SPEC 85010
Multi-Conductor CU 600 V FR-XLPE Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT 600V SUNLIGHT RESISTANT MM/YYYY{SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
16 AWG | |||||||||||||||||||
673140 | 16 | 2 | 7 | 0.056 | 25 | 45 | 0.308 | 16 | 48 | 4.181 | 5.037 | 1.2 | 0 | 0 | 18 | ||||
619261 | 16 | 4 | 7 | 0.056 | 25 | 45 | 0.354 | 32 | 75 | 4.181 | 5.037 | 1.4 | 0 | 0 | 14 | ||||
604310 | 16 | 7 | 7 | 0.056 | 25 | 45 | 0.424 | 56 | 118 | 4.181 | 5.037 | 1.6 | 0 | 0 | 12 | ||||
619263 | 16 | 8 | 7 | 0.056 | 25 | 45 | 0.449 | 64 | 132 | 4.181 | 5.037 | 1.7 | 0 | 0 | 12 | ||||
14 AWG | |||||||||||||||||||
604210 | 14 | 2 | 7 | 0.07 | 30 | 45 | 0.357 | 25 | 64 | 2.631 | 3.17 | 1.4 | 15 | 20 | 25 | ||||
619930 | 14 | 12 | 7 | 0.07 | 30 | 60 | 0.663 | 153 | 291 | 2.631 | 3.17 | 2.6 | 7 | 10 | 12 | ||||
12 AWG | |||||||||||||||||||
604305 | 12 | 2 | 19 | 0.088 | 30 | 45 | 0.394 | 40 | 101 | 1.662 | 2.002 | 1.5 | 20 | 25 | 30 | ||||
6066720 | 12 | 2 | 7 | 0.088 | 30 | 45 | 0.4 | 40 | 87 | 1.662 | 2.002 | 1.6 | 20 | 25 | 30 | ||||
6168900 | 12 | 4 | 7 | 0.088 | 30 | 45 | 0.445 | 81 | 141 | 1.662 | 2.002 | 1.7 | 16 | 20 | 24 | ||||
6043070 | 12 | 4 | 19 | 0.088 | 30 | 45 | 0.46 | 81 | 153 | 1.662 | 2.002 | 1.8 | 16 | 20 | 24 | ||||
619308 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.561 | 142 | 246 | 1.662 | 2.002 | 2.2 | 14 | 17 | 21 | ||||
619937 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.569 | 142 | 251 | 1.662 | 2.002 | 2.2 | 14 | 17 | 21 | ||||
619939 | 12 | 9 | 7 | 0.088 | 30 | 60 | 0.655 | 183 | 311 | 1.662 | 2.002 | 2.6 | 14 | 17 | 21 | ||||
618414 | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.732 | 244 | 402 | 1.662 | 2.002 | 2.9 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
619943 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.44 | 64 | 118 | 1.04 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
6043010 | 10 | 2 | 19 | 0.113 | 30 | 45 | 0.44 | 64 | 117 | 1.04 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
6066710 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.448 | 64 | 129 | 1.04 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
618360 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.459 | 97 | 165 | 1.04 | 1.253 | 1.8 | 30 | 35 | 40 | ||||
619945 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.506 | 129 | 203 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
619240 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.506 | 129 | 202 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
604302 | 10 | 4 | 19 | 0.113 | 30 | 45 | 0.515 | 129 | 204 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
604219 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.637 | 226 | 349 | 1.04 | 1.253 | 2.5 | 21 | 24 | 28 | ||||
619950 | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.745 | 291 | 443 | 1.04 | 1.253 | 2.9 | 21 | 24 | 28 | ||||
622897 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.875 | 388 | 607 | 1.04 | 1.253 | 3.5 | 15 | 17 | 20 | ||||
604304 | 10 | 12 | 19 | 0.113 | 30 | 80 | 0.887 | 388 | 608 | 1.04 | 1.253 | 3.5 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! 19 strand combination unilay copper conductor based on ASTM B787
^ UL Listed part number
! 19 strand combination unilay copper conductor based on ASTM B787
Revision: 3.0.00C