SPEC 26521

HVTECK AL 1/C 280NLEPR TS PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 280 NLEPR AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchinchmilinchlb/1000ft
    TBA1190.2980.8962800.9561.468501.568995
    TBA1/0190.3360.9342800.9941.506601.6261086
    TBA2/0190.3760.9742801.0341.546601.6661155
    TBA3/0190.4221.0202801.0801.592601.7121237
    TBA4/0190.4741.0722801.1321.668601.7881366
    TBA250370.5201.1262801.1861.722601.8421463
    TBA350370.6151.2212801.2811.817601.9371660
    TBA500370.7351.3412801.4011.937602.0572028
    TBA750610.9081.5242801.5842.180602.3002605
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    110.95020.2110.2660.0570.0600.624 + j0.370.267 + j0.0582961193194
    1/011.36330.1680.2110.0530.0580.567 + j0.3560.212 + j0.0563079221219
    2/011.67980.1330.1670.0490.0560.521 + j0.3410.168 + j0.0543203253246
    3/011.910060.1050.1330.0450.0540.484 + j0.3250.134 + j0.0523346288275
    4/012.512690.0840.1050.0420.0520.452 + j0.3080.106 + j0.0513507327305
    25012.815000.0710.0900.0400.0510.433 + j0.2930.091 + j0.0493674367343
    35013.521000.0500.0650.0350.0480.4 + j0.2670.066 + j0.0463968443399
    50014.330000.0350.0460.0310.0450.37 + j0.2390.047 + j0.0444340529451
    75016.145000.0240.0330.0270.0430.339 + j0.2040.034 + j0.0414907633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmkg/km
    TBA1197.5722.767.1124.2837.291.2739.831481
    TBA1/0198.5323.727.1125.2538.251.5241.301616
    TBA2/0199.5524.747.1126.2639.271.5242.321719
    TBA3/01910.7225.917.1127.4340.441.5243.481841
    TBA4/01912.0427.237.1128.7542.371.5245.422033
    TBA2503713.2128.607.1130.1243.741.5246.792177
    TBA3503715.6231.017.1132.5446.151.5249.202470
    TBA5003718.6734.067.1135.5949.201.5252.253018
    TBA7506123.0638.717.1140.2355.371.5258.423877
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1276.8622340.69230.870.01740.19690.624 + j0.370.267 + j0.0582961193194
    1/0287.0228170.55120.690.01620.19030.567 + j0.3560.212 + j0.0563079221219
    2/0294.6435510.43640.550.01490.18370.521 + j0.3410.168 + j0.0543203253246
    3/0302.2644770.34450.440.01370.17720.484 + j0.3250.134 + j0.0523346288275
    4/0317.5056470.27560.340.01280.17060.452 + j0.3080.106 + j0.0513507327305
    250325.1266750.23290.300.01220.16730.433 + j0.2930.091 + j0.0493674367343
    350342.9093450.16400.210.01070.15750.4 + j0.2670.066 + j0.0463968443399
    500363.22133500.11480.150.00940.14760.37 + j0.2390.047 + j0.0444340529451
    750408.94200250.07870.110.00820.14110.339 + j0.2040.034 + j0.0414907633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C