SPEC 26531
HVTECK AL 1/C 280TRXLPE TS PVC AIA PVC 28kV 100% CSA
Single Conductor, 280 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:280 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 280 TRXLPE AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.299 | 0.897 | 280 | 0.957 | 80 | 1.347 | 50 | 1.447 | 79 | 1029 | 3.5 |
| 1/0 | 19 | 0.336 | 0.934 | 280 | 0.994 | 80 | 1.384 | 50 | 1.484 | 82 | 1089 | 4 |
| 2/0 | 19 | 0.376 | 0.974 | 280 | 1.034 | 80 | 1.424 | 50 | 1.524 | 85 | 1159 | 4 |
| 3/0 | 19 | 0.423 | 1.021 | 280 | 1.081 | 80 | 1.571 | 60 | 1.691 | 89 | 1417 | 4.5 |
| 4/0 | 19 | 0.475 | 1.073 | 280 | 1.133 | 80 | 1.623 | 60 | 1.743 | 93 | 1519 | 4.5 |
| 250 | 37 | 0.52 | 1.126 | 280 | 1.186 | 80 | 1.676 | 60 | 1.796 | 98 | 1623 | 4.5 |
| 350 | 37 | 0.616 | 1.222 | 280 | 1.282 | 80 | 1.772 | 60 | 1.892 | 105 | 1833 | 5 |
| 500 | 37 | 0.736 | 1.342 | 280 | 1.402 | 80 | 1.892 | 60 | 2.012 | 115 | 2119 | 5.5 |
| 750 | 61 | 0.908 | 1.524 | 280 | 1.584 | 110 | 2.134 | 60 | 2.254 | 130 | 2701 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 10.1 | 502 | 0.211 | 0.289 | 0.067 | 0.058 | 0.644+j0.409 | 0.290+j0.062 | 2996 | 193 | 194 |
| 1/0 | 10.4 | 633 | 0.167 | 0.229 | 0.062 | 0.056 | 0.583+j0.395 | 0.230+j0.060 | 3111 | 221 | 219 |
| 2/0 | 10.7 | 798 | 0.133 | 0.182 | 0.058 | 0.054 | 0.536+j0.380 | 0.183+j0.058 | 3235 | 253 | 246 |
| 3/0 | 11.8 | 1006 | 0.105 | 0.144 | 0.054 | 0.054 | 0.494+j0.364 | 0.145+j0.057 | 3380 | 288 | 275 |
| 4/0 | 12.2 | 1269 | 0.084 | 0.115 | 0.05 | 0.052 | 0.463+j0.347 | 0.116+j0.055 | 3541 | 327 | 305 |
| 250 | 12.6 | 1500 | 0.07 | 0.096 | 0.047 | 0.05 | 0.442+j0.331 | 0.097+j0.054 | 3706 | 367 | 343 |
| 350 | 13.2 | 2100 | 0.051 | 0.07 | 0.042 | 0.047 | 0.411+j0.305 | 0.071+j0.051 | 4003 | 443 | 399 |
| 500 | 14.1 | 3000 | 0.036 | 0.05 | 0.037 | 0.045 | 0.383+j0.276 | 0.052+j0.049 | 4375 | 529 | 451 |
| 750 | 15.8 | 4500 | 0.023 | 0.033 | 0.031 | 0.043 | 0.352+j0.239 | 0.035+j0.046 | 4939 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 7.59 | 22.78 | 7.11 | 24.31 | 2.03 | 34.21 | 1.27 | 36.75 | 118 | 1531 | 3.5 |
| 1/0 | 19 | 8.53 | 23.72 | 7.11 | 25.25 | 2.03 | 35.15 | 1.27 | 37.69 | 122 | 1621 | 4 |
| 2/0 | 19 | 9.55 | 24.74 | 7.11 | 26.26 | 2.03 | 36.17 | 1.27 | 38.71 | 126 | 1725 | 4 |
| 3/0 | 19 | 10.74 | 25.93 | 7.11 | 27.46 | 2.03 | 39.90 | 1.52 | 42.95 | 132 | 2109 | 4.5 |
| 4/0 | 19 | 12.07 | 27.25 | 7.11 | 28.78 | 2.03 | 41.22 | 1.52 | 44.27 | 138 | 2261 | 4.5 |
| 250 | 37 | 13.21 | 28.60 | 7.11 | 30.12 | 2.03 | 42.57 | 1.52 | 45.62 | 146 | 2415 | 4.5 |
| 350 | 37 | 15.65 | 31.04 | 7.11 | 32.56 | 2.03 | 45.01 | 1.52 | 48.06 | 156 | 2728 | 5 |
| 500 | 37 | 18.69 | 34.09 | 7.11 | 35.61 | 2.03 | 48.06 | 1.52 | 51.10 | 171 | 3153 | 5.5 |
| 750 | 61 | 23.06 | 38.71 | 7.11 | 40.23 | 2.79 | 54.20 | 1.52 | 57.25 | 193 | 4020 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 256.54 | 2234 | 0.6923 | 0.95 | 0.0204 | 0.1903 | 0.644+j0.409 | 0.290+j0.062 | 2996 | 193 | 194 |
| 1/0 | 264.16 | 2817 | 0.5479 | 0.75 | 0.0189 | 0.1837 | 0.583+j0.395 | 0.230+j0.060 | 3111 | 221 | 219 |
| 2/0 | 271.78 | 3551 | 0.4364 | 0.60 | 0.0177 | 0.1772 | 0.536+j0.380 | 0.183+j0.058 | 3235 | 253 | 246 |
| 3/0 | 299.72 | 4477 | 0.3445 | 0.47 | 0.0165 | 0.1772 | 0.494+j0.364 | 0.145+j0.057 | 3380 | 288 | 275 |
| 4/0 | 309.88 | 5647 | 0.2756 | 0.38 | 0.0152 | 0.1706 | 0.463+j0.347 | 0.116+j0.055 | 3541 | 327 | 305 |
| 250 | 320.04 | 6675 | 0.2297 | 0.31 | 0.0143 | 0.1640 | 0.442+j0.331 | 0.097+j0.054 | 3706 | 367 | 343 |
| 350 | 335.28 | 9345 | 0.1673 | 0.23 | 0.0128 | 0.1542 | 0.411+j0.305 | 0.071+j0.051 | 4003 | 443 | 399 |
| 500 | 358.14 | 13350 | 0.1181 | 0.16 | 0.0113 | 0.1476 | 0.383+j0.276 | 0.052+j0.049 | 4375 | 529 | 451 |
| 750 | 401.32 | 20025 | 0.0755 | 0.11 | 0.0094 | 0.1411 | 0.352+j0.239 | 0.035+j0.046 | 4939 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

