SPEC 26421

HVTECK AL 1/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchinchmilinchlb/1000ft
    TBA1190.2980.8562600.9161.428501.528944
    TBA1/0190.3360.8942600.9541.466501.5661002
    TBA2/0190.3760.9342600.9941.506601.6261100
    TBA3/0190.4220.9802601.0401.552601.6721181
    TBA4/0190.4741.0322601.0921.604601.7241275
    TBA250370.5201.0862601.1461.682601.8021403
    TBA350370.6151.1812601.2411.777601.8971596
    TBA500370.7351.3012601.3611.897602.0171959
    TBA750610.9081.4842601.5442.140602.2602528
    TBA1000611.0601.6362601.6962.292752.4423014
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    110.65020.2110.2660.0540.0590.626 + j0.3840.267 + j0.0582838193194
    1/010.96330.1680.2110.0510.0570.57 + j0.3680.212 + j0.0562955221219
    2/011.37980.1330.1670.0470.0550.523 + j0.3530.168 + j0.0543079253246
    3/011.710060.1050.1330.0430.0530.487 + j0.3360.134 + j0.0523222288275
    4/012.012690.0840.1050.0400.0510.455 + j0.3190.106 + j0.053383327305
    25012.615000.0710.0900.0380.0500.436 + j0.3030.091 + j0.0493550367343
    35013.221000.0500.0650.0330.0480.403 + j0.2760.066 + j0.0463845443399
    50014.130000.0350.0460.0290.0450.373 + j0.2470.047 + j0.0434216529451
    75015.845000.0240.0330.0250.0430.343 + j0.210.034 + j0.0414783633505
    100017.060000.0180.0260.0220.0410.322 + j0.1860.027 + j0.045254711544
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmkg/km
    TBA1197.5721.746.6023.2736.271.2738.811405
    TBA1/0198.5322.716.6024.2337.241.2739.781491
    TBA2/0199.5523.726.6025.2538.251.5241.301637
    TBA3/01910.7224.896.6026.4239.421.5242.471758
    TBA4/01912.0426.216.6027.7440.741.5243.791897
    TBA2503713.2127.586.6029.1142.721.5245.772088
    TBA3503715.6230.006.6031.5245.141.5248.182375
    TBA5003718.6733.056.6034.5748.181.5251.232915
    TBA7506123.0637.696.6039.2254.361.5257.403762
    TBA10006126.9241.556.6043.0858.221.9162.034485
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1269.2422340.69230.870.01650.19360.626 + j0.3840.267 + j0.0582838193194
    1/0276.8628170.55120.690.01550.18700.57 + j0.3680.212 + j0.0562955221219
    2/0287.0235510.43640.550.01430.18040.523 + j0.3530.168 + j0.0543079253246
    3/0297.1844770.34450.440.01310.17390.487 + j0.3360.134 + j0.0523222288275
    4/0304.8056470.27560.340.01220.16730.455 + j0.3190.106 + j0.053383327305
    250320.0466750.23290.300.01160.16400.436 + j0.3030.091 + j0.0493550367343
    350335.2893450.16400.210.01010.15750.403 + j0.2760.066 + j0.0463845443399
    500358.14133500.11480.150.00880.14760.373 + j0.2470.047 + j0.0434216529451
    750401.32200250.07870.110.00760.14110.343 + j0.210.034 + j0.0414783633505
    1000431.80267000.05910.090.00670.13450.322 + j0.1860.027 + j0.045254711544
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I