SPEC 80213

35kV AL 100% TRXLPE One-Third (Based on Short Circuit) Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
  • Not recommended for use above 90ºC in wind farm applications

Specifications:

  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA1/0 (19)0.3611.0893451.1996x140.438501.42784611.4633
    TBA3/0 (19)0.4431.1713451.2819x140.292501.509100712.11006
    TBA250 (37)0.5581.2943451.40413x140.202751.682131713.51500
    662829^750 (61)0.9681.7083451.84824x120.069752.163244117.34500
    662818^1000 (61)1.1171.8573451.99720x100.052752.354302118.86000
    662816^1250 (61)1.2502.0003452.14025x100.041752.497353420.07500
    6638361250 (61)1.2502.0003452.14025x100.041752.497353420.07500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.1670.2110.0740.0530.1553.130.265 + j0.7470.211 + j0.0543103160195
    3/0 (19)0.1050.1320.0660.0500.1763.550.186 + j0.7400.132 + j0.0504655210250
    250 (37)0.0710.0900.0570.0470.2044.120.144 + j0.730.090 + j0.0476724257302
    750 (61)0.0240.0330.0380.0400.3006.060.087 + j0.7050.033 + j0.04019725470530
    1000 (61)0.0180.0260.0340.0390.3356.760.080 + j0.6980.026 + j0.03926129530585
    1250 (61)0.0140.0230.0310.0380.3657.370.077 + j0.4370.023 - j0.21832661
    1250 (61)0.0140.0230.0310.0380.3657.370.077 + j0.4370.023 - j0.21832661
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA1/0 (19)9.1727.668.7630.456x141.441.2736.251259289.562817
    TBA3/0 (19)11.2529.748.7632.549x140.961.2738.331499307.344477
    TBA250 (37)14.1732.878.7635.6613x140.661.9142.721960342.906675
    662829^750 (61)24.5943.388.7646.9424x120.231.9154.943633439.4220025
    662818^1000 (61)28.3747.178.7650.7220x100.171.9159.794496477.5226700
    662816^1250 (61)31.7550.808.7654.3625x100.131.9163.425259508.0033375
    6638361250 (61)31.7550.808.7654.3625x100.131.9163.425259508.0033375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.54790.690.02260.17390.50910.26900.265 + j0.7470.211 + j0.0543103160195
    3/0 (19)0.34450.430.02010.16400.57711.64700.186 + j0.7400.132 + j0.0504655210250
    250 (37)0.23290.300.01740.15420.66913.51710.144 + j0.730.090 + j0.0476724257302
    750 (61)0.07870.110.01160.13120.98419.88190.087 + j0.7050.033 + j0.04019725470530
    1000 (61)0.05910.090.01040.12801.09922.17850.080 + j0.6980.026 + j0.03926129530585
    1250 (61)0.04590.080.00940.12471.19824.17980.077 + j0.4370.023 - j0.21832661
    1250 (61)0.04590.080.00940.12471.19824.17980.077 + j0.4370.023 - j0.21832661
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.