SPEC 48010

1/C CU 600V Tray Rated LSZH RW90 VW-1 Cable SOLONONplus® Living Building Challenge™ (LBC) Red List Free

SOLONONplus® 600 Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RW 90

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:SOLONONplus® Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type RW 90 VW-1

Applications and Features:

Southwire’s 600 Volt SOLONONplus® Type RW 90 VW-1 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. Color Available upon request
c. Listed and marked CSA VW-1 for all sizes
d. The halogen content is less than 0.2% and Acid gas less than 2.0%
e. CSA listed for TC use on 1/0 and Larger. 70,000 BTU/Hr. Vertical Flalme Test (CSA C22.2 NO. 2556)
f. CSA listed FT4/IEEE 1202 and ST-1 (1/0 and larger)
g. -40°C Cold impact and cold bend
h. PRI Oil resistance I at 60°C & PRII Oil resistance II at 75°C
i. GRI gasoline and oil resistance at 60°C
j. GRII gasoline and oil resistance at 75°C
k. REACH & RoHS compliant
l. Listed and marked HAL-FREE (Halogen Free) per CSA 2556-15
m. Living Building Challenge™ (LBC) Red List Free

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables Type RW90
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • ISO 9001 Quality management
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

  • 1/0 AWG and larger cables
  • SOUTHWIRE SOLONONplus (TM) LSZH XLPO 156205 MASTER-DESIGN {CSA} 1/0 AWG (XXX mm2) CU RW90 600V VW-1 HAL-FREE TC PRI PRII GRI GRII -40{D}C SR FT4 ST-1 {SEQUENTIAL METER MARKS} SEQ METERS [date code]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.milinchlb/1000ftinchΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA147300.13160.52.6313.170.05825
    TBA127300.148250.51.6622.0020.05430
    TBA107300.173390.61.041.2530.0540
    TBA87450.231630.90.6530.7860.05255
    TBA67450.267971.00.4110.4950.05175
    TBA47450.3151471.20.2580.310.04895
    TBA37450.3421831.30.2050.2460.047115
    TBA27450.3722281.40.1620.1950.045130
    TBA119550.4322911.70.1280.1540.046145
    TBA1/019550.4713621.80.1020.1220.044170
    TBA2/019550.5154512.00.0810.0970.043195
    TBA3/019550.5665642.20.0640.0780.042225
    TBA4/019550.6227042.40.0510.0620.041260
    TBA25037650.6888372.70.0430.0530.041290
    TBA35037650.79111583.10.0310.0390.040350
    TBA50037650.91916343.60.0220.0290.039430
    TBA60061801.02519765.10.0180.0250.039475
    TBA75061801.12824535.60.0140.0220.038535
    TBA100061801.27732446.30.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.mmmmkg/kmmmΩ/kmΩ/kmΩ/kmAmp
    TBA1470.763.302412.708.631910.400.190325
    TBA1270.763.763712.705.45286.570.177230
    TBA1070.764.395815.243.41214.110.164040
    TBA871.145.879422.862.14242.580.170655
    TBA671.146.7814425.401.34841.620.167375
    TBA471.148.0021930.480.84651.020.157595
    TBA371.148.6927233.020.67260.810.1542115
    TBA271.149.4533935.560.53150.640.1476130
    TBA1191.4010.9743343.180.41990.510.1509145
    TBA1/0191.4011.9653945.720.33460.400.1444170
    TBA2/0191.4013.0867150.800.26570.320.1411195
    TBA3/0191.4014.3883955.880.21000.260.1378225
    TBA4/0191.4015.80104860.960.16730.200.1345260
    TBA250371.6517.48124668.580.14110.170.1345290
    TBA350371.6520.09172378.740.10170.130.1312350
    TBA500371.6523.34243291.440.07220.100.1280430
    TBA600612.0326.032941129.540.05910.080.1280475
    TBA750612.0328.653650142.240.04590.070.1247535
    TBA1000612.0332.444828160.020.03610.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Stock Codes and Colors

    SizeBLKBRNORGYLWWHTREDBLUGRN
    1/0678792678795678796678798678791678793678794678790
    2/0678802678806678807678808678801678803678804678800
    3/0678811678815678816678817678810678812678814678809
    4/0678824678827678828678829678823678825678826678822
    250678832678835678836678837678831678833678834678830
    350678841678844678845678846678840678842678843678838
    500678850678853678855678856678849678851678852678848
    600678859678863678864678865678858678860678861678857

    Revision: 3.0.00M