SPEC 26636

HVTECK AL 1/C 420TRXLPE CB PVC AIA PVC 35kV 133% CSA

Single Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 TRXLPE AIA 35kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    1/0190.3361.2144201.2745x121101.7842.094602.21418623846
    2/0190.3761.2544201.3147x121101.8242.134602.25423725286
    3/0190.4231.3014201.3617x121101.8712.181602.30124126426
    4/0190.4751.3534201.4137x121101.9232.233602.35324527736
    250370.521.4064201.4669x121101.9762.286752.43628830086.5
    350370.6161.5024201.56211x121102.0722.382752.53233333106.5
    500370.7361.6224201.68213x121102.1922.502752.65239737187
    750610.9081.8044201.86417x121102.3742.684752.83447943527.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/015.56330.1670.2290.080.0650.520+j0.2070.232+j0.0692770221219
    2/015.87980.1330.1820.0750.0630.421+j0.1360.186+j0.0663879253246
    3/016.110060.1050.1440.0710.0610.383+j0.1350.147+j0.0643879288275
    4/016.512690.0840.1150.0660.0580.354+j0.1330.118+j0.0623879327305
    25017.115000.070.0960.0620.0570.295+j0.0960.100+j0.0604987367343
    35017.721000.0510.070.0560.0540.239+j0.0740.075+j0.0576095443399
    50018.630000.0360.050.050.0510.196+j0.0590.056+j0.0547203529451
    75019.845000.0230.0330.0430.0480.148+j0.0430.040+j0.0509420633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmmmkg/kmkg/kminch
    1/0198.5330.8410.6732.365x122.7945.3153.191.5256.2427735486
    2/0199.5531.8510.6733.387x122.7946.3354.201.5257.2535337626
    3/01910.7433.0510.6734.577x122.7947.5255.401.5258.4535939326
    4/01912.0734.3710.6735.897x122.7948.8456.721.5259.7736541276
    2503713.2135.7110.6737.249x122.7950.1958.061.9161.8742944766.5
    3503715.6538.1510.6739.6711x122.7952.6360.501.9164.3149649266.5
    5003718.6941.2010.6742.7213x122.7955.6863.551.9167.3659155337
    7506123.0645.8210.6747.3517x122.7960.3068.171.9171.9871364767.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0393.7028170.54790.750.02440.21330.520+j0.2070.232+j0.0692770221219
    2/0401.3235510.43640.600.02290.20670.421+j0.1360.186+j0.0663879253246
    3/0408.9444770.34450.470.02160.20010.383+j0.1350.147+j0.0643879288275
    4/0419.1056470.27560.380.02010.19030.354+j0.1330.118+j0.0623879327305
    250434.3466750.22970.310.01890.18700.295+j0.0960.100+j0.0604987367343
    350449.5893450.16730.230.01710.17720.239+j0.0740.075+j0.0576095443399
    500472.44133500.11810.160.01520.16730.196+j0.0590.056+j0.0547203529451
    750502.92200250.07550.110.01310.15750.148+j0.0430.040+j0.0509420633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A