SPEC 45411
CU 2000V XLPE Insulation. RHH/RHW-2 PV
Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 14 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

Construction:
- Conductor:Stranded bare copper per ASTM B3 and ASTM B8 or ASTM B787
- Insulation:Cross Linked Polyethylene (XLPE). Colors available upon request.
Applications and Features:
Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Sample Print Legend:
SOUTHWIRE E316464 {UL} PV WIRE XX AWG (XXX.XX{mm2}) CU 2000V 90{D}C WET OR DRY -40{D}C SUN RES DIRECT BURIAL VW-1 OR RHW-2 2000V --- RoHS {MMM/DD/YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
597961 | 14 | 19 | 0.070 | 75 | 0.224 | 13 | 30 |
597958 | 12 | 19 | 0.088 | 75 | 0.243 | 20 | 39 |
579962 | 10 | 19 | 0.113 | 75 | 0.263 | 32 | 53 |
569037* | 8 | 19 | 0.134 | 85 | 0.313 | 50 | 79 |
569039* | 6 | 19 | 0.169 | 85 | 0.349 | 81 | 114 |
569040* | 4 | 19 | 0.212 | 85 | 0.396 | 128 | 166 |
569041* | 2 | 19 | 0.268 | 85 | 0.456 | 204 | 250 |
TBA | 1 | 19 | 0.298 | 105 | 0.508 | 259 | 328 |
569043 | 1/0 | 19 | 0.336 | 105 | 0.570 | 326 | 396 |
569044 | 2/0 | 19 | 0.376 | 105 | 0.614 | 426 | 504 |
569045 | 3/0 | 19 | 0.422 | 105 | 0.664 | 518 | 604 |
569047 | 4/0 | 19 | 0.474 | 105 | 0.720 | 655 | 752 |
679559 | 250 | 37 | 0.520 | 120 | 0.782 | 772 | 897 |
653096 | 300 | 37 | 0.611 | 120 | 0.851 | 926 | 1052 |
590138 | 350 | 37 | 0.615 | 120 | 0.901 | 1080 | 1215 |
578324 | 500 | 37 | 0.735 | 120 | 1.006 | 1543 | 1685 |
672530 | 600 | 61 | 0.812 | 135 | 1.136 | 1852 | 2042 |
TBA | 750 | 61 | 0.908 | 135 | 1.178 | 2316 | 2546 |
TBA | 1000 | 61 | 1.060 | 135 | 1.330 | 3086 | 3350 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
597961 | 14 | 1.8 | 33 | 2.631 | 3.423 | 0.058 | 15 | 20 | 25 |
597958 | 12 | 1.9 | 52 | 1.630 | 2.002 | 0.054 | 20 | 25 | 30 |
579962 | 10 | 2.1 | 83 | 1.020 | 1.250 | 0.050 | 30 | 35 | 40 |
569037* | 8 | 2.5 | 132 | 0.654 | 0.787 | 0.052 | 40 | 50 | 55 |
569039* | 6 | 2.8 | 210 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
569040* | 4 | 3.2 | 334 | 0.258 | 0.310 | 0.048 | 70 | 85 | 95 |
569041* | 2 | 3.6 | 531 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
TBA | 1 | 4.1 | 670 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
569043 | 1/0 | 4.6 | 845 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
569044 | 2/0 | 4.9 | 1065 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
569045 | 3/0 | 5.3 | 1342 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
569047 | 4/0 | 5.8 | 1693 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
679559 | 250 | 6.2 | 2000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
653096 | 300 | 6.8 | 2400 | 0.036 | 0.047 | 0.029 | 240 | 285 | 320 |
590138 | 350 | 7.2 | 2800 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
578324 | 500 | 8.0 | 4000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
672530 | 600 | 9.1 | 4800 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
TBA | 750 | 9.4 | 6000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
TBA | 1000 | 10.6 | 8000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Inductive Reactance is based on non-ferrous conduit with one diameter spacing.
*VW-1 Rated
Inductive Reactance is based on non-ferrous conduit with one diameter spacing.
*VW-1 Rated
Stock Code Colors
Size | Black | White | Red | Green | Green/Yellow |
---|---|---|---|---|---|
AWG/Kcmil | ![]() | ![]() | ![]() | ![]() | ![]() |
14 | 597961 | ||||
12 | 597958 | 596376 | 596377 | ||
10 | 579962 | 583665 | 583687 | ||
1/0 | 569043 | 677562 | |||
2/0 | 569044 | ||||
3/0 | 569045 | ||||
4/0 | 569047 | ||||
250 | 679559 | ||||
300 | 653096 | 599400 | 599401 | ||
350 | 590138 | ||||
500 | 578324 | ||||
600 | 672530 |
Stock Code Colors (VW-1)
Size | Black | White | Red | Green | Green/Yellow |
---|---|---|---|---|---|
AWG/Kcmil | ![]() | ![]() | ![]() | ![]() | ![]() |
10 | 568110 | 577645 | |||
8 | 569037 | 585080 | 589110 | ||
6 | 569039 | 671956 | 585840 | ||
4 | 569040 | 673880 | 653094 | ||
2 | 569041 |
Revision: 1.000.006
Updated On: Sept. 23, 2023, 4:37 p.m. UTC