SPEC 45252

CU 600/1000V XLPE Insulation PVC Jacket. XHHW-2

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    Bare Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C

    Green Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    5551968370.14145600.627154283
    4805908370.14145600.682186322
    5551956370.17745600.704245386
    4806086370.17745600.782297466
    4806164370.22545600.806441612
    4806242370.28245800.974702920
    48063213190.32255801.1068641142
    4806401/03190.36155801.19210691408
    4806572/03190.40555801.28713261713
    4806653/03190.45655801.39116992054
    4806734/03190.51255801.49421092502
    4806812503370.55865801.61124692928
    6722063503370.661651101.88535354300
    4807073503370.661651101.89834384105
    5880133503370.661651102.08137974578
    4807154003370.705651102.02539064726
    4807235003370.789651102.15548845676
    8901485003370.789651102.15550075904
    5836975003370.789651102.26250926073
    5931736003610.865801102.43661367248
    TBA6003610.865801102.44658156970
    8903886003610.865801102.45358206795
    6722106003610.865801102.56663927564
    5893597503610.968801102.65676768955
    5544107503610.968801102.65672778557
    TBA10003611.117801403.038968411368
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    555196832.53960.6530.7860.052405055
    480590832.73960.6530.7860.052405055
    555195632.86290.4110.4950.051556575
    480608633.16290.4110.4950.051556575
    480616433.210010.2580.3100.048708595
    480624233.815920.1620.1950.04595115130
    480632135.520080.1280.1540.046110130145
    4806401/035.925340.1020.1220.044125150170
    4806572/036.431940.0810.0970.043145175195
    4806653/036.940270.0640.0780.042165200225
    4806734/037.450780.0510.0620.041195230260
    48068125038.060000.0430.0530.041215255290
    67220635039.484000.0310.0390.040260310350
    48070735039.484000.0310.0390.040260310350
    588013350312.484000.0310.0390.040260310350
    480715400312.196000.0270.0350.040280335380
    480723500312.9100000.0220.0290.039320380430
    890148500312.9100000.0220.0290.039320380430
    583697500313.5100000.0220.0290.039320380430
    593173600314.6100000.0180.0250.039350420475
    TBA600314.6100000.0180.0250.039350420475
    890388600314.7100000.0180.0250.039350420475
    672210600315.3100000.0180.0250.039350420475
    589359750315.9100000.0140.0220.038400475535
    554410750315.9100000.0140.0220.038400475535
    TBA1000318.2100000.0110.0180.037455545615
    *Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.002

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC