SPEC 45043

Southwire® MACHINE FLEX™ CU 600/1000V PVC-Nylon Insulation TPE Black Jacket. THHN

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Black Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s MachineFLEX™ tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • UL 13 Type PLTC-ER sizes 18-12AWG
  • UL 2250 Type ITC-ER on sizes 18-12 AWG
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    SOUTHWIRE{R} XX AWG (X.XXmm2) X/C PVC/NYLON TYPE TC-ER E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC-ER OR ITC-ER OR AWM 2587 -- LL90458 CSA CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- {NOM}-ANCE PLTC -- {CE} RoHS-2 MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    677315183160.04420450.28115437.1488.6131.1--14
    677530184160.04420450.30620547.1488.6131.2--11
    677316185160.04420450.33225637.1488.6131.3--11
    665090186160.04420450.34830847.1488.6131.4--11
    677531187160.04420450.35835807.1488.6131.4--9
    665089188160.04420450.401401117.1488.6131.6--9
    677532189160.04420450.411451027.1488.6131.6--9
    6650911810160.04420450.438501377.1488.6131.8--7
    6775331812160.04420450.456601327.1488.6131.8--7
    6650921814160.04420450.469701407.1488.6131.9--7
    6650931816160.04420450.495801657.1488.6132.0--7
    6650941819160.04420650.560952367.1488.6132.2--7
    6773171825160.04420650.6351252547.1488.6131.3--6
    6650951837160.04420650.7321864227.1488.6132.9--5
    16 AWG
    665096162260.05920500.31116484.4875.4061.2--18
    677535163260.05920500.31124584.4875.4061.2--18
    677536164260.05920500.33932714.4875.4061.4--14
    677318165260.05920450.37040864.4875.4061.5--14
    665098167260.05920500.400561224.4875.4061.6--12
    665099168260.05920500.431641424.4875.4061.7--12
    665097166260.05920500.462481404.4875.4061.9--14
    677320169260.05920500.462721384.4875.4061.9--12
    6651001610260.05920500.509811534.4875.4062.0--9
    6773211612260.05920500.509971754.4875.4062.0--9
    6651011616260.05920650.6011292414.4875.4062.4--9
    6651021619260.05920650.6301543154.4875.4062.5--9
    6651031624260.05920650.7161943404.4875.4062.9--8
    6651041630260.05920850.8112434394.4875.4063.2--8
    6651051637260.05920850.8702995274.4875.4063.5--7
    14 AWG
    677258143410.07320500.34238772.8143.3911.4152025
    677259144410.07320500.37551972.8143.3911.5121620
    665106146410.07320500.445761342.8143.3911.8121620
    653005148410.07320500.4951021752.8143.3911.9101417
    677261149410.07320500.5161151892.8143.3912.1101417
    6651071410410.07320650.6011272262.8143.3912.471012
    6773221412410.07320650.6081532582.8143.3912.571012
    6651081416410.07320650.6662043322.8143.3912.771012
    6772621418410.07320650.6972304192.8143.3912.871012
    6772631425410.07320650.8063184882.8143.3913.26911
    12 AWG
    677256123650.09420500.389601081.7742.1371.6202530
    677537124650.09420500.420811371.7742.1371.7162024
    677538125650.09420500.4621011651.7742.1371.9162024
    665109126650.09420500.5021421941.7742.1372.0162024
    677257127650.09420500.5021412191.7742.1372.0141721
    6651111212650.09420650.6872434251.7742.1372.8101215
    10 AWG
    6530091031050.11725500.462971601.1111.3392.0303540
    6775391041050.11725500.5021292021.1111.3392.0242832
    6772541051050.11725500.5791612571.1111.3392.0242832
    6772551071050.11725600.6282263371.1111.3392.4212428
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.