SPEC 26452
HVTECK CU 3/C 320TRXLPE TS PVC AIA PVC 25kV 133% CSA
3 Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Filler:Non-wicking, non-hygroscopic and flame retardant polypropylene filler
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 320 TRXLPE AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | mil | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.322 | 1.000 | 320 | 1.060 | 6 | 110 | 2.908 | 75 | 3.058 | 4177 |
TBA | 1/0 | 19 | 0.361 | 1.039 | 320 | 1.099 | 6 | 110 | 2.993 | 75 | 3.143 | 4535 |
TBA | 2/0 | 19 | 0.405 | 1.083 | 320 | 1.143 | 6 | 125 | 3.118 | 85 | 3.288 | 5121 |
TBA | 3/0 | 19 | 0.456 | 1.134 | 320 | 1.194 | 4 | 125 | 3.228 | 85 | 3.398 | 5652 |
678745 | 4/0 | 19 | 0.512 | 1.190 | 320 | 1.250 | 4 | 125 | 3.363 | 85 | 3.533 | 6143 |
TBA | 250 | 37 | 0.558 | 1.244 | 320 | 1.304 | 4 | 125 | 3.465 | 85 | 3.635 | 6878 |
137995! | 350 | 37 | 0.641 | 1.327 | 320 | 1.387 | 3 | 125 | 3.659 | 85 | 3.829 | 7906 |
TBA | 350 | 37 | 0.661 | 1.347 | 320 | 1.407 | 3 | 125 | 3.688 | 85 | 3.858 | 8246 |
678737 | 500 | 37 | 0.789 | 1.475 | 320 | 1.535 | 3 | 125 | 3.979 | 85 | 4.149 | 9763 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
! Gray Jacket Color
! Gray Jacket Color
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 21.4 | 2008 | 0.128 | 0.162 | 0.077 | 0.050 | 0.523 + j0.339 | 0.162 + j0.05 | 3284 | 202 | 226 |
1/0 | 22.0 | 2534 | 0.102 | 0.128 | 0.071 | 0.048 | 0.486 + j0.325 | 0.128 + j0.048 | 3405 | 231 | 256 |
2/0 | 23.0 | 3194 | 0.081 | 0.102 | 0.066 | 0.046 | 0.456 + j0.31 | 0.102 + j0.046 | 3541 | 265 | 290 |
3/0 | 23.7 | 4027 | 0.064 | 0.081 | 0.061 | 0.044 | 0.43 + j0.295 | 0.081 + j0.044 | 3699 | 303 | 327 |
4/0 | 24.7 | 5078 | 0.051 | 0.065 | 0.057 | 0.043 | 0.409 + j0.279 | 0.065 + j0.043 | 3872 | 348 | 369 |
250 | 25.4 | 6000 | 0.043 | 0.056 | 0.054 | 0.042 | 0.395 + j0.265 | 0.056 + j0.042 | 4040 | 384 | 408 |
350 | 26.8 | 8400 | 0.031 | 0.041 | 0.048 | 0.039 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
350 | 27.0 | 8400 | 0.031 | 0.041 | 0.048 | 0.039 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
500 | 29.0 | 12000 | 0.022 | 0.030 | 0.042 | 0.037 | 0.345 + j0.215 | 0.031 + j0.037 | 4755 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 8.18 | 25.40 | 8.13 | 26.92 | 6 | 2.79 | 73.86 | 1.91 | 77.67 | 6216 |
TBA | 1/0 | 19 | 9.17 | 26.39 | 8.13 | 27.91 | 6 | 2.79 | 76.02 | 1.91 | 79.83 | 6749 |
TBA | 2/0 | 19 | 10.29 | 27.51 | 8.13 | 29.03 | 6 | 3.18 | 79.20 | 2.16 | 83.52 | 7621 |
TBA | 3/0 | 19 | 11.58 | 28.80 | 8.13 | 30.33 | 4 | 3.18 | 81.99 | 2.16 | 86.31 | 8411 |
678745 | 4/0 | 19 | 13.00 | 30.23 | 8.13 | 31.75 | 4 | 3.18 | 85.42 | 2.16 | 89.74 | 9142 |
TBA | 250 | 37 | 14.17 | 31.60 | 8.13 | 33.12 | 4 | 3.18 | 88.01 | 2.16 | 92.33 | 10236 |
137995! | 350 | 37 | 16.28 | 33.71 | 8.13 | 35.23 | 3 | 3.18 | 92.94 | 2.16 | 97.26 | 11765 |
TBA | 350 | 37 | 16.79 | 34.21 | 8.13 | 35.74 | 3 | 3.18 | 93.68 | 2.16 | 97.99 | 12271 |
678737 | 500 | 37 | 20.04 | 37.47 | 8.13 | 38.99 | 3 | 3.18 | 101.07 | 2.16 | 105.38 | 14529 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
! Gray Jacket Color
! Gray Jacket Color
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 543.56 | 8936 | 0.4199 | 0.53 | 0.0235 | 0.1640 | 0.523 + j0.339 | 0.162 + j0.05 | 3284 | 202 | 226 |
1/0 | 558.80 | 11276 | 0.3346 | 0.42 | 0.0216 | 0.1575 | 0.486 + j0.325 | 0.128 + j0.048 | 3405 | 231 | 256 |
2/0 | 584.20 | 14213 | 0.2657 | 0.33 | 0.0201 | 0.1509 | 0.456 + j0.31 | 0.102 + j0.046 | 3541 | 265 | 290 |
3/0 | 601.98 | 17920 | 0.2100 | 0.27 | 0.0186 | 0.1444 | 0.43 + j0.295 | 0.081 + j0.044 | 3699 | 303 | 327 |
4/0 | 627.38 | 22597 | 0.1673 | 0.21 | 0.0174 | 0.1411 | 0.409 + j0.279 | 0.065 + j0.043 | 3872 | 348 | 369 |
250 | 645.16 | 26700 | 0.1411 | 0.18 | 0.0165 | 0.1378 | 0.395 + j0.265 | 0.056 + j0.042 | 4040 | 384 | 408 |
350 | 680.72 | 37380 | 0.1017 | 0.13 | 0.0146 | 0.1280 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
350 | 685.80 | 37380 | 0.1017 | 0.13 | 0.0146 | 0.1280 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
500 | 736.60 | 53400 | 0.0722 | 0.10 | 0.0128 | 0.1214 | 0.345 + j0.215 | 0.031 + j0.037 | 4755 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Revision: 1.000.000
Updated On: Aug. 18, 2023, 2:39 p.m. UTC