SPEC 26316

HVTECK CU 1/C 220TRXLPE CB PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    TBA270.2820.7602200.8207 x 14801.446501.5461033
    TBA1190.3220.8002200.86011 x 14801.486501.5861176
    TBA1/0190.3610.8392200.89911 x 14801.525601.6451308
    TBA2/0190.4050.8832200.94311 x 14801.569601.6891433
    TBA3/0190.4560.9342200.99413 x 14801.620601.7401613
    TBA4/0190.5120.9902201.05013 x 14801.700601.8201831
    TBA250370.5581.0442201.10417 x 14801.754601.8742054
    TBA350370.6611.1472201.20721 x 14801.857601.9772602
    672982500370.7891.2752201.33524 X 14801.973602.0933118
    668996750610.9681.4642201.52430 X 141102.222602.3424258
    TBA750610.9681.4642201.52421 x 121102.268752.4184524
    6729861000611.1171.6132201.67333 X 141102.369752.5195277
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    210.85300.1620.2040.0670.0610.186 + j0.0350.192 + j0.0435458215221
    111.16690.1280.1620.0610.0580.144 + j0.0320.15 + j0.048577245247
    1/011.58440.1020.1280.0570.0570.11 + j0.0310.116 + j0.0398577278275
    2/011.810640.0810.1020.0530.0550.084 + j0.0290.09 + j0.0378577317306
    3/012.113420.0640.0810.0480.0520.063 + j0.0270.069 + j0.03510137357335
    4/012.716920.0510.0650.0440.0510.047 + j0.0260.053 + j0.03410137404369
    25013.120000.0430.0560.0420.0500.038 + j0.0250.044 + j0.03313256456412
    35013.828000.0310.0410.0370.0470.023 + j0.0230.029 + j0.03116376537456
    50014.640000.0220.0300.0320.0440.012 + j0.0210.018 + j0.02920275616497
    75016.360000.0140.0230.0280.0430.005 + j0.0190.011 + j0.02726018706551
    75016.960000.0140.0230.0280.0430.005 + j0.0190.011 + j0.02726018706551
    100017.680000.0110.0190.0250.0410.001 + j0.0180.008 + j0.02626018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA277.1619.305.5920.837 x 142.0336.731.2739.271537
    TBA1198.1820.325.5921.8411 x 142.0337.741.2740.281750
    TBA1/0199.1721.315.5922.8311 x 142.0338.731.5241.781947
    TBA2/01910.2922.435.5923.9511 x 142.0339.851.5242.902133
    TBA3/01911.5823.725.5925.2513 x 142.0341.151.5244.202400
    TBA4/01913.0025.155.5926.6713 x 142.0343.181.5246.232725
    TBA2503714.1726.525.5928.0417 x 142.0344.551.5247.603057
    TBA3503716.7929.135.5930.6621 x 142.0347.171.5250.223872
    6729825003720.0432.395.5933.9124 X 142.0350.111.5253.164640
    6689967506124.5937.195.5938.7130 X 142.7956.441.5259.496337
    TBA7506124.5937.195.5938.7121 x 122.7957.611.9161.426732
    67298610006128.3740.975.5942.4933 X 142.7960.171.9163.987853
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2274.3223590.53150.670.02040.20010.186 + j0.0350.192 + j0.0435458215221
    1281.9429770.41990.530.01860.19030.144 + j0.0320.15 + j0.048577245247
    1/0292.1037560.33460.420.01740.18700.11 + j0.0310.116 + j0.0398577278275
    2/0299.7247350.26570.330.01620.18040.084 + j0.0290.09 + j0.0378577317306
    3/0307.3459720.21000.270.01460.17060.063 + j0.0270.069 + j0.03510137357335
    4/0322.5875290.16730.210.01340.16730.047 + j0.0260.053 + j0.03410137404369
    250332.7489000.14110.180.01280.16400.038 + j0.0250.044 + j0.03313256456412
    350350.52124600.10170.130.01130.15420.023 + j0.0230.029 + j0.03116376537456
    500370.84178000.07220.100.00980.14440.012 + j0.0210.018 + j0.02920275616497
    750414.02267000.04590.080.00850.14110.005 + j0.0190.011 + j0.02726018706551
    750429.26267000.04590.080.00850.14110.005 + j0.0190.011 + j0.02726018706551
    1000447.04356000.03610.060.00760.13450.001 + j0.0180.008 + j0.02626018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC