SPEC 83244

Quadruplex XLPE Service Drop. AAC Neutral - Messenger

Aluminum Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:AAC Neutral

Applications and Features:

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBAClydesdale4Solid0.204300.264470.572204
    TBAPinto470.225300.285470.618212
    TBAMustang270.282450.372270.806351
    105213Criollo1/090.361600.4811/071.139504
    105221Percheron2/0110.405600.5252/071.243619
    TBAHanoverian3/0190.456600.5763/0191.246858
    105247Oldenburg4/0180.512600.6324/0191.491340
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    Clydesdale48810.2580.3100.0480.007100 / 115
    Pinto48810.4240.5110.0480.007100 / 115
    Mustang213500.2660.3200.0450.008135 / 150
    Criollo1/019900.1670.2010.0440.011180 / 205
    Percheron2/025100.1330.1590.0430.013210 / 235
    Hanoverian3/033100.1050.1260.0420.014240 / 270
    Oldenburg4/040200.0840.1000.0410.016280 / 315
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Sizes of AAAC neutrals are not the AAAC size, but are the size of an ACSR of equal diameter.
    7. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    Size-StrandsCode WordOD (inches)
    #6-7Peachbell0.184
    #4-7Rose0..232
    #2-7Iris0.292
    1/0-7Poppy0.368
    2/0-7Aster0.414
    3/0-19Primrose0.470
    4/0-19Sunflower0.528
    336.4-19Tulip0.665

    Revision: 1.000.000

    Updated On: July 3, 2024, 9:53 p.m. UTC