SPEC 87019

Cable-in-Conduit (CIC) AL 15kV UD Primary SCH 40

...

Construction:

• Manufactured by continuously extruding HDPE loosely around the cable assembly with no adhesion between the conduit and the cable, thus leaving the cables free in the conduit.
• Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.
• Other constructions are available upon request.

Applications and Features:

Commonly installed from transformer to transformer or as underground cables exiting substations.

Specifications:

  • ASTM D3350 Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
  • ASTM D3485 Standard Specification for Coilable High Density Polyethylene (HDPE) Cable in Conduit (CIC)
  • ASTM F2160 Standard Specification for Solid Wall High Density Polyethylene (HDPE) Conduit Based on Controlled Outside Diameter (OD)
  • UL 1990 Standard for Nonmetallic Underground Conduit with Conductors
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    {SQFTG} FEET (LOGO) SOUTHWIRE CABLE IN CONDUIT (UL) HDPE X.XX" SCH40 NEMA TC 7 / ASTM F2160 (NESC) {MMM/DD/YYYY} {MACH/SHFT/OP}
    Table 1 – Physical and Electrical Data
    Stock NumberDescriptionCable ColorDuct Nominal SizeDuct Nominal Outside Dia.Duct Min. Wall ThicknessDuct Nominal Inside Dia.Duct Min. Bending RadiusDuct Max. Pull TensionDuct ColorApprox. Cable and Duct Weight
    inchinchinchinchinchlblb/1000ft
    6301351 x #2 AWG STR AL 220 mil 15kV Primary UDBK/RD Stripe1.501.9000.1451.590211700BK/3-RD Stripes888
    6169901 x #2 AWG SOL AL 175 mil 15kV Primary UDBK/RD Stripe1.501.9000.1451.590211700BK/3-RD Stripes826
    6304741 x #2 AWG SOL AL 220 mil 15kV Primary UDBK/RD Stripe1.501.9000.1451.590211700BK/3-RD Stripes865
    6343681 x 4/0 AWG STR AL 220 mi 15kV Primary UDBK/RD Stripe2.002.3750.1542.047262280RD1555
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Cable Specification

    Stock NumberCable Specification
    630135 / 634368 / 630474SPEC 81111
    616990SPEC 81101

    Cell Classification for HDPE Conduit

    PropertyTest MethodValue
    DensityD48830.953 g/cc
    Melt IndexD12380.25 g/10 min
    Flexural ModulusD790168,000 psi
    Tensile StrengthD6383900 yield @ 2 in/min
    SP-NCLS ESCRF2136>1000 hrs
    Hydrostatic Design BasisD2837N/A

  • (PE436580C-BK), (PE436580E-Colors)
  • Revision: 1.000.053

    Updated On: Dec. 31, 2023, 7:19 p.m. UTC