SPEC 46120
CU Compact 5/8kV NLEPR Insulation 133/100% IL SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Compact Copper, 5kV/8kV 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133%/100% Insulation Level, Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Construction:
- Conductor:Class B compact stranded per ASTM B496
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where supe- rior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE SIMpull{R} POWER CABLE {UL} XXX KCMIL CPT CU 115 MILS NL-EPR 5KV 133%/8KV 100% INS LEVEL 25%TS MV-105 FOR CT USE SUN RES (NESC) -- {CSA} XXX KCMIL CPT CU 2.92mm (115 mils) NL-EPR 5KV 133%/8KV 100% INS LEVEL 25%TS SR TC-ER 105{D}C FT4 -25{D}C LTDD -- PAT www.patentSW.com -- RoHS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size* |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb | inch | inch | |
TBA | 2 | 7 | 0.268 | 0.536 | 0.596 | 55 | 0.726 | 403 | 530 | 8.7 | 2.0 |
TBA | 1 | 19 | 0.298 | 0.566 | 0.626 | 55 | 0.756 | 468 | 669 | 9.0 | 2.5 |
TBA | 1/0 | 19 | 0.336 | 0.604 | 0.664 | 55 | 0.794 | 551 | 844 | 9.5 | 2.5 |
TBA | 2/0 | 19 | 0.376 | 0.644 | 0.704 | 80 | 0.884 | 694 | 1064 | 10.6 | 2.5 |
TBA | 3/0 | 19 | 0.422 | 0.690 | 0.750 | 80 | 0.930 | 821 | 1342 | 11.1 | 3.0 |
TBA | 4/0 | 19 | 0.474 | 0.742 | 0.802 | 80 | 0.982 | 980 | 1692 | 11.7 | 3.0 |
TBA | 250 | 37 | 0.520 | 0.796 | 0.856 | 80 | 1.036 | 1126 | 2000 | 12.4 | 3.0 |
TBA | 350 | 37 | 0.615 | 0.891 | 0.951 | 80 | 1.131 | 1477 | 2800 | 13.5 | 3.5 |
TBA | 500 | 37 | 0.735 | 1.011 | 1.071 | 80 | 1.251 | 1993 | 4000 | 15.0 | 3.5 |
679723 | 750 | 61 | 0.908 | 1.194 | 1.254 | 80 | 1.434 | 2922 | 6000 | 17.2 | 4.0 |
TBA | 1000 | 61 | 1.060 | 1.346 | 1.406 | 80 | 1.586 | 3696 | 8000 | 19.0 | 4.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.162 | 0.204 | 0.036 | 0.045 | 0.568 + j0.521 | 0.204 + j0.044 | 1877 | 145/155 | 190/215 |
1 | 0.128 | 0.162 | 0.033 | 0.043 | 0.529 + j0.503 | 0.162 + j0.042 | 1970 | 170/180 | 225/250 |
1/0 | 0.102 | 0.128 | 0.030 | 0.041 | 0.498 + j0.482 | 0.128 + j0.04 | 2088 | 195/210 | 260/290 |
2/0 | 0.081 | 0.102 | 0.028 | 0.041 | 0.472 + j0.46 | 0.102 + j0.04 | 2212 | 220/235 | 300/330 |
3/0 | 0.064 | 0.081 | 0.025 | 0.040 | 0.452 + j0.437 | 0.081 + j0.038 | 2354 | 250/270 | 345/385 |
4/0 | 0.051 | 0.065 | 0.023 | 0.038 | 0.436 + j0.413 | 0.065 + j0.037 | 2515 | 290/310 | 400/445 |
250 | 0.043 | 0.056 | 0.022 | 0.038 | 0.426 + j0.39 | 0.056 + j0.036 | 2683 | 320/345 | 445/495 |
350 | 0.031 | 0.041 | 0.019 | 0.036 | 0.406 + j0.352 | 0.042 + j0.034 | 2977 | 385/415 | 550/615 |
500 | 0.022 | 0.030 | 0.016 | 0.034 | 0.387 + j0.312 | 0.031 + j0.032 | 3349 | 470/505 | 695/775 |
750 | 0.014 | 0.023 | 0.014 | 0.032 | 0.364 + j0.261 | 0.024 + j0.031 | 3916 | 585/630 | 900/1000 |
1000 | 0.011 | 0.019 | 0.012 | 0.031 | 0.345 + j0.227 | 0.02 + j0.03 | 4387 | 670/720 | 1075/1200 |
* Ampacities are based on:
* For Duct: Table 310.60(C)(77) Detail 1.
* For Free Air: Table 310.60(C)(69).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(77) Detail 1.
* For Free Air: Table 310.60(C)(69).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
* Capacitive Reactance is between Phase-to-Shield.
Revision: 1.000.001
Updated On: Dec. 6, 2023, 8:01 p.m. UTC