull{TM} XX AWG CU X CDR WITH XX AWG GROUND TYPE NM-B-PCS 600 VOLTS - PATENT PENDING

    Signal/Control
    CONDUCTORS UNDER THIS JACKET ARE ONLY FOR SIGNAL/CONTROL CONNECTIONS, NOT FOR CIRCUIT POWER

    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberConductor StrandingInsulation ThicknessGround SizeJacket ThicknessApprox. ODOverall Weight
    AWG/KcmilmilsNo. x AWGmilinchlbs/1000ft
    678071142Solid201x14280.213 X 0.637109
    679628122Solid201x12280.213 X 0.687135
    679630102Solid251x10280.213 X 0.767169
    679629123Solid201x12280.213 X 0.806163
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberDC Resistance at 25°CAC Resistance at 75°CAllowable Ampacity Raceway 60°C
    AWG/KcmilΩ/1000ftΩ/1000ftAmp
    1422.573.17015
    1221.622.00220
    1021.021.25330
    1231.622.00220
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.002

    Updated On: Aug. 21, 2023, 11:26 a.m. UTC