SPEC 60007

SIMpull Type MC®THHN/THWN Circuit Size Copper Conductor 277/480V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Anti-Short bushing not required

  • Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    TBA144BN/OE/YW/GY0.064Solid201x140.508116
    TBA122PE/GY0.080Solid201x120.487107
    TBA122OE/GY0.080Solid201x120.487107
    TBA122BN/GY0.080Solid201x120.487107
    TBA122YW/GY0.080Solid201x120.487107
    TBA123OE/YW/GY0.080Solid201x120.518134
    TBA123BN/OE/GY0.080Solid201x120.518134
    TBA123BN/YW/GY0.080Solid201x120.518134
    TBA124BN/OE/YW/GY0.080Solid201x120.553162
    TBA102BN/GY0.101Solid251x100.554154
    TBA102YW/GY0.101Solid251x100.554154
    TBA102BN/GY0.101Solid251x100.554154
    TBA103BN/OE/GY0.101Solid251x100.593194
    TBA104BN/OE/YW/GY0.101Solid251x100.637235
    TBA122BN/GY0.09019201x120.508112
    TBA122YW/GY0.09019201x120.508112
    TBA122OE/GY0.09019201x120.508112
    TBA123BN/OE/GY0.09019201x120.542140
    TBA102BN/GY0.11719251x100.587166
    TBA103BN/OE/GY0.11719251x100.630209
    TBA104BN/OE/YW/GY0.11719251x100.678254
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin. Bend Radius*DC Resistance at 25°CAC Resistance at 75°CAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA◊143.52.6313.170121620
    TBA◊123.41.6622.002202530
    TBA◊123.41.6622.002202530
    TBA◊123.41.6622.002202530
    TBA◊123.41.6622.002202530
    TBA◊123.61.6622.002202530
    TBA◊123.61.6622.002202530
    TBA◊123.61.6622.002202530
    TBA◊123.81.6622.002162024
    TBA◊103.81.041.253303540
    TBA◊103.81.041.253303540
    TBA◊103.81.041.253303540
    TBA◊104.11.041.253303540
    TBA◊104.41.041.253242832
    TBA◊123.51.6622.002202530
    TBA◊123.51.6622.002202530
    TBA◊123.51.6622.002202530
    TBA◊123.71.6622.002202530
    TBA◊104.11.041.253303540
    TBA◊104.41.041.253303540
    TBA◊104.71.041.253242832
    Ampacities have been adjusted for more than Three Current-Carrying Conductors
    Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 3.0.00C