SPEC 26361

HVTECK AL 3/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA

3 Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    TBA270.2680.6561750.71681102.165602.2852116
    TBA1190.2980.6861750.74661102.230602.3502253
    TBA1/0190.3360.7241750.78461102.312752.4622501
    TBA2/0190.3760.7641750.82461102.399752.5492703
    TBA3/0190.4220.8101750.87061102.498752.6482942
    578144^4/0180.4740.8631750.92341102.607602.7273356
    578135^250350.5200.9161750.97641102.721602.8413856
    TBA350370.6151.0111751.07141102.932753.0824102
    TBA500370.7351.1311751.19131253.221853.3915080
    578149^750580.9081.3261751.4061/01253.700703.8406668
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    215.911940.2670.3360.0460.0450.71 + j0.470.336 + j0.0452218135157
    116.415060.2110.2660.0430.0430.641 + j0.4530.266 + j0.0422311154178
    1/017.219000.1680.2110.0400.0420.586 + j0.4340.211 + j0.042429176202
    2/017.823950.1330.1670.0360.0400.541 + j0.4150.167 + j0.0392552204229
    3/018.530200.1050.1330.0330.0390.506 + j0.3940.133 + j0.0372695234260
    4/019.038080.0840.1050.0310.0370.476 + j0.3720.105 + j0.0362856268294
    25019.845000.0710.0900.0290.0370.457 + j0.3520.09 + j0.0353024296323
    35021.563000.0500.0650.0250.0350.425 + j0.3190.065 + j0.0333318363386
    50023.790000.0350.0460.0220.0330.396 + j0.2830.046 + j0.0323689447465
    75026.8135000.0240.0330.0190.0320.365 + j0.2380.033 + j0.034257566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    TBA276.8116.664.4418.1982.7954.991.5258.043149
    TBA1197.5717.424.4418.9562.7956.641.5259.693353
    TBA1/0198.5318.394.4419.9162.7958.721.9162.533722
    TBA2/0199.5519.414.4420.9362.7960.931.9164.744023
    TBA3/01910.7220.574.4422.1062.7963.451.9167.264378
    578144^4/01812.0421.924.4423.4442.7966.221.5269.274994
    578135^2503513.2123.274.4424.7942.7969.111.5272.165738
    TBA3503715.6225.684.4427.2042.7974.471.9178.286104
    TBA5003718.6728.734.4430.2533.1881.812.1686.137560
    578149^7505823.0633.684.4435.711/03.1893.981.7897.549923
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2403.8653130.87601.100.01400.14760.71 + j0.470.336 + j0.0452218135157
    1416.5667020.69230.870.01310.14110.641 + j0.4530.266 + j0.0422311154178
    1/0436.8884550.55120.690.01220.13780.586 + j0.4340.211 + j0.042429176202
    2/0452.12106580.43640.550.01100.13120.541 + j0.4150.167 + j0.0392552204229
    3/0469.90134390.34450.440.01010.12800.506 + j0.3940.133 + j0.0372695234260
    4/0482.60169460.27560.340.00940.12140.476 + j0.3720.105 + j0.0362856268294
    250502.92200250.23290.300.00880.12140.457 + j0.3520.09 + j0.0353024296323
    350546.10280350.16400.210.00760.11480.425 + j0.3190.065 + j0.0333318363386
    500601.98400500.11480.150.00670.10830.396 + j0.2830.046 + j0.0323689447465
    750680.72600750.07870.110.00580.10500.365 + j0.2380.033 + j0.034257566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.