SPEC 83310
Quadruplex Copper XLPE Service Drop Neutral - Messenger
Copper Conductors With Crosslinked Polyethylene Insulation.
Construction:
- Conductor:Conductors are stranded, compressed copper
- Messenger:Hard Drawn Copper
- Insulation:Cross Linked Polyethylene (XLPE)
Applications and Features:
Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.
Specifications:
Table 1 – Weights and Measurements
Stock Number | Code Word | Phase Cond. Size | Phase Strand | Dia. Over Phase Conductor | Phase Insul. Thickness | Dia. Over Phase Insulation | Neutral Cond. Size | Neutral Strand | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | mil | inch | AWG/Kcmil | No. | lb/1000ft | ||
TBA | Atlanta | 6 | 7 | 0.178 | 45 | 0.268 | 6 | 1 | 368 |
TBA | Tallahassee | 6 | 7 | 0.178 | 45 | 0.268 | 6 | 7 | 369 |
606621 | Richmond | 4 | 7 | 0.225 | 45 | 0.315 | 4 | 7 | 573 |
TBA | Baton Rouge | 4 | 7 | 0.225 | 45 | 0.315 | 4 | 1 | 570 |
TBA | Jackson | 2 | 7 | 0.283 | 45 | 0.373 | 2 | 1 | 889 |
325886 | Seattle | 2 | 7 | 0.283 | 45 | 0.373 | 2 | 7 | 893 |
TBA | Nashville | 1/0 | 19 | 0.362 | 60 | 0.482 | 1/0 | 7 | 1420 |
TBA | Lincoln | 2/0 | 19 | 0.405 | 60 | 0.525 | 2/0 | 7 | 1773 |
TBA | Raleigh | 3/0 | 19 | 0.456 | 60 | 0.576 | 3/0 | 7 | 2220 |
TBA | Denver | 4/0 | 19 | 0.512 | 60 | 0.632 | 4/0 | 7 | 2781 |
All dimensions are nominal and subject to normal manufacturing tolerances
Table 2 – Electrical and Engineering Data
Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | GMR | Allowable Ampacity In Air 90°C |
---|---|---|---|---|---|---|---|
AWG/Kcmil | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | ft | Amp | |
Atlanta | 6 | 1280 | 0.41 | 0.535 | 0.022 | 0.0086 | 95 |
Tallahassee | 6 | 1228 | 0.41 | 0.535 | 0.022 | 0.0107 | 95 |
Richmond | 4 | 1938 | 0.258 | 0.336 | 0.022 | 0.0121 | 125 |
Baton Rouge | 4 | 1970 | 0.258 | 0.336 | 0.022 | 0.0122 | 125 |
Jackson | 2 | 3003 | 0.162 | 0.211 | 0.022 | 0.0204 | 170 |
Seattle | 2 | 3050 | 0.162 | 0.211 | 0.022 | 0.0205 | 170 |
Nashville | 1/0 | 4752 | 0.102 | 0.133 | 0.022 | 0.0206 | 230 |
Lincoln | 2/0 | 5926 | 0.0811 | 0.1055 | 0.022 | 0.0207 | 265 |
Raleigh | 3/0 | 7366 | 0.0642 | 0.0836 | 0.022 | 0.0208 | 305 |
Denver | 4/0 | 9154 | 0.051 | 0.0633 | 0.022 | 0.021 | 350 |