SPEC 85005

Multi-Conductor CU 600 V FR-XLPE PVC Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG X/C FR-XLPE CDRS 90C PVC JKT 600V TYPE TC-ER SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JKT 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.milmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    16 AWG
    60689516425450.35832784.1815.0370.0331.4--14
    62353316725450.420561194.1815.0370.0331.6--12
    14 AWG
    625291^14230450.35725682.6313.1700.0581.4152025
    TBA14330450.37238852.6313.1700.0581.4152025
    624097^14430450.414511102.6313.1700.0581.6121620
    TBA14530450.443631222.6313.1700.0581.7121620
    TBA14630450.482761432.6313.1700.0581.9121620
    TBA14730450.482891612.6313.1700.0581.9101417
    TBA14830600.5521021992.6313.1700.0582.2101417
    TBA14930600.5911152222.6313.1700.0582.3101417
    TBA141030600.6421272452.6313.1700.0582.571012
    624096^141230600.6691532982.6313.1700.0582.671012
    TBA141530600.7341913432.6313.1700.0582.971012
    662633^141930600.7782434412.6313.1700.0583.171012
    TBA142030600.8122554422.6313.1700.0583.271012
    TBA142530800.9423195772.6313.1700.0583.76911
    TBA143030800.9953836742.6313.1700.0583.96911
    TBA143730801.0724738102.6313.1700.0585.36810
    12 AWG
    TBA12230450.38840871.6622.0020.0541.5202530
    62066112230450.39240881.6622.0020.0541.5202530
    TBA12330450.411611151.6622.0020.0541.6202530
    607613^12430450.457811481.6622.0020.0541.8162024
    620722^12430450.459811491.6622.0020.0541.8162024
    TBA12530450.4911011681.6622.0020.0541.9162024
    TBA12630600.5661222161.6622.0020.0542.2162024
    607615^12730600.5831422591.6622.0020.0542.3141721
    TBA12830600.6111622731.6622.0020.0542.4141721
    60813312930600.6571833121.6622.0020.0542.6141721
    TBA121030600.7142033371.6622.0020.0542.8101215
    620554^121230600.7422444101.6622.0020.0542.9101215
    607650^12430600.7462444121.6622.0020.0542.9162024
    622458121530800.8613055321.6622.0020.0543.4101215
    TBA121930800.9023866261.6622.0020.0543.6101215
    TBA122030800.9474066581.6622.0020.0543.7101215
    TBA122530801.0505088051.6622.0020.0545.291113
    TBA123030801.1106109451.6622.0020.0545.591113
    TBA123730801.19875211421.6622.0020.0545.981012
    10 AWG
    61908610230450.444641221.0401.2530.0501.7303540
    618887^10230450.448641361.0401.2530.0501.7303540
    620546^10330450.467971691.0401.2530.0501.8303540
    60796010430450.5061292111.0401.2530.0502.0242832
    618888^10430600.5521292271.0401.2530.0502.2242832
    628424^10530600.5911612701.0401.2530.0502.3242832
    619089^10730600.6402263541.0401.2530.0502.5212428
    TBA10630600.6411943041.0401.2530.0502.5242832
    TBA10830600.6942583891.0401.2530.0502.7212428
    TBA10930600.7462914351.0401.2530.0502.9212428
    TBA101030600.8143234821.0401.2530.0503.2151720
    607647^101230800.8783886151.0401.2530.0503.5151720
    619091^101230800.8873886241.0401.2530.0503.5151720
    TBA101530800.9764857311.0401.2530.0503.9151720
    TBA101930801.0276148961.0401.2530.0505.1151720
    TBA102030801.0806469441.0401.2530.0505.4151720
    TBA102430801.20077611211.0401.2530.0506.0131518
    TBA102530801.20080811601.0401.2530.0506.0131518
    TBA103030801.27097013681.0401.2530.0506.3131518
    TBA103730801.373119616591.0401.2530.0506.8121416
    8 AWG
    6080268245600.5841021960.6530.7860.0522.3405055
    6205538245600.5981022180.6530.7860.0522.3405055
    6607138345600.6351542860.6530.7860.0522.5405055
    6080598445600.6782053420.6530.7860.0522.7324044
    607652^8445600.6942053540.6530.7860.0522.7324044
    604092^8445600.6942053650.6530.7860.0522.7324044
    6 AWG
    6240956445600.7813275260.4110.4950.0513.1445260
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.002