SPEC 26326

HVTECK AL 1/C 220NLEPR CB PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2680.7462200.8067x14801.426501.526878
    1190.2980.7762200.8367x14801.456501.556921
    1/0190.3360.8142200.8747x14801.494501.594975
    2/0190.3760.8542200.91411x14801.534601.6541121
    3/0190.4220.9002200.96011x14801.580601.7001195
    4/0190.4740.9522201.01211x14801.656601.7761314
    250370.5201.0062201.06613x14801.710601.8301429
    350370.6151.1012201.16117x14801.839601.9591679
    500370.7351.2212201.28121x14801.959602.0792080
    750610.9081.4042201.46417x121102.202602.3222695
    1000611.0601.5562201.61617x121102.354752.5043162
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    218.33980.2670.3360.0490.0620.695 + j0.4260.337 + j0.0615458169176
    118.75020.2110.2660.0460.0600.625 + j0.4110.267 + j0.0585458194198
    1/019.16330.1680.2110.0430.0570.569 + j0.3940.212 + j0.0565458222223
    2/019.87980.1330.1670.0400.0560.524 + j0.3780.168 + j0.0548577255250
    3/020.410060.1050.1330.0370.0540.488 + j0.3600.134 + j0.0528577290278
    4/021.312690.0840.1050.0340.0520.457 + j0.3410.106 + j0.0508577329309
    25022.015000.0710.0900.0320.0510.439 + j0.3230.091 + j0.04910137370347
    35023.521000.0500.0650.0280.0480.407 + j0.2950.066 + j0.04713256446402
    50024.930000.0350.0460.0240.0460.378 + j0.2630.047 + j0.04416376533451
    75027.945000.0240.0330.0210.0430.348 + j0.2240.034 + j0.04221062631500
    100030.060000.0180.0260.0180.0410.327 + j0.1970.027 + j0.04021062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    276.8118.955.5920.477x142.0336.221.2738.761307
    1197.5719.715.5921.237x142.0336.981.2739.521371
    1/0198.5320.685.5922.207x142.0337.951.2740.491451
    2/0199.5521.695.5923.2211x142.0338.961.5242.011668
    3/01910.7222.865.5924.3811x142.0340.131.5243.181778
    4/01912.0424.185.5925.7011x142.0342.061.5245.111955
    2503713.2125.555.5927.0813x142.0343.431.5246.482127
    3503715.6227.975.5929.4917x142.0346.711.5249.762499
    5003718.6731.015.5932.5421x142.0349.761.5252.813095
    7506123.0635.665.5937.1917x122.7955.931.5258.984011
    10006126.9239.525.5941.0517x122.7959.791.9163.604706
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2464.8217710.87601.100.01490.20340.695 + j0.4260.337 + j0.0615458169176
    1474.9822340.69230.870.01400.19690.625 + j0.4110.267 + j0.0585458194198
    1/0485.1428170.55120.690.01310.18700.569 + j0.3940.212 + j0.0565458222223
    2/0502.9235510.43640.550.01220.18370.524 + j0.3780.168 + j0.0548577255250
    3/0518.1644770.34450.440.01130.17720.488 + j0.3600.134 + j0.0528577290278
    4/0541.0256470.27560.340.01040.17060.457 + j0.3410.106 + j0.0508577329309
    250558.8066750.23290.300.00980.16730.439 + j0.3230.091 + j0.04910137370347
    350596.9093450.16400.210.00850.15750.407 + j0.2950.066 + j0.04713256446402
    500632.46133500.11480.150.00730.15090.378 + j0.2630.047 + j0.04416376533451
    750708.66200250.07870.110.00640.14110.348 + j0.2240.034 + j0.04221062631500
    1000762.00267000.05910.090.00550.13450.327 + j0.1970.027 + j0.04021062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC