SPEC 26425
HVTECK AL 1/C 260NLEPR CB PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.298 | 0.856 | 260 | 0.916 | 7 x 14 | 1.542 | 60 | 1.662 | 1045 |
TBA | 1/0 | 19 | 0.336 | 0.894 | 260 | 0.954 | 7 x 14 | 1.580 | 60 | 1.700 | 1101 |
TBA | 2/0 | 19 | 0.376 | 0.934 | 260 | 0.994 | 11 x 14 | 1.620 | 60 | 1.740 | 1219 |
TBA | 3/0 | 19 | 0.422 | 0.980 | 260 | 1.040 | 11 x 14 | 1.690 | 60 | 1.810 | 1329 |
TBA | 4/0 | 19 | 0.474 | 1.032 | 260 | 1.092 | 11 x 14 | 1.742 | 60 | 1.862 | 1421 |
TBA | 250 | 37 | 0.520 | 1.086 | 260 | 1.146 | 13 x 14 | 1.796 | 60 | 1.916 | 1539 |
TBA | 350 | 37 | 0.615 | 1.181 | 260 | 1.241 | 17 x 14 | 1.891 | 60 | 2.011 | 1872 |
TBA | 500 | 37 | 0.735 | 1.301 | 260 | 1.361 | 21 x 14 | 2.071 | 60 | 2.191 | 2311 |
TBA | 750 | 61 | 0.908 | 1.484 | 260 | 1.544 | 17 x 12 | 2.288 | 75 | 2.438 | 2914 |
TBA | 1000 | 61 | 1.060 | 1.636 | 260 | 1.696 | 17 x 12 | 2.440 | 75 | 2.590 | 3321 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 11.6 | 502 | 0.211 | 0.266 | 0.054 | 0.061 | 0.248 + j0.034 | 0.254 + j0.042 | 5458 | 193 | 194 |
1/0 | 11.9 | 633 | 0.168 | 0.211 | 0.051 | 0.059 | 0.193 + j0.032 | 0.199 + j0.04 | 5458 | 221 | 219 |
2/0 | 12.1 | 798 | 0.133 | 0.167 | 0.047 | 0.057 | 0.149 + j0.03 | 0.155 + j0.038 | 8577 | 253 | 246 |
3/0 | 12.6 | 1006 | 0.105 | 0.133 | 0.043 | 0.055 | 0.115 + j0.028 | 0.121 + j0.036 | 8577 | 288 | 275 |
4/0 | 13.0 | 1269 | 0.084 | 0.105 | 0.040 | 0.053 | 0.087 + j0.027 | 0.093 + j0.035 | 8577 | 327 | 305 |
250 | 13.4 | 1500 | 0.071 | 0.090 | 0.038 | 0.052 | 0.072 + j0.025 | 0.078 + j0.034 | 10137 | 367 | 343 |
350 | 14.0 | 2100 | 0.050 | 0.065 | 0.033 | 0.049 | 0.047 + j0.023 | 0.053 + j0.031 | 13256 | 443 | 399 |
500 | 15.3 | 3000 | 0.035 | 0.046 | 0.029 | 0.047 | 0.028 + j0.021 | 0.034 + j0.029 | 16376 | 529 | 451 |
750 | 17.0 | 4500 | 0.024 | 0.033 | 0.025 | 0.044 | 0.015 + j0.019 | 0.021 + j0.028 | 21062 | 633 | 505 |
1000 | 18.1 | 6000 | 0.018 | 0.026 | 0.022 | 0.042 | 0.008 + j0.018 | 0.015 + j0.026 | 21062 | 711 | 544 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 7.57 | 21.74 | 6.60 | 23.27 | 7 x 14 | 39.17 | 1.52 | 42.21 | 1555 |
TBA | 1/0 | 19 | 8.53 | 22.71 | 6.60 | 24.23 | 7 x 14 | 40.13 | 1.52 | 43.18 | 1638 |
TBA | 2/0 | 19 | 9.55 | 23.72 | 6.60 | 25.25 | 11 x 14 | 41.15 | 1.52 | 44.20 | 1814 |
TBA | 3/0 | 19 | 10.72 | 24.89 | 6.60 | 26.42 | 11 x 14 | 42.93 | 1.52 | 45.97 | 1978 |
TBA | 4/0 | 19 | 12.04 | 26.21 | 6.60 | 27.74 | 11 x 14 | 44.25 | 1.52 | 47.29 | 2115 |
TBA | 250 | 37 | 13.21 | 27.58 | 6.60 | 29.11 | 13 x 14 | 45.62 | 1.52 | 48.67 | 2290 |
TBA | 350 | 37 | 15.62 | 30.00 | 6.60 | 31.52 | 17 x 14 | 48.03 | 1.52 | 51.08 | 2786 |
TBA | 500 | 37 | 18.67 | 33.05 | 6.60 | 34.57 | 21 x 14 | 52.60 | 1.52 | 55.65 | 3439 |
TBA | 750 | 61 | 23.06 | 37.69 | 6.60 | 39.22 | 17 x 12 | 58.12 | 1.91 | 61.93 | 4337 |
TBA | 1000 | 61 | 26.92 | 41.55 | 6.60 | 43.08 | 17 x 12 | 61.98 | 1.91 | 65.79 | 4942 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 294.64 | 2234 | 0.6923 | 0.87 | 0.0165 | 0.2001 | 0.248 + j0.034 | 0.254 + j0.042 | 5458 | 193 | 194 |
1/0 | 302.26 | 2817 | 0.5512 | 0.69 | 0.0155 | 0.1936 | 0.193 + j0.032 | 0.199 + j0.04 | 5458 | 221 | 219 |
2/0 | 307.34 | 3551 | 0.4364 | 0.55 | 0.0143 | 0.1870 | 0.149 + j0.03 | 0.155 + j0.038 | 8577 | 253 | 246 |
3/0 | 320.04 | 4477 | 0.3445 | 0.44 | 0.0131 | 0.1804 | 0.115 + j0.028 | 0.121 + j0.036 | 8577 | 288 | 275 |
4/0 | 330.20 | 5647 | 0.2756 | 0.34 | 0.0122 | 0.1739 | 0.087 + j0.027 | 0.093 + j0.035 | 8577 | 327 | 305 |
250 | 340.36 | 6675 | 0.2329 | 0.30 | 0.0116 | 0.1706 | 0.072 + j0.025 | 0.078 + j0.034 | 10137 | 367 | 343 |
350 | 355.60 | 9345 | 0.1640 | 0.21 | 0.0101 | 0.1608 | 0.047 + j0.023 | 0.053 + j0.031 | 13256 | 443 | 399 |
500 | 388.62 | 13350 | 0.1148 | 0.15 | 0.0088 | 0.1542 | 0.028 + j0.021 | 0.034 + j0.029 | 16376 | 529 | 451 |
750 | 431.80 | 20025 | 0.0787 | 0.11 | 0.0076 | 0.1444 | 0.015 + j0.019 | 0.021 + j0.028 | 21062 | 633 | 505 |
1000 | 459.74 | 26700 | 0.0591 | 0.09 | 0.0067 | 0.1378 | 0.008 + j0.018 | 0.015 + j0.026 | 21062 | 711 | 544 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C