SPEC 80211

35kV AL 100% TRXLPE Two-Thirds Neutral (Based on Short Circuit) Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. Two-Thirds Copper Concentric Neutral. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied Two-Thirds Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
  • Not recommended for use above 90ºC in wind farm applications

Specifications:

  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA1/0 (19)0.3611.0893451.19912x140.239501.42791311.4633
    TBA2/0 (19)0.3951.1233451.23314x140.187501.461100511.7798
    TBA3/0 (19)0.4431.1713451.28117x140.154501.509111512.11006
    TBA4/0 (19)0.4981.2263451.33621x140.125501.564125212.51269
    TBA250 (37)0.5581.2943451.40416x120.103751.716147913.71500
    TBA350 (37)0.6611.3973451.50722x120.075751.819178314.62100
    662828^350 (37)0.6611.3913451.50114x100.074751.858175514.92100
    TBA500 (37)0.7891.5253451.66532x120.051751.977228015.83000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.1670.2110.0740.0530.1553.130.265 + j0.7470.211 + j0.0545690160195
    2/0 (19)0.1330.1670.0710.0520.1643.310.221 + j0.7440.167 + j0.0517242185220
    3/0 (19)0.1050.1320.0660.0500.1763.550.186 + j0.7400.132 + j0.0508794210250
    4/0 (19)0.0840.1050.0610.0480.1903.830.159 + j0.7350.105 + j0.04810863235280
    250 (37)0.0710.0900.0570.0480.2044.120.144 + j0.7290.09 + j0.04813150302
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7220.065 + j0.04518081315370
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7210.065 + j0.04618290315370
    500 (37)0.0350.0460.0440.0430.2605.250.100 + j0.7140.046 + j0.04326300380435
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA1/0 (19)9.1727.668.7630.4512x140.781.2736.251359289.562817
    TBA2/0 (19)10.0328.528.7631.3214x140.611.2737.111496297.183551
    TBA3/0 (19)11.2529.748.7632.5417x140.511.2738.331659307.344477
    TBA4/0 (19)12.6531.148.7633.9321x140.411.2739.731863317.505647
    TBA250 (37)14.1732.878.7635.6616x120.341.9143.592201347.986675
    TBA350 (37)16.7935.488.7638.2822x120.251.9146.202653370.849345
    662828^350 (37)16.7935.338.7638.1314x100.241.9147.192612378.469345
    TBA500 (37)20.0438.738.7642.2932x120.171.9150.223393401.3213350
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.54790.690.02260.17390.50910.26900.265 + j0.7470.211 + j0.0545690160195
    2/0 (19)0.43640.550.02160.17060.53810.85960.221 + j0.7440.167 + j0.0517242185220
    3/0 (19)0.34450.430.02010.16400.57711.64700.186 + j0.7400.132 + j0.0508794210250
    4/0 (19)0.27560.340.01860.15750.62312.56560.159 + j0.7350.105 + j0.04810863235280
    250 (37)0.23290.300.01740.15750.66913.51710.144 + j0.7290.09 + j0.04813150302
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7220.065 + j0.04518081315370
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7210.065 + j0.04618290315370
    500 (37)0.11480.150.01340.14110.85317.22440.100 + j0.7140.046 + j0.04326300380435
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.