SPEC 26521

HVTECK AL 1/C 280NLEPR TS PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 280 NLEPR AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    1190.2990.8972800.957801.347501.4477910293.5
    1/0190.3360.9342800.994801.384501.4848210894
    2/0190.3760.9742801.034801.424501.5248511594
    3/0190.4231.0212801.081801.571601.6918914174.5
    4/0190.4751.0732801.133801.623601.7439315194.5
    250370.521.1262801.186801.676601.7969816234.5
    350370.6161.2222801.282801.772601.89210518335
    500370.7361.3422801.402801.892602.01211521195.5
    750610.9081.5242801.5841102.134602.25413027016
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    110.15020.2110.2890.0510.0580.644+j0.4090.290+j0.0622996193194
    1/010.46330.1670.2290.0480.0560.583+j0.3950.230+j0.0603111221219
    2/010.77980.1330.1820.0450.0540.536+j0.3800.183+j0.0583235253246
    3/011.810060.1050.1440.0410.0540.494+j0.3640.145+j0.0573380288275
    4/012.212690.0840.1150.0390.0520.463+j0.3470.116+j0.0553541327305
    25012.615000.070.0960.0360.050.442+j0.3310.097+j0.0543706367343
    35013.221000.0510.070.0320.0470.411+j0.3050.071+j0.0514003443399
    50014.130000.0360.050.0280.0450.383+j0.2760.052+j0.0494375529451
    75015.845000.0230.0330.0240.0430.352+j0.2390.035+j0.0464939633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    1197.5922.787.1124.312.0334.211.2736.7511815313.5
    1/0198.5323.727.1125.252.0335.151.2737.6912216214
    2/0199.5524.747.1126.262.0336.171.2738.7112617254
    3/01910.7425.937.1127.462.0339.901.5242.9513221094.5
    4/01912.0727.257.1128.782.0341.221.5244.2713822614.5
    2503713.2128.607.1130.122.0342.571.5245.6214624154.5
    3503715.6531.047.1132.562.0345.011.5248.0615627285
    5003718.6934.097.1135.612.0348.061.5251.1017131535.5
    7506123.0638.717.1140.232.7954.201.5257.2519340206
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1256.5422340.69230.950.01550.19030.644+j0.4090.290+j0.0622996193194
    1/0264.1628170.54790.750.01460.18370.583+j0.3950.230+j0.0603111221219
    2/0271.7835510.43640.600.01370.17720.536+j0.3800.183+j0.0583235253246
    3/0299.7244770.34450.470.01250.17720.494+j0.3640.145+j0.0573380288275
    4/0309.8856470.27560.380.01190.17060.463+j0.3470.116+j0.0553541327305
    250320.0466750.22970.310.01100.16400.442+j0.3310.097+j0.0543706367343
    350335.2893450.16730.230.00980.15420.411+j0.3050.071+j0.0514003443399
    500358.14133500.11810.160.00850.14760.383+j0.2760.052+j0.0494375529451
    750401.32200250.07550.110.00730.14110.352+j0.2390.035+j0.0464939633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A