SPEC 60237

MC-AP™ Type MC All Purpose THHN/THWN Circuit Size Copper Conductor 277/480V Colors

Copper THHN Insulated Conductors. Full-Sized Aluminum Equipment Grounding/Bonding Conductor. UL Listed 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Binder:Mylar tape
  4. Ground:Full-sized bare 8000 series aluminum grounding/bonding conductor. Armor and bare aluminum conductor form the equipment ground path.
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi- residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS -- ARMOR IS EQUIPMENT GROUNDING PATH COMPONENT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessDiameter Over ArmorCopper WeightOverall Weight
    AWG/Kcmilinchmilsinchlbs/1000ftlbs/1000ft
    12 AWG | Solid
    555542123OE,YW,GY0.08Solid200.51259118
    555726122BN,GY0.080Solid200.4873992
    555538122OE,GY0.080Solid200.4933992
    555539122YW,GY0.080Solid200.4933992
    555541123BN,YW,GY0.080Solid200.50659117
    555728123BN,OE,GY0.080Solid200.51259118
    555731124BN,OE,YW,GY0.080Solid200.53879144
    12 AWG | 19 Strands
    596054122PE,WE0.08819200.5134096
    10 AWG | Solid
    555733102BN,GY0.101Solid250.55561130
    561000102YW,GY0.101Solid250.56161132
    560998102OE,GY0.101Solid250.56161132
    585574102BN,YW0.101Solid250.55561130
    555735103BN,OE,GY0.101Solid250.58092169
    582022104BN,OE,GY/BN,GY/OE0.101Solid250.706123219
    555737104BN,OE,YW,GY0.101Solid250.619123210
    582025106BN,OE,YW,GY/BN,GY/OE,GY/YW0.101Solid251.045185316
    10 AWG | 19 Strands
    561006102BN,GY0.11319250.58664139
    12 AWG | 19 Strands
    558790122OE,GY0.09019200.5074095
    558743122BN,GY0.09019200.5074095
    558793122YW,GY0.09019200.5074095
    558745123BN,OE,YW0.09019200.52860122
    558747124BN,OE,YW,GY0.09019200.56280151
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | Solid
    1233.61.6622.0020.0542024
    1223.41.6622.0020.0542530
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    1233.51.6622.0020.0542530
    1233.61.6622.0020.0542530
    1243.81.6622.0020.0542024
    12 AWG | 19 Strands
    1223.61.6622.0020.0542530
    10 AWG | Solid
    1023.91.0401.2530.0503540
    1023.91.041.2530.053540
    1023.91.041.2530.053540
    1023.91.041.2530.053540
    1034.11.0401.2530.0503540
    1044.91.041.2530.052832
    1044.31.0401.2530.0502832
    1067.31.041.2530.052428
    10 AWG | 19 Strands
    1024.11.041.2530.053540
    12 AWG | 19 Strands
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    1233.71.6622.0020.0542530
    1243.91.6622.0020.0542024
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC

    MCAP Savings Calculator
    QR Code