SPEC 85021
Multi-Conductor CU 600 V FR-XLPE LCT Shielded PVC Jacket Control Cable Color Method 1 Table 2
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE {UL} XX AWG X/C FRXLP SHIELDED TYPE TC 600V PVC SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FRXLP SHIELDED TYPE TC 600V PVC SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
14 AWG | |||||||||||||||||||
6040590 | 14 | 4 | 7 | 0.07 | 30 | 45 | 0.498 | 84 | 165 | 2.631 | 3.17 | 5.9 | 12 | 16 | 20 | ||||
6040570 | 14 | 7 | 7 | 0.07 | 30 | 60 | 0.604 | 128 | 249 | 2.631 | 3.17 | 7.2 | 10 | 14 | 17 | ||||
6040560 | 14 | 12 | 7 | 0.07 | 30 | 60 | 0.76 | 203 | 383 | 2.631 | 3.17 | 9.1 | 7 | 10 | 12 | ||||
12 AWG | |||||||||||||||||||
6244570 | 12 | 12 | 7 | 0.088 | 30 | 80 | 0.876 | 299 | 543 | 1.662 | 2.002 | 10.5 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
6293830 | 10 | 2 | 7 | 0.113 | 30 | 60 | 0.572 | 95 | 192 | 1.04 | 1.253 | 6.8 | 30 | 35 | 40 | ||||
620886 | 10 | 3 | 7 | 0.113 | 30 | 60 | 0.589 | 135 | 251 | 1.04 | 1.253 | 7 | 30 | 35 | 40 | ||||
6040910 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.638 | 173 | 309 | 1.04 | 1.253 | 7.6 | 24 | 28 | 32 | ||||
6193800 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.655 | 173 | 308 | 1.04 | 1.253 | 7.8 | 24 | 28 | 32 | ||||
6293810 | 10 | 5 | 7 | 0.113 | 30 | 60 | 0.691 | 200 | 341 | 1.04 | 1.253 | 8.2 | 24 | 28 | 32 | ||||
6040960 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.734 | 259 | 429 | 1.04 | 1.253 | 8.8 | 21 | 24 | 28 | ||||
6293790 | 10 | 9 | 7 | 0.113 | 30 | 80 | 0.885 | 341 | 570 | 1.04 | 1.253 | 10.6 | 21 | 24 | 28 | ||||
6040930 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.975 | 421 | 701 | 1.04 | 1.253 | 11.7 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! Tinned Copper conductor per ASTM B33
^ UL Listed part number
! Tinned Copper conductor per ASTM B33
Revision: 3.0.00C