SPEC 26425

HVTECK AL 1/C 260NLEPR CB PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchmilinchlb/1000ft
    TBA1190.2980.8562600.9167 x 141.542601.6621045
    TBA1/0190.3360.8942600.9547 x 141.580601.7001101
    TBA2/0190.3760.9342600.99411 x 141.620601.7401219
    TBA3/0190.4220.9802601.04011 x 141.690601.8101329
    TBA4/0190.4741.0322601.09211 x 141.742601.8621421
    TBA250370.5201.0862601.14613 x 141.796601.9161539
    TBA350370.6151.1812601.24117 x 141.891602.0111872
    TBA500370.7351.3012601.36121 x 142.071602.1912311
    TBA750610.9081.4842601.54417 x 122.288752.4382914
    TBA1000611.0601.6362601.69617 x 122.440752.5903321
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    111.65020.2110.2660.0540.0610.248 + j0.0340.254 + j0.0425458193194
    1/011.96330.1680.2110.0510.0590.193 + j0.0320.199 + j0.045458221219
    2/012.17980.1330.1670.0470.0570.149 + j0.030.155 + j0.0388577253246
    3/012.610060.1050.1330.0430.0550.115 + j0.0280.121 + j0.0368577288275
    4/013.012690.0840.1050.0400.0530.087 + j0.0270.093 + j0.0358577327305
    25013.415000.0710.0900.0380.0520.072 + j0.0250.078 + j0.03410137367343
    35014.021000.0500.0650.0330.0490.047 + j0.0230.053 + j0.03113256443399
    50015.330000.0350.0460.0290.0470.028 + j0.0210.034 + j0.02916376529451
    75017.045000.0240.0330.0250.0440.015 + j0.0190.021 + j0.02821062633505
    100018.160000.0180.0260.0220.0420.008 + j0.0180.015 + j0.02621062711544
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmkg/km
    TBA1197.5721.746.6023.277 x 1439.171.5242.211555
    TBA1/0198.5322.716.6024.237 x 1440.131.5243.181638
    TBA2/0199.5523.726.6025.2511 x 1441.151.5244.201814
    TBA3/01910.7224.896.6026.4211 x 1442.931.5245.971978
    TBA4/01912.0426.216.6027.7411 x 1444.251.5247.292115
    TBA2503713.2127.586.6029.1113 x 1445.621.5248.672290
    TBA3503715.6230.006.6031.5217 x 1448.031.5251.082786
    TBA5003718.6733.056.6034.5721 x 1452.601.5255.653439
    TBA7506123.0637.696.6039.2217 x 1258.121.9161.934337
    TBA10006126.9241.556.6043.0817 x 1261.981.9165.794942
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1294.6422340.69230.870.01650.20010.248 + j0.0340.254 + j0.0425458193194
    1/0302.2628170.55120.690.01550.19360.193 + j0.0320.199 + j0.045458221219
    2/0307.3435510.43640.550.01430.18700.149 + j0.030.155 + j0.0388577253246
    3/0320.0444770.34450.440.01310.18040.115 + j0.0280.121 + j0.0368577288275
    4/0330.2056470.27560.340.01220.17390.087 + j0.0270.093 + j0.0358577327305
    250340.3666750.23290.300.01160.17060.072 + j0.0250.078 + j0.03410137367343
    350355.6093450.16400.210.01010.16080.047 + j0.0230.053 + j0.03113256443399
    500388.62133500.11480.150.00880.15420.028 + j0.0210.034 + j0.02916376529451
    750431.80200250.07870.110.00760.14440.015 + j0.0190.021 + j0.02821062633505
    1000459.74267000.05910.090.00670.13780.008 + j0.0180.015 + j0.02621062711544
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C