SPEC 26436

HVTECK AL 1/C 320TRXLPE CB PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 320 TRXLPE AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    1190.2980.9763201.0367 x 14801.686601.8061227
    1/0190.3361.0143201.0747 x 14801.724601.8441289
    2/0190.3761.0543201.11411 x 14801.764601.8841412
    3/0190.4221.1003201.16011 x 14801.810601.9301492
    4/0190.4741.1523201.21211 x 14801.862601.9821681
    250370.5201.2063201.26613 x 14801.916602.0361808
    350370.6151.3013201.36117 x 141102.071602.1912181
    500370.7351.4213201.48121 x 141102.191602.3112521
    750610.9081.6043201.66417 x 121102.408752.5583145
    1000611.0601.7563201.81617 x 121102.560752.7103566
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    112.65020.2110.2660.0800.0630.248 + j0.0360.254 + j0.0445458193194
    1/012.96330.1680.2110.0750.0610.193 + j0.0340.199 + j0.0425458221219
    2/013.17980.1330.1670.0700.0590.149 + j0.0320.155 + j0.048577253246
    3/013.510060.1050.1330.0650.0570.115 + j0.0310.121 + j0.0398577288275
    4/013.812690.0840.1050.0600.0550.087 + j0.0290.093 + j0.0378577327305
    25014.215000.0710.0900.0570.0530.072 + j0.0270.078 + j0.03610137367343
    35015.321000.0500.0650.0500.0510.047 + j0.0250.053 + j0.03313256443399
    50016.130000.0350.0460.0440.0480.028 + j0.0230.034 + j0.03116376529451
    75017.945000.0240.0330.0380.0460.015 + j0.0210.022 + j0.02921062633505
    100018.960000.0180.0260.0340.0430.008 + j0.0190.015 + j0.02821062711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    1197.5724.798.1326.317 x 142.0342.821.5245.871826
    1/0198.5325.768.1327.287 x 142.0343.791.5246.841918
    2/0199.5526.778.1328.3011 x 142.0344.811.5247.852101
    3/01910.7227.948.1329.4611 x 142.0345.971.5249.022220
    4/01912.0429.268.1330.7811 x 142.0347.291.5250.342502
    2503713.2130.638.1332.1613 x 142.0348.671.5251.712691
    3503715.6233.058.1334.5717 x 142.7952.601.5255.653246
    5003718.6736.098.1337.6221 x 142.7955.651.5258.703752
    7506123.0640.748.1342.2717 x 122.7961.161.9164.974680
    10006126.9244.608.1346.1317 x 122.7965.021.9168.835307
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1320.0422340.69230.870.02440.20670.248 + j0.0360.254 + j0.0445458193194
    1/0327.6628170.55120.690.02290.20010.193 + j0.0340.199 + j0.0425458221219
    2/0332.7435510.43640.550.02130.19360.149 + j0.0320.155 + j0.048577253246
    3/0342.9044770.34450.440.01980.18700.115 + j0.0310.121 + j0.0398577288275
    4/0350.5256470.27560.340.01830.18040.087 + j0.0290.093 + j0.0378577327305
    250360.6866750.23290.300.01740.17390.072 + j0.0270.078 + j0.03610137367343
    350388.6293450.16400.210.01520.16730.047 + j0.0250.053 + j0.03313256443399
    500408.94133500.11480.150.01340.15750.028 + j0.0230.034 + j0.03116376529451
    750454.66200250.07870.110.01160.15090.015 + j0.0210.022 + j0.02921062633505
    1000480.06267000.05910.090.01040.14110.008 + j0.0190.015 + j0.02821062711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC