SPEC 85020
Multi-Conductor CU 600 V FR-XLPE Shielded PVC Jacket Control Cable Color Method 1 Table 2
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shielding:5 mils tape shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS 90{D}C PVC JKT TYPE TC-ER SHIELDED 600V SUN. RES. DIRECT BURIAL {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
14 AWG | |||||||||||||||||||
6236640 | 14 | 7 | 7 | 0.07 | 30 | 45 | 0.506 | 119 | 202 | 2.631 | 3.17 | 6 | 10 | 14 | 17 | ||||
12 AWG | |||||||||||||||||||
6625800 | 12 | 3 | 7 | 0.088 | 30 | 45 | 0.436 | 84 | 146 | 1.662 | 2.002 | 5.2 | 20 | 25 | 30 | ||||
6189280 | 12 | 4 | 7 | 0.088 | 30 | 45 | 0.469 | 108 | 175 | 1.662 | 2.002 | 5.6 | 16 | 20 | 24 | ||||
6189290 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.587 | 175 | 288 | 1.662 | 2.002 | 7 | 14 | 17 | 21 | ||||
6720880 | 12 | 9 | 7 | 0.088 | 30 | 60 | 0.685 | 221 | 361 | 1.662 | 2.002 | 8.2 | 14 | 17 | 21 | ||||
6041050 | 12 | 12 | 7 | 0.088 | 30 | 80 | 0.752 | 288 | 451 | 1.662 | 2.002 | 9 | 10 | 12 | 15 | ||||
6189300 | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.758 | 289 | 457 | 1.662 | 2.002 | 9 | 10 | 12 | 15 | ||||
620555 | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.768 | 278 | 542 | 1.662 | 2.002 | 9.2 | 10 | 12 | 15 | ||||
6188930 | 12 | 19 | 7 | 0.088 | 30 | 80 | 0.956 | 399 | 683 | 1.662 | 2.002 | 11.4 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
620680 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.45 | 91 | 147 | 1.04 | 1.253 | 5.4 | 30 | 35 | 40 | ||||
6041070 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.487 | 125 | 199 | 1.04 | 1.253 | 5.8 | 30 | 35 | 40 | ||||
6189320 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.558 | 160 | 262 | 1.04 | 1.253 | 6.6 | 24 | 28 | 32 | ||||
6206840 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.566 | 161 | 259 | 1.04 | 1.253 | 6.7 | 24 | 28 | 32 | ||||
6285070 | 10 | 5 | 7 | 0.113 | 30 | 60 | 0.615 | 194 | 307 | 1.04 | 1.253 | 7.3 | 24 | 28 | 32 | ||||
6189330 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.659 | 264 | 398 | 1.04 | 1.253 | 7.9 | 21 | 24 | 28 | ||||
6233050 | 10 | 8 | 7 | 0.113 | 30 | 60 | 0.72 | 301 | 452 | 1.04 | 1.253 | 8.6 | 21 | 24 | 28 | ||||
6206830 | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.779 | 330 | 505 | 1.04 | 1.253 | 9.3 | 21 | 24 | 28 | ||||
6189350 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.89 | 439 | 667 | 1.04 | 1.253 | 10.6 | 15 | 17 | 20 | ||||
6206810 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.903 | 441 | 678 | 1.04 | 1.253 | 10.8 | 15 | 17 | 20 | ||||
6285010 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.903 | 438 | 673 | 1.04 | 1.253 | 10.8 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! XHHW-2 Insulation
^ UL Listed part number
! XHHW-2 Insulation
Revision: 3.0.00C