SPEC 26511

HVTECK CU 1/C 280TRXLPE TS PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:280 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 280 TRXLPE AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    TBA1190.3220.922800.98801.37501.4733912334
    TBA1/0190.3620.962801.02801.41501.5141013444
    TBA2/0190.4051.0032801.063801.453501.55349814754
    TBA3/0190.4561.0542801.114801.604601.72461018154.5
    TBA4/0190.5121.112801.17801.66601.7874920164.5
    TBA250370.5581.1642801.224801.714601.83487322035
    672631350370.6611.2672801.341801.865601.985119424545
    653134350370.6611.2672801.341801.865601.985119424585
    TBA500370.7891.3952801.455801.945602.065166432515.5
    TBA750610.9681.5842801.6441102.194602.314245143796
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    110.36690.1280.1750.0640.0570.530+j0.4020.176+j0.0623067245244
    1/010.68440.1020.1390.060.0550.493+j0.3870.140+j0.0603191278272
    2/010.910640.0820.1120.0560.0530.465+j0.3720.113+j0.0583325316303
    3/012.113420.0640.0870.0520.0520.436+j0.3550.088+j0.0583483356333
    4/012.516920.0510.070.0480.050.417+j0.3380.071+j0.0563656403367
    25012.820000.0430.0590.0450.0490.403+j0.3220.060+j0.0543823455411
    35013.928000.0310.0430.040.0470.379+j0.2920.045+j0.0524186537459
    35013.928000.0310.0430.040.0470.379+j0.2920.045+j0.0524186537459
    50014.540000.0210.030.0350.0440.359+j0.2660.032+j0.0494539616499
    75016.260000.0140.0210.030.0420.335+j0.2290.023+j0.0475125716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA1198.1823.377.1124.892.0334.801.2737.3450418354
    TBA1/0199.1924.387.1125.912.0335.811.2738.3561020004
    TBA2/01910.2925.487.1127.002.0336.911.2739.4574121954
    TBA3/01911.5826.777.1128.302.0340.741.5243.7990827014.5
    TBA4/01913.0028.197.1129.722.0342.161.5245.21111530004.5
    TBA2503714.1729.577.1131.092.0343.541.5246.58129932785
    6726313503716.7932.187.1134.062.0347.371.5250.42177736525
    6531343503716.7932.187.1134.062.0347.371.5250.42177736585
    TBA5003720.0435.437.1136.962.0349.401.5252.45247648385.5
    TBA7506124.5940.237.1141.762.7955.731.5258.78364765176
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1261.6229770.41990.570.01950.18700.530+j0.4020.176+j0.0623067245244
    1/0269.2437560.33460.460.01830.18040.493+j0.3870.140+j0.0603191278272
    2/0276.8647350.26900.370.01710.17390.465+j0.3720.113+j0.0583325316303
    3/0307.3459720.21000.290.01580.17060.436+j0.3550.088+j0.0583483356333
    4/0317.5075290.16730.230.01460.16400.417+j0.3380.071+j0.0563656403367
    250325.1289000.14110.190.01370.16080.403+j0.3220.060+j0.0543823455411
    350353.06124600.10170.140.01220.15420.379+j0.2920.045+j0.0524186537459
    350353.06124600.10170.140.01220.15420.379+j0.2920.045+j0.0524186537459
    500368.30178000.06890.100.01070.14440.359+j0.2660.032+j0.0494539616499
    750411.48267000.04590.070.00910.13780.335+j0.2290.023+j0.0475125716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC