SPEC 80210

35kV AL 100% TRXLPE Full Neutral Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. Full Copper Concentric Neutrals. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied Full Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.

Specifications:

  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6262941/0 (19)0.3511.0723451.18219x160.220501.3838339.6633
    TBA1/0 (19)0.3511.0793451.18916x140.164501.4179739.9633
    TBA1/0 (19)0.3611.0893451.19916x140.164501.4279819.9633
    TBA2/0 (19)0.3951.1233451.23320x140.131501.461108610.2798
    TBA3/0 (19)0.4431.1713451.28125x140.105501.509122310.51006
    6638644/0 (19)0.4981.2183451.32824x140.109501.556120610.81269
    662826^4/0 (19)0.4981.2183451.32820x120.083501.589133211.11269
    TBA250 (37)0.5581.2943451.40425x120.066751.716166612.01500
    TBA350 (37)0.6611.3973451.50732x120.051751.819199112.72100
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.1670.2110.0760.0530.1533.090.265 + j0.7490.211 + j0.0536169160195
    1/0 (19)0.1670.2110.0760.0540.1533.090.265 + j0.7480.211 + j0.0538276160195
    1/0 (19)0.1670.2110.0740.0530.1553.130.265 + j0.7470.211 + j0.0548276160195
    2/0 (19)0.1330.1670.0710.0520.1643.310.221 + j0.7440.167 + j0.05110346185220
    3/0 (19)0.1050.1320.0660.0500.1763.550.186 + j0.7400.132 + j0.05012932210250
    4/0 (19)0.0840.1050.0610.0480.1903.830.159 + j0.7350.105 + j0.04812415240280
    4/0 (19)0.0840.1050.0610.0490.1903.830.159 + j0.7340.105 + j0.04816437240280
    250 (37)0.0710.0900.0570.0480.2044.120.144 + j0.7290.090 + j0.04820547261302
    350 (37)0.0500.0650.0500.0450.2294.620.119 + j0.7220.065 + j0.04526300315365
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6262941/0 (19)8.9227.238.7630.0219x160.721.2735.131240243.842817
    TBA1/0 (19)8.9227.418.7630.2016x140.541.2735.991448251.462817
    TBA1/0 (19)9.1727.668.7630.4516x140.541.2736.251460251.462817
    TBA2/0 (19)10.0328.528.7631.3220x140.431.2737.111616259.083551
    TBA3/0 (19)11.2529.748.7632.5425x140.341.2738.331820266.704477
    6638644/0 (19)12.6530.948.7633.7324x140.361.2739.521795274.325647
    662826^4/0 (19)12.6530.948.7633.7320x120.271.2740.361982281.945647
    TBA250 (37)14.1732.878.7635.6625x120.221.9143.592479304.806675
    TBA350 (37)16.7935.488.7638.2832x120.171.9146.202963322.589345
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Non-UL listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.54790.690.02320.17390.50210.13780.265 + j0.7490.211 + j0.0536169160195
    1/0 (19)0.54790.690.02320.17720.50210.13780.265 + j0.7480.211 + j0.0538276160195
    1/0 (19)0.54790.690.02260.17390.50910.26900.265 + j0.7470.211 + j0.0548276160195
    2/0 (19)0.43640.550.02160.17060.53810.85960.221 + j0.7440.167 + j0.05110346185220
    3/0 (19)0.34450.430.02010.16400.57711.64700.186 + j0.7400.132 + j0.05012932210250
    4/0 (19)0.27560.340.01860.15750.62312.56560.159 + j0.7350.105 + j0.04812415240280
    4/0 (19)0.27560.340.01860.16080.62312.56560.159 + j0.7340.105 + j0.04816437240280
    250 (37)0.23290.300.01740.15750.66913.51710.144 + j0.7290.090 + j0.04820547261302
    350 (37)0.16400.210.01520.14760.75115.15750.119 + j0.7220.065 + j0.04526300315365
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.