SPEC 85047
Multi-Conductor CU 1000 V FR-XLPE Shielded Thermoset LSZH Jacket Control Cable Color Method 1 Table 1
Control Cable 1000 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shielding:5 mils tape shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket
Applications and Features:
Southwire’s 1000 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS SHIELDED 90C LSZH JACKET SUNLIGHT RESISTANT DIRECT BURIAL 1000V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C LSZH JACKET SUN RES FT-4 DIR BUR 1000V YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
14 AWG | |||||||||||||||||||
621894 | 14 | 7 | 7 | 0.07 | 30 | 60 | 0.626 | 127 | 266 | 2.631 | 3.17 | 7.5 | 10 | 14 | 17 | ||||
621892 | 14 | 12 | 7 | 0.07 | 30 | 60 | 0.819 | 206 | 418 | 2.631 | 3.17 | 9.8 | 7 | 10 | 12 | ||||
12 AWG | |||||||||||||||||||
6261720 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.679 | 182 | 338 | 1.662 | 2.002 | 8.1 | 14 | 17 | 21 | ||||
10 AWG | |||||||||||||||||||
621899 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.56 | 162 | 267 | 1.04 | 1.253 | 6.7 | 24 | 28 | 32 | ||||
621885 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.582 | 131 | 245 | 1.04 | 1.253 | 6.9 | 30 | 35 | 40 | ||||
6261520 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.633 | 171 | 299 | 1.04 | 1.253 | 7.5 | 24 | 28 | 32 | ||||
621887 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.751 | 272 | 452 | 1.04 | 1.253 | 9 | 21 | 24 | 28 | ||||
621883 | 10 | 10 | 7 | 0.113 | 30 | 80 | 0.992 | 383 | 669 | 1.04 | 1.253 | 11.9 | 15 | 17 | 20 | ||||
623760 | 10 | 12 | 7 | 0.113 | 30 | 80 | 1.02 | 450 | 766 | 1.04 | 1.253 | 12.2 | 15 | 17 | 20 | ||||
624410 | 6 | 4 | 7 | 0.177 | 45 | 80 | 0.883 | 379 | 641 | 0.411 | 0.495 | 10.5 | 44 | 52 | 60 | ||||
624409 | 2 | 2 | 7 | 0.282 | 45 | 80 | 0.962 | 471 | 692 | 0.162 | 0.195 | 11.5 | 95 | 115 | 130 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! Copper drain wire under tape shield
^ UL Listed part number
! Copper drain wire under tape shield
Revision: