SPEC 87000
SIMpull® CABLE-IN-CONDUIT

Construction:
• Manufactured by continuously extruding HDPE loosely around the cable assembly with no adhesion between the conduit and the cable, thus leaving the cables free in the conduit.
• Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.
• All cables are installed as single conductors or paralleled in HDPE conduit and are available in Standard Wall, Schedule 40, Schedule 80, SDR 13.5, SDR 11, and EPEC-17.
• Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.
• All cables are installed as single conductors or paralleled in HDPE conduit and are available in Standard Wall, Schedule 40, Schedule 80, SDR 13.5, SDR 11, and EPEC-17.
Applications and Features:
Commonly installed from transformer to transformer or as underground cables exiting substations
Specifications:
EPEC-17 (SDR 17)
NOMINAL SIZE | NOMINAL OUTSIDE DIAMETER | MINIMUM WALL THICKNESS | NOMINAL INSIDE DIAMETER | MINIMUM BENDING RADIUS | MAXIMUM PULLING TENSION | WEIGHT |
---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lbs | lbs/1000’ |
0.75 | 1.05 | 0.062 | 0.906 | 12 | 410 | 92 |
1 | 1.315 | 0.077 | 1.141 | 14 | 635 | 140 |
1.25 | 1.66 | 0.098 | 1.444 | 18 | 1020 | 219 |
1.5 | 1.9 | 0.112 | 1.656 | 21 | 1335 | 284 |
2 | 2.375 | 0.14 | 2.075 | 26 | 2090 | 437 |
2.5 | 2.875 | 0.169 | 2.517 | 32 | 3060 | 632 |
3 | 3.5 | 0.206 | 3.063 | 39 | 4525 | 939 |
EPEC 13.5 (SDR 13.5)
NOMINAL SIZE | NOMINAL OUTSIDE DIAMETER | MINIMUM WALL THICKNESS | NOMINAL INSIDE DIAMETER | MINIMUM BENDING RADIUS | MAXIMUM PULLING TENSION | WEIGHT |
---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lbs | lbs/1000’ |
0.75 | 1.05 | 0.078 | 0.874 | 12 | 505 | 111 |
1 | 1.315 | 0.097 | 1.101 | 14 | 790 | 169 |
1.25 | 1.66 | 0.123 | 1.394 | 18 | 1260 | 266 |
1.5 | 1.9 | 0.141 | 1.598 | 21 | 1655 | 346 |
2 | 2.375 | 0.176 | 2.002 | 26 | 2585 | 534 |
2.5 | 2.875 | 0.213 | 2.423 | 32 | 3785 | 784 |
3 | 3.5 | 0.259 | 2.951 | 39 | 5610 | 1159 |
4 | 4.5 | 0.333 | 3.794 | 50 | 9265 | 1916 |
EPEC 11 (SDR 11)
NOMINAL SIZE | NOMINAL OUTSIDE DIAMETER | MINIMUM WALL THICKNESS | NOMINAL INSIDE DIAMETER | MINIMUM BENDING RADIUS | MAXIMUM PULLING TENSION | WEIGHT |
---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lbs | lbs/1000’ |
0.75 | 1.05 | 0.095 | 0.84 | 12 | 605 | 130 |
1 | 1.315 | 0.12 | 1.055 | 14 | 960 | 202 |
1.25 | 1.66 | 0.151 | 1.338 | 18 | 1520 | 316 |
1.5 | 1.9 | 0.173 | 1.533 | 21 | 1995 | 412 |
2 | 2.375 | 0.216 | 1.917 | 26 | 3125 | 643 |
2.5 | 2.875 | 0.261 | 2.322 | 32 | 4550 | 941 |
3 | 3.5 | 0.318 | 2.826 | 39 | 6760 | 1395 |
4 | 4.5 | 0.409 | 3.633 | 50 | 11170 | 2308 |
EPEC 40 (Schedule 40)
NOMINAL SIZE | NOMINAL OUTSIDE DIAMETER | MINIMUM WALL THICKNESS | NOMINAL INSIDE DIAMETER | MINIMUM BENDING RADIUS | MAXIMUM PULLING TENSION | WEIGHT |
---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lbs | lbs/1000’ |
0.75 | 1.05 | 0.113 | 0.804 | 12 | 710 | 149 |
1 | 1.315 | 0.133 | 1.029 | 14 | 1050 | 219 |
1.25 | 1.66 | 0.14 | 1.36 | 18 | 1420 | 297 |
1.5 | 1.9 | 0.145 | 1.59 | 21 | 1700 | 354 |
2 | 2.375 | 0.154 | 2.047 | 26 | 2280 | 475 |
2.5 | 2.875 | 0.203 | 2.445 | 32 | 3615 | 749 |
3 | 3.5 | 0.216 | 3.042 | 39 | 4740 | 981 |
4 | 4.5 | 0.237 | 3.998 | 50 | 6745 | 1396 |
EPEC 80 (Schedule 80)
NOMINAL SIZE | NOMINAL OUTSIDE DIAMETER | MINIMUM WALL THICKNESS | NOMINAL INSIDE DIAMETER | MINIMUM BENDING RADIUS | MAXIMUM PULLING TENSION | WEIGHT |
---|---|---|---|---|---|---|
inch | inch | inch | inch | inch | lbs | lbs/1000’ |
0.75 | 1.05 | 0.154 | 0.722 | 12 | 920 | 190 |
1 | 1.315 | 0.179 | 0.936 | 14 | 1360 | 279 |
1.25 | 1.66 | 0.191 | 1.255 | 18 | 1870 | 386 |
1.5 | 1.9 | 0.2 | 1.476 | 21 | 2275 | 468 |
2 | 2.375 | 0.218 | 1.913 | 26 | 3145 | 648 |
2.5 | 2.875 | 0.276 | 2.29 | 32 | 4780 | 989 |
3 | 3.5 | 0.3 | 2.864 | 39 | 6420 | 1325 |
4 | 4.5 | 0.337 | 3.786 | 50 | 9365 | 1936 |
Options
• 600 V, MV, Fiber, and Specialty Cables
• Available with UL marking on 3/4" through 4" Schedule 40 & 80 conduit
• Color options available: black, red, orange, gray. Striping is also available.
• Available with UL marking on 3/4" through 4" Schedule 40 & 80 conduit
• Color options available: black, red, orange, gray. Striping is also available.
Color Options
Conduit | Fiber Optic Cable | Colors | orange |
---|---|---|---|
CATV/Telephone | orange | ||
Electric | black, gray, red |
Other Properties
Property | Test Method | Value |
---|---|---|
Density | D4883 | .953 g/cc |
Melt Index | D1238 | .25 g/10 min |
Flexural Modulus | D790 | 168,000 psi |
Tensile Strength | D638 | 3900 yield @ 2 in/min |
SP-NCLS ESCR | F2136 | >1000 hrs |
Hydrostatic Design Basis | D2837 | N/A |
Revision: