SPEC 48001

CU 600V LSZH XHHW-2 SOLONONplus®

SOLONONplus® 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:SOLONONplus® Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2

Applications and Features:

Southwire’s 600 Volt SOLONONplus® Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. Passes UL VW-1 # 8 AWG and larger
e. 70,000 BTU/Hr. Vertical Flame Test
f. UL listed for CT use on 1/0 and Larger
g. UL listed FT4/IEEE 1202 and ST-1 (#8 and larger)
h. -40°C Cold impact and cold bend
i. Oil Resistant I and II
j. UV/Sunlight resistant black color
k. Color Available upon request

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (#8 AWG and larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus{TM} E30117 MASTER-DESIGN {UL} AWG XX BARE OR TINNED CU LSZH XLPO TYPE XHHW-2 HF -40{D}C SR PRI PRII FT4 ST-1 600V {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsmilinchlb/1000ftlb/1000ft
    64959314Solid300.1281218
    647361147300.1331218
    59925412Solid300.1441926
    649601127300.1512027
    59926310Solid300.1653139
    646542107300.1773240
    59932887450.2365067
    679070067450.27281100
    59933767450.27281100
    59934647450.319128152
    64169137450.346162188
    59935527450.371204233
    643752119550.438258299
    6416931/019550.478326371
    5995092/019550.522410461
    5995194/019550.614653714
    64169925037650.678771849
    64964530037650.7479261012
    64170360061801.03418522000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ # 6AWG Stock Number 679070 is Tinned Copper Conductor
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    649593140.52.6313.1700.058152025
    647361140.52.6313.1700.058152025
    599254120.51.6622.0020.054202530
    649601120.61.6622.0020.054202530
    599263100.61.0401.2530.050303540
    646542100.71.0401.2530.050303540
    59932880.90.6530.7860.052405055
    679070061.00.4110.4950.051556575
    59933761.00.4110.4950.051556575
    59934641.20.2580.310.048708595
    64169131.30.2050.2460.04785100115
    59935521.40.1620.1950.04595115130
    64375211.70.1280.1540.046110130145
    6416931/01.90.1020.1220.044125150170
    5995092/02.00.0810.0970.043145175195
    5995194/02.40.0510.0620.041195230260
    6416992502.70.0430.0530.041215255290
    6496453002.90.0360.0450.041240285320
    6417036005.10.0180.0250.039350420475
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

    Table 3 - Stock Code Colors (Black in Table 1)

    SizeRedBlueWhiteBrownOrangeYellowGrayGreenPurple
    RedBlueWhiteBrownOrangeYellowGrayGreenPurple
    12 (Solid)599255599256599253599258599259599260599257599252647516
    10 (Solid)599264599265599262599281599282599283599280599261
    14 (19)643917
    12 (19)677425*646526646527646528646529
    10 (19)646530646531646532646533
    8 (19)599331599329599333599335599336599334599330
    6 (19)599340599338599341599342599344599345599343599339
    4 (19)599349599347599350599351599353599354599352599348
    2 (19)599358599356599359599360599507599508599505599357
    1/0 (19)641694
    2/0 (19)679228*
    250 (37)679131*
    500 (37)641702
    *Tinned Copper per ASTM B33

    Revision: 3.0.00M