SPEC 80212
35kV AL 100% TRXLPE One-Half Neutral (Based on Short Circuit) Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Half Copper Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied One-Half Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
- Not recommended for use above 90ºC in wind farm applications
Specifications:
Sample Print Legend:
SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
Table 1 – Weights and Measurements
Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb |
1/0 (19) | 0.361 | 1.089 | 345 | 1.199 | 8x14 | 0.328 | 50 | 1.427 | 873 | 11.4 | 633 |
2/0 (19) | 0.395 | 1.123 | 345 | 1.233 | 10x14 | 0.263 | 50 | 1.461 | 951 | 11.7 | 798 |
3/0 (19) | 0.443 | 1.171 | 345 | 1.281 | 13x14 | 0.202 | 50 | 1.509 | 1061 | 12.1 | 1006 |
250 (37) | 0.558 | 1.294 | 345 | 1.404 | 19x14 | 0.138 | 75 | 1.682 | 1398 | 13.5 | 1500 |
350 (37) | 0.661 | 1.397 | 345 | 1.507 | 11x10 | 0.094 | 75 | 1.861 | 1697 | 14.9 | 2100 |
500 (37) | 0.789 | 1.525 | 345 | 1.665 | 15x10 | 0.069 | 75 | 2.019 | 2120 | 16.2 | 3000 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | A/1000ft | W/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (19) | 0.167 | 0.211 | 0.074 | 0.053 | 0.155 | 3.13 | 0.265 + j0.747 | 0.211 + j0.054 | 4138 | 160 | 195 |
2/0 (19) | 0.133 | 0.167 | 0.071 | 0.052 | 0.164 | 3.31 | 0.221 + j0.744 | 0.167 + j0.051 | 5173 | 185 | 220 |
3/0 (19) | 0.105 | 0.132 | 0.066 | 0.050 | 0.176 | 3.55 | 0.186 + j0.740 | 0.132 + j0.050 | 6724 | 210 | 250 |
250 (37) | 0.071 | 0.090 | 0.057 | 0.047 | 0.204 | 4.12 | 0.144 + j0.730 | 0.090 + j0.047 | 9828 | 302 | |
350 (37) | 0.050 | 0.065 | 0.050 | 0.045 | 0.229 | 4.62 | 0.119 + j0.721 | 0.065 + j0.046 | 14371 | 315 | 370 |
500 (37) | 0.035 | 0.046 | 0.044 | 0.043 | 0.260 | 5.25 | 0.100 + j0.713 | 0.046 + j0.043 | 19597 | 380 | 435 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton |
1/0 (19) | 9.17 | 27.66 | 8.76 | 30.45 | 8x14 | 1.08 | 1.27 | 36.25 | 1299 | 289.56 | 2817 |
2/0 (19) | 10.03 | 28.52 | 8.76 | 31.32 | 10x14 | 0.86 | 1.27 | 37.11 | 1415 | 297.18 | 3551 |
3/0 (19) | 11.25 | 29.74 | 8.76 | 32.54 | 13x14 | 0.66 | 1.27 | 38.33 | 1579 | 307.34 | 4477 |
250 (37) | 14.17 | 32.87 | 8.76 | 35.66 | 19x14 | 0.45 | 1.91 | 42.72 | 2080 | 342.90 | 6675 |
350 (37) | 16.79 | 35.48 | 8.76 | 38.28 | 11x10 | 0.31 | 1.91 | 47.27 | 2525 | 378.46 | 9345 |
500 (37) | 20.04 | 38.73 | 8.76 | 42.29 | 15x10 | 0.23 | 1.91 | 51.28 | 3155 | 411.48 | 13350 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | A/km | W/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (19) | 0.5479 | 0.69 | 0.0226 | 0.1739 | 0.509 | 10.2690 | 0.265 + j0.747 | 0.211 + j0.054 | 4138 | 160 | 195 |
2/0 (19) | 0.4364 | 0.55 | 0.0216 | 0.1706 | 0.538 | 10.8596 | 0.221 + j0.744 | 0.167 + j0.051 | 5173 | 185 | 220 |
3/0 (19) | 0.3445 | 0.43 | 0.0201 | 0.1640 | 0.577 | 11.6470 | 0.186 + j0.740 | 0.132 + j0.050 | 6724 | 210 | 250 |
250 (37) | 0.2329 | 0.30 | 0.0174 | 0.1542 | 0.669 | 13.5171 | 0.144 + j0.730 | 0.090 + j0.047 | 9828 | 302 | |
350 (37) | 0.1640 | 0.21 | 0.0152 | 0.1476 | 0.751 | 15.1575 | 0.119 + j0.721 | 0.065 + j0.046 | 14371 | 315 | 370 |
500 (37) | 0.1148 | 0.15 | 0.0134 | 0.1411 | 0.853 | 17.2244 | 0.100 + j0.713 | 0.046 + j0.043 | 19597 | 380 | 435 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.003
Updated On: Dec. 4, 2023, 9:12 p.m. UTC