SPEC 85008
Multi-Conductor CU 600 V FR-XLPE Thermoset CPE-TS Jacket Control Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoset Chlorinated Polyethylene (CPE-TS) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoset Chlorinated Polyethylene (CPE-TS) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Sample Print Legend:
Non UL:
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT TYPE TC 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
UL:
SOUTHWIRE MASTER-DESIGN E75755 {UL} XX AWG 3/C TYPE TC-ER FR-XLPE XHHW-2 CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT TYPE TC 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
UL:
SOUTHWIRE MASTER-DESIGN E75755 {UL} XX AWG 3/C TYPE TC-ER FR-XLPE XHHW-2 CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
18 AWG | |||||||||||||||||||
622124 | 18 | 4 | 7 | 0.045 | 25 | 45 | 0.326 | 20 | 57 | 6.669 | 8.035 | 1.3 | 0 | 0 | 11 | ||||
16 AWG | |||||||||||||||||||
6287950 | 16 | 2 | 7 | 0.056 | 25 | 45 | 0.318 | 16 | 50 | 4.181 | 5.037 | 1.2 | 0 | 0 | 18 | ||||
14 AWG | |||||||||||||||||||
6203390 | 14 | 3 | 7 | 0.07 | 30 | 45 | 0.386 | 38 | 93 | 2.631 | 3.17 | 1.5 | 15 | 20 | 25 | ||||
6203410 | 14 | 4 | 7 | 0.07 | 30 | 45 | 0.421 | 51 | 110 | 2.631 | 3.17 | 1.6 | 12 | 16 | 20 | ||||
6203610 | 14 | 7 | 7 | 0.07 | 30 | 45 | 0.498 | 89 | 173 | 2.631 | 3.17 | 1.9 | 10 | 14 | 17 | ||||
12 AWG | |||||||||||||||||||
622177 | 12 | 2 | 7 | 0.088 | 30 | 45 | 0.392 | 40 | 86 | 1.662 | 2.002 | 1.5 | 20 | 25 | 30 | ||||
669327 | 12 | 3 | 7 | 0.088 | 30 | 45 | 0.416 | 61 | 117 | 1.662 | 2.002 | 1.6 | 20 | 25 | 30 | ||||
618423 | 12 | 4 | 7 | 0.088 | 30 | 45 | 0.445 | 81 | 143 | 1.662 | 2.002 | 1.7 | 16 | 20 | 24 | ||||
622179 | 12 | 4 | 7 | 0.088 | 30 | 45 | 0.453 | 81 | 145 | 1.662 | 2.002 | 1.8 | 16 | 20 | 24 | ||||
669323 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.571 | 142 | 250 | 1.662 | 2.002 | 2.2 | 14 | 17 | 21 | ||||
6207330 | 12 | 7 | 19 | 0.088 | 30 | 60 | 0.588 | 189 | 298 | 1.662 | 2.002 | 2.3 | 14 | 17 | 21 | ||||
669319 | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.742 | 244 | 405 | 1.662 | 2.002 | 2.9 | 10 | 12 | 15 | ||||
620280 | 12 | 16 | 7 | 0.088 | 30 | 80 | 0.861 | 325 | 551 | 1.662 | 2.002 | 3.4 | 10 | 12 | 15 | ||||
6625210 | 12 | 19 | 7 | 0.088 | 30 | 80 | 0.923 | 386 | 648 | 1.662 | 2.002 | 3.6 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
622195 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.44 | 64 | 117 | 1.04 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
6203530 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.479 | 97 | 170 | 1.04 | 1.253 | 1.9 | 30 | 35 | 40 | ||||
622199 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.514 | 129 | 209 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
6071880 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.553 | 129 | 224 | 1.04 | 1.253 | 2.2 | 24 | 28 | 32 | ||||
6203590 | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.76 | 291 | 449 | 1.04 | 1.253 | 3 | 21 | 24 | 28 | ||||
6264800 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.895 | 388 | 615 | 1.04 | 1.253 | 3.5 | 15 | 17 | 20 | ||||
6203880 | 6 | 4 | 7 | 0.177 | 45 | 60 | 0.783 | 327 | 507 | 0.411 | 0.495 | 3.1 | 44 | 52 | 60 | ||||
6203900 | 4 | 3 | 7 | 0.225 | 45 | 60 | 0.816 | 390 | 577 | 0.258 | 0.31 | 3.2 | 70 | 85 | 95 | ||||
6203920 | 4 | 4 | 7 | 0.225 | 45 | 80 | 0.936 | 520 | 805 | 0.258 | 0.31 | 3.7 | 56 | 68 | 76 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^Tinned copper
^^19 strand conductor
† UL Listed
^Tinned copper
^^19 strand conductor
† UL Listed
Revision: 3.0.00C