SPEC 87010
Cable-in-Conduit (CIC) CU 600V THHN SCH 40
Construction:
• Manufactured by continuously extruding HDPE loosely around the cable assembly with no adhesion between the conduit and the cable, thus leaving the cables free in the conduit.
• Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.
• All cables are installed as single conductors or paralleled in HDPE conduit and are available in Standard Wall, Schedule 40, Schedule 80, SDR 13.5, SDR 11, and EPEC-17.
• Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.
• All cables are installed as single conductors or paralleled in HDPE conduit and are available in Standard Wall, Schedule 40, Schedule 80, SDR 13.5, SDR 11, and EPEC-17.
Applications and Features:
Commonly installed from transformer to transformer or as underground cables exiting substations
Specifications:
Sample Print Legend:
{SQFTG} FEET (LOGO) SOUTHWIRE CABLE IN CONDUIT (UL) HDPE X" SCH40 NEMA TC 7 / ASTM F2160 (NESC) {MMM/DD/YYYY} {MACH/SHFT/OP}
Table 1 – Physical and Electrical Data
Stock Number | Description | Cable Color | Duct Nominal Size | Duct Nominal Outside Dia. | Duct Min. Wall Thickness | Duct Nominal Inside Dia. | Duct Min. Bending Radius | Duct Max. Pull Tension | Duct Color | Approx. Cable and Duct Weight |
---|---|---|---|---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lb | lb/1000ft | ||||
631263 | 4 x #10 CU THHN | BK, WE, RD GN | 0.75 | 1.050 | 0.113 | 0.804 | 12 | 710 | Black | 305 |
632374 | 3x#10 CU THHN | BK, WE, GN | 0.75 | 1.050 | 0.113 | 0.804 | 12 | 710 | Black | 305 |
632375 | 4x#10 CU THHN | BN, OE, YW, GY | 0.75 | 1.050 | 0.113 | 0.804 | 12 | 710 | Black | 305 |
632362 | 4x#8 CU THHN | BN, OE, YW, GN | 1.00 | 1.315 | 0.133 | 1.029 | 14 | 1050 | Black | 475 |
632545 | 4x#6 CU THHN | BN, OE, YW, GN | 1.00 | 1.315 | 0.133 | 1.029 | 14 | 1050 | Black | 607 |
633471 | 4x#4 CU THHN | BN, OE, YW, GN | 1.25 | 1.660 | 0.140 | 1.360 | 18 | 1420 | Black | 917 |
634449 | 4x1/0 AL THHN | BN, OE, YW, GY | 1.50 | 1.900 | 0.145 | 1.590 | 21 | 1700 | Red | 1029 |
634598 | 4x#3/0 CU THHN - 1x#4 | BN, OE, YW, GY, GN | 2.50 | 2.875 | 0.203 | 2.445 | 32 | 3615 | Black | 3240 |
634600 | 4x#2 CU THHN - 1x#4 | BN, OE, YW, GY, GN | 2.50 | 2.875 | 0.203 | 2.445 | 32 | 3615 | Black | 1855 |
634599 | 4x#1 CU THHN - 1x#4 | BN, OE, YW, GY, GN | 2.50 | 2.875 | 0.203 | 2.445 | 32 | 3615 | Black | 2120 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Cable Specification
Stock Number | Cable Specification |
---|---|
632374 / 632375 / 632362 / 632545 / 634598 / 634600 / 634599 / 633471 | SPEC 10000 |
Cell Classification for HDPE Conduit
Property | Test Method | Value |
---|---|---|
Density | D4883 | 0.953 g/cc |
Melt Index | D1238 | 0.25 g/10 min |
Flexural Modulus | D790 | 168,000 psi |
Tensile Strength | D638 | 3900 yield @ 2 in/min |
SP-NCLS ESCR | F2136 | >1000 hrs |
Hydrostatic Design Basis | D2837 | N/A |
Revision: 1.000.013
Updated On: Feb. 29, 2024, 11:29 a.m. UTC
CIC Labor Saving Calculator