SPEC 85012
Multi-Conductor CU 600 V PE/PVC Insulation PVC Jacket Power Cable Color Method 1 Table 1
Power Cable 600 Volt Copper Conductors, Polyethylene and Polyvinyl Chloride (PE/PVC) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Polyethylene (PE) and Polyvinyl Chloride (PVC)
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.
Specifications:
Sample Print Legend:
Non UL Listed
SOUTHWIRE XX AWG X/C PE/PVC CDRS 75C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |
617347^ | 9 | 2 | 19 | 0.126 | 25 | 45 | 0.472 | 77 | 136 | 0.825 | 0.994 | 1.8 | 0 | 0 | 0 |
617349^ | 9 | 4 | 19 | 0.126 | 25 | 60 | 0.581 | 154 | 250 | 0.825 | 0.994 | 2.3 | 0 | 0 | 0 |
617350^ | 9 | 8 | 19 | 0.126 | 25 | 60 | 0.753 | 309 | 451 | 0.825 | 0.994 | 3 | 0 | 0 | 0 |
606784 | 8 | 2 | 7 | 0.141 | 45 | 60 | 0.654 | 102 | 244 | 0.653 | 0.786 | 2.6 | 40 | 50 | 55 |
619121 | 8 | 2 | 7 | 0.141 | 45 | 60 | 0.658 | 102 | 224 | 0.653 | 0.786 | 2.6 | 40 | 50 | 55 |
618426 | 8 | 3 | 7 | 0.141 | 45 | 60 | 0.695 | 154 | 315 | 0.653 | 0.786 | 2.7 | 40 | 50 | 55 |
661502^ | 8 | 4 | 19 | 0.141 | 45 | 60 | 0.768 | 205 | 377 | 0.653 | 0.786 | 3 | 32 | 40 | 44 |
620288 | 8 | 5 | 7 | 0.141 | 45 | 80 | 0.883 | 257 | 489 | 0.653 | 0.786 | 3.5 | 32 | 40 | 44 |
606775 | 6 | 2 | 7 | 0.177 | 45 | 60 | 0.766 | 163 | 326 | 0.411 | 0.495 | 3 | 55 | 65 | 75 |
606763 | 6 | 3 | 7 | 0.177 | 45 | 60 | 0.808 | 245 | 444 | 0.411 | 0.495 | 3.2 | 55 | 65 | 75 |
619125 | 4 | 2 | 7 | 0.225 | 45 | 80 | 0.919 | 260 | 487 | 0.258 | 0.31 | 3.6 | 70 | 85 | 95 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ 19 strand combination unilay strand conductor per ASTM B787
^ 19 strand combination unilay strand conductor per ASTM B787
Revision: 3.0.00C