SPEC 60001

SIMpull MC™ THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Low Profile Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape with print legend wrapped around assembly.
  5. Armor:Low Profile Aluminum Interlocked Armor

Applications and Features:

  • Southwire SIMpull MC Cable is suitable for use as follows:
  • Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Anti-Short bushing not required

  • Southwire SIMpull MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    137914142BK/WE0.064Solid201x140.41576
    TBA143BK/WE/BE0.064Solid201x140.44298
    665383143BK/WE/RD0.064Solid201x140.44294
    TBA144BK/RD/BE/WE0.064Solid201x140.508116
    665378122BE/WE0.080Solid201x120.451104
    137912122BK/WE0.080Solid201x120.451104
    665377122RD/WE0.080Solid201x120.451104
    137918122BN/GY0.080Solid201x120.451104
    665381122OE/GY0.080Solid201x120.451104
    665382122YW/GY0.080Solid201x120.451104
    665387123BN/OE/GY0.080Solid201x120.482129
    665436123BK/RD/BE0.080Solid201x120.482129
    137913123BK/RD/WE0.080Solid201x120.482129
    665384124BK/RD/BE/WE0.080Solid201x120.517156
    TBA124BK/RD/BE/WE0.080Solid201x120.553162
    665379102RD/WE0.101Solid251x100.518148
    TBA102BE/WE0.101Solid251x100.554154
    665380102BN/GY0.101Solid251x100.518147
    137917102BK/WE0.101Solid251x100.518147
    137916103BK/RD/WE0.101Solid251x100.557188
    TBA104BK/RD/BE/WE0.101Solid251x100.637235
    TBA142BK/WE0.07319201x140.46883
    TBA143BK/WE/RD0.07319201x140.497103
    137915122BK/WE0.09019201x120.472107
    665385123BK/RD/WE0.09019201x120.506135
    TBA124BK/RD/BE/WE0.09019201x120.580169
    665386102BK/WE0.11719251x100.551160
    TBA103BK/RD/BE0.11719251x100.630209
    TBA104BK/RD/BE/WE0.11719251x100.678254
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1423.12.6313.1700.032152025
    1433.32.6313.1700.032152025
    1433.12.6313.1700.040152025
    1443.52.6313.1700.040121620
    1223.41.6622.0020.030202530
    1223.41.6622.0020.030202530
    1223.41.6622.0020.030202530
    1223.41.6622.0020.030202530
    1223.41.6622.0020.030202530
    1223.41.6622.0020.030202530
    1233.61.6622.0020.030202530
    1233.61.6622.0020.030202530
    1233.61.6622.0020.030202530
    1243.51.6622.0020.039162024
    1243.81.6622.0020.038162024
    1023.81.0401.2530.030303540
    1023.81.0401.2530.030303540
    1023.81.0401.2530.030303540
    1023.81.0401.2530.030303540
    1034.11.0401.2530.030303540
    1044.41.0401.2530.038242832
    1423.22.6313.1700.031152025
    1433.42.6313.1700.031152025
    1223.51.6622.0020.030202530
    1233.71.6622.0020.030202530
    1244.01.6622.0020.038162024
    1024.11.0401.2530.029303540
    1034.41.0401.2530.029303540
    1044.71.0401.2530.037242832
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.012