SPEC 26342

HVTECK CU 3/C 220NLEPR TS PVC AIA PVC 15kV 133% CSA

3 Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA). (Optional galvanized steel armour GSIA available upon request)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 220 NLEPR AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGinchmilinchlb/1000ft
    576232270.2820.7612200.82162.387752.5373035
    648836^1190.3220.8002200.86062.471752.6213333
    TBA1/0190.3610.8392200.89962.561752.7113632
    583354^2/0190.4050.8842200.94442.652752.8024078
    5762272/0190.4050.8842200.94442.652752.8024089
    TBA3/0190.4560.9342200.99442.766752.9164533
    5761674/0190.5120.9762201.03632.851753.0015181
    576228250370.5581.0282201.10823.007853.1775915
    576229350370.6611.1272201.18723.227853.3977242
    672302?500370.7891.2522201.31213.497853.6679657
    583355^500370.7891.2522201.31213.497853.6679135
    576230500370.7891.2522201.31213.497853.6679152
    665338^750610.9681.4642201.52423.955854.12512172
    581926750610.9681.4642201.5242/03.955854.12512385
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^ Black outer jacket
    † 3-#1awg grounds equal to 50% of the phase conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    217.715920.1620.2040.0510.0470.579 + j0.4250.204 + j0.0482540172201
    118.320080.1280.1620.0470.0450.535 + j0.4060.162 + j0.0452664197228
    1/018.925340.1020.1280.0430.0430.5 + j0.3890.128 + j0.0432785225257
    2/019.631940.0810.1020.0400.0420.471 + j0.370.102 + j0.0422921260292
    2/019.631940.0810.1020.0400.0420.471 + j0.370.102 + j0.0422921260292
    3/020.440270.0640.0810.0370.0400.447 + j0.3510.081 + j0.043079297330
    4/021.050780.0510.0650.0340.0390.427 + j0.3310.065 + j0.0393253342372
    25022.260000.0430.0560.0320.0380.413 + j0.3130.056 + j0.0383420376410
    35023.784000.0310.0410.0280.0360.389 + j0.2830.041 + j0.0363739460487
    50025.6120000.0220.0300.0250.0340.366 + j0.2510.03 + j0.0344136556573
    50025.6120000.0220.0300.0250.0340.366 + j0.2510.03 + j0.0344136556573
    50025.6120000.0220.0300.0250.0340.366 + j0.2510.03 + j0.0344136556573
    75028.8180000.0140.0230.0210.0320.34 + j0.2120.024 + j0.0324721678668
    75028.8180000.0140.0230.0210.0320.34 + j0.2120.024 + j0.0324721678668
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmkg/km
    576232277.1619.335.5920.85660.631.9164.444517
    648836^1198.1820.325.5921.84662.761.9166.574960
    TBA1/0199.1721.315.5922.83665.051.9168.865405
    583354^2/01910.2922.455.5923.98467.361.9171.176069
    5762272/01910.2922.455.5923.98467.361.9171.176085
    TBA3/01911.5823.725.5925.25470.261.9174.076746
    5761674/01913.0024.795.5926.31372.421.9176.237710
    5762282503714.1726.115.5928.14276.382.1680.708802
    5762293503716.7928.635.5930.15281.972.1686.2810777
    672302?5003720.0431.805.5933.32188.822.1693.1414371
    583355^5003720.0431.805.5933.32188.822.1693.1413594
    5762305003720.0431.805.5933.32188.822.1693.1413620
    665338^7506124.5937.195.5938.712100.462.16104.7718114
    5819267506124.5937.195.5938.712/0100.462.16104.7718431
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^ Black outer jacket
    † 3-#1awg grounds equal to 50% of the phase conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2449.5870840.53150.670.01550.15420.579 + j0.4250.204 + j0.0482540172201
    1464.8289360.41990.530.01430.14760.535 + j0.4060.162 + j0.0452664197228
    1/0480.06112760.33460.420.01310.14110.5 + j0.3890.128 + j0.0432785225257
    2/0497.84142130.26570.330.01220.13780.471 + j0.370.102 + j0.0422921260292
    2/0497.84142130.26570.330.01220.13780.471 + j0.370.102 + j0.0422921260292
    3/0518.16179200.21000.270.01130.13120.447 + j0.3510.081 + j0.043079297330
    4/0533.40225970.16730.210.01040.12800.427 + j0.3310.065 + j0.0393253342372
    250563.88267000.14110.180.00980.12470.413 + j0.3130.056 + j0.0383420376410
    350601.98373800.10170.130.00850.11810.389 + j0.2830.041 + j0.0363739460487
    500650.24534000.07220.100.00760.11150.366 + j0.2510.03 + j0.0344136556573
    500650.24534000.07220.100.00760.11150.366 + j0.2510.03 + j0.0344136556573
    500650.24534000.07220.100.00760.11150.366 + j0.2510.03 + j0.0344136556573
    750731.52801000.04590.080.00640.10500.34 + j0.2120.024 + j0.0324721678668
    750731.52801000.04590.080.00640.10500.34 + j0.2120.024 + j0.0324721678668
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C