SPEC 26602

HVTECK CU 1/C 420NLEPR TS PVC AIA PVC 35kV 133% CSA

Single Conductor, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 420 NLEPR AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    TBA1/0190.3621.244201.3801.79601.9143319685
    TBA2/0190.4051.2834201.343801.833601.95352121145
    TBA3/0190.4561.3344201.394801.884602.00463322955
    TBA4/0190.5121.394201.45801.94602.0677225105.5
    TBA250370.5581.4444201.5041102.054602.17489628255.5
    139088350370.6611.5474201.6071102.191602.311121431046
    TBA500370.7891.6754201.7351102.285752.435168740076.5
    TBA750610.9681.8644201.9241102.474752.624247450757
    5792221000611.1172.0134202.0731102.637832.803325857387.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/013.48440.1020.1390.0590.060.478+j0.3150.140+j0.0654059278272
    2/013.710640.0820.1120.0550.0580.449+j0.3030.113+j0.0634192316303
    3/01413420.0640.0870.0520.0560.420+j0.2900.089+j0.0614350356333
    4/014.416920.0510.070.0480.0540.399+j0.2770.072+j0.0594524403367
    25015.220000.0430.0590.0450.0530.384+j0.2650.061+j0.0584691455411
    35016.228000.0310.0430.0410.050.360+j0.2440.045+j0.0565010537459
    5001740000.0210.030.0360.0480.337+j0.2210.032+j0.0535407616499
    75018.460000.0140.0210.0310.0450.313+j0.1930.023+j0.0505992716557
    100019.680000.0110.0180.0280.0430.298+j0.1750.020+j0.0486454825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA1/0199.1931.5010.6733.022.0345.471.5248.5164429295
    TBA2/01910.2932.5910.6734.112.0346.561.5249.6177531465
    TBA3/01911.5833.8810.6735.412.0347.851.5250.9094234155
    TBA4/01913.0035.3110.6736.832.0349.281.5252.32114937355.5
    TBA2503714.1736.6810.6738.202.7952.171.5255.22133342045.5
    1390883503716.7939.2910.6740.822.7955.651.5258.70180746196
    TBA5003720.0442.5510.6744.072.7958.041.9161.85251159636.5
    TBA7506124.5947.3510.6748.872.7962.841.9166.65368275527
    57922210006128.3751.1310.6752.652.7966.982.1171.20484885397.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0340.3637560.33460.460.01800.19690.478+j0.3150.140+j0.0654059278272
    2/0347.9847350.26900.370.01680.19030.449+j0.3030.113+j0.0634192316303
    3/0355.6059720.21000.290.01580.18370.420+j0.2900.089+j0.0614350356333
    4/0365.7675290.16730.230.01460.17720.399+j0.2770.072+j0.0594524403367
    250386.0889000.14110.190.01370.17390.384+j0.2650.061+j0.0584691455411
    350411.48124600.10170.140.01250.16400.360+j0.2440.045+j0.0565010537459
    500431.80178000.06890.100.01100.15750.337+j0.2210.032+j0.0535407616499
    750467.36267000.04590.070.00940.14760.313+j0.1930.023+j0.0505992716557
    1000497.84356000.03610.060.00850.14110.298+j0.1750.020+j0.0486454825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.002

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC