SPEC 26316
HVTECK CU 1/C 220TRXLPE CB PVC AIA PVC 15kV 133% CSA
Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 2 | 7 | 0.283 | 0.761 | 220 | 0.821 | 5x12 | 80 | 1.581 | 60 | 1.701 | 354 | 1586 | 4.5 |
| TBA | 1 | 19 | 0.322 | 0.8 | 220 | 0.86 | 7x12 | 80 | 1.62 | 60 | 1.74 | 458 | 1738 | 4.5 |
| TBA | 1/0 | 19 | 0.362 | 0.84 | 220 | 0.9 | 7x12 | 80 | 1.66 | 60 | 1.78 | 529 | 1858 | 4.5 |
| TBA | 2/0 | 19 | 0.405 | 0.883 | 220 | 0.943 | 7x12 | 80 | 1.703 | 60 | 1.823 | 618 | 2001 | 4.5 |
| TBA | 3/0 | 19 | 0.456 | 0.934 | 220 | 0.994 | 9x12 | 80 | 1.754 | 60 | 1.874 | 763 | 2209 | 5 |
| TBA | 4/0 | 19 | 0.512 | 0.99 | 220 | 1.05 | 9x12 | 80 | 1.81 | 60 | 1.93 | 902 | 2417 | 5 |
| TBA | 250 | 37 | 0.558 | 1.044 | 220 | 1.104 | 11x12 | 80 | 1.864 | 60 | 1.984 | 1068 | 2654 | 5 |
| TBA | 350 | 37 | 0.661 | 1.147 | 220 | 1.207 | 13x12 | 80 | 1.967 | 60 | 2.087 | 1438 | 3152 | 5.5 |
| 672982 | 500 | 37 | 0.789 | 1.275 | 220 | 1.335 | 17x12 | 110 | 1.974 | 60 | 2.094 | 1864 | 3119 | 5.5 |
| 668996 | 750 | 61 | 0.968 | 1.464 | 220 | 1.524 | 21x12 | 110 | 2.223 | 60 | 2.343 | 2716 | 4259 | 6 |
| TBA | 750 | 61 | 0.968 | 1.464 | 220 | 1.524 | 21x12 | 110 | 2.344 | 75 | 2.494 | 2852 | 5165 | 6.5 |
| 672986 | 1000 | 61 | 1.117 | 1.613 | 220 | 1.673 | 21x12 | 110 | 2.37 | 75 | 2.52 | 3528 | 5277 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 11.9 | 530 | 0.162 | 0.221 | 0.059 | 0.063 | 0.518+j0.202 | 0.224+j0.069 | 2770 | 215 | 221 |
| 1 | 12.2 | 669 | 0.128 | 0.175 | 0.054 | 0.06 | 0.418+j0.130 | 0.179+j0.066 | 3879 | 245 | 247 |
| 1/0 | 12.5 | 844 | 0.102 | 0.139 | 0.05 | 0.058 | 0.381+j0.129 | 0.143+j0.063 | 3879 | 278 | 275 |
| 2/0 | 12.8 | 1064 | 0.082 | 0.112 | 0.047 | 0.056 | 0.354+j0.127 | 0.116+j0.061 | 3879 | 317 | 306 |
| 3/0 | 13.1 | 1342 | 0.064 | 0.087 | 0.043 | 0.054 | 0.288+j0.091 | 0.092+j0.059 | 4987 | 357 | 335 |
| 4/0 | 13.5 | 1692 | 0.051 | 0.07 | 0.04 | 0.052 | 0.270+j0.090 | 0.075+j0.057 | 4987 | 404 | 369 |
| 250 | 13.9 | 2000 | 0.043 | 0.059 | 0.037 | 0.051 | 0.229+j0.069 | 0.065+j0.055 | 6095 | 456 | 412 |
| 350 | 14.6 | 2800 | 0.031 | 0.043 | 0.033 | 0.048 | 0.190+j0.055 | 0.049+j0.052 | 7203 | 537 | 456 |
| 500 | 14.7 | 4000 | 0.021 | 0.03 | 0.029 | 0.044 | 0.145+j0.040 | 0.037+j0.048 | 9420 | 616 | 497 |
| 750 | 16.4 | 6000 | 0.014 | 0.021 | 0.024 | 0.042 | 0.115+j0.031 | 0.029+j0.045 | 11636 | 706 | 551 |
| 750 | 17.5 | 6000 | 0.014 | 0.021 | 0.024 | 0.043 | 0.115+j0.031 | 0.030+j0.046 | 11636 | 706 | 551 |
| 1000 | 17.6 | 8000 | 0.011 | 0.018 | 0.022 | 0.04 | 0.112+j0.030 | 0.026+j0.043 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 2 | 7 | 7.19 | 19.33 | 5.59 | 20.85 | 5x12 | 2.03 | 40.16 | 1.52 | 43.21 | 527 | 2360 | 4.5 |
| TBA | 1 | 19 | 8.18 | 20.32 | 5.59 | 21.84 | 7x12 | 2.03 | 41.15 | 1.52 | 44.20 | 682 | 2586 | 4.5 |
| TBA | 1/0 | 19 | 9.19 | 21.34 | 5.59 | 22.86 | 7x12 | 2.03 | 42.16 | 1.52 | 45.21 | 787 | 2765 | 4.5 |
| TBA | 2/0 | 19 | 10.29 | 22.43 | 5.59 | 23.95 | 7x12 | 2.03 | 43.26 | 1.52 | 46.30 | 920 | 2978 | 4.5 |
| TBA | 3/0 | 19 | 11.58 | 23.72 | 5.59 | 25.25 | 9x12 | 2.03 | 44.55 | 1.52 | 47.60 | 1135 | 3287 | 5 |
| TBA | 4/0 | 19 | 13.00 | 25.15 | 5.59 | 26.67 | 9x12 | 2.03 | 45.97 | 1.52 | 49.02 | 1342 | 3597 | 5 |
| TBA | 250 | 37 | 14.17 | 26.52 | 5.59 | 28.04 | 11x12 | 2.03 | 47.35 | 1.52 | 50.39 | 1589 | 3950 | 5 |
| TBA | 350 | 37 | 16.79 | 29.13 | 5.59 | 30.66 | 13x12 | 2.03 | 49.96 | 1.52 | 53.01 | 2140 | 4691 | 5.5 |
| 672982 | 500 | 37 | 20.04 | 32.39 | 5.59 | 33.91 | 17x12 | 2.79 | 50.14 | 1.52 | 53.19 | 2774 | 4642 | 5.5 |
| 668996 | 750 | 61 | 24.59 | 37.19 | 5.59 | 38.71 | 21x12 | 2.79 | 56.46 | 1.52 | 59.51 | 4042 | 6338 | 6 |
| TBA | 750 | 61 | 24.59 | 37.19 | 5.59 | 38.71 | 21x12 | 2.79 | 59.54 | 1.91 | 63.35 | 4244 | 7686 | 6.5 |
| 672986 | 1000 | 61 | 28.37 | 40.97 | 5.59 | 42.49 | 21x12 | 2.79 | 60.20 | 1.91 | 64.01 | 5250 | 7853 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 302.26 | 2359 | 0.5315 | 0.73 | 0.0180 | 0.2067 | 0.518+j0.202 | 0.224+j0.069 | 2770 | 215 | 221 |
| 1 | 309.88 | 2977 | 0.4199 | 0.57 | 0.0165 | 0.1969 | 0.418+j0.130 | 0.179+j0.066 | 3879 | 245 | 247 |
| 1/0 | 317.50 | 3756 | 0.3346 | 0.46 | 0.0152 | 0.1903 | 0.381+j0.129 | 0.143+j0.063 | 3879 | 278 | 275 |
| 2/0 | 325.12 | 4735 | 0.2690 | 0.37 | 0.0143 | 0.1837 | 0.354+j0.127 | 0.116+j0.061 | 3879 | 317 | 306 |
| 3/0 | 332.74 | 5972 | 0.2100 | 0.29 | 0.0131 | 0.1772 | 0.288+j0.091 | 0.092+j0.059 | 4987 | 357 | 335 |
| 4/0 | 342.90 | 7529 | 0.1673 | 0.23 | 0.0122 | 0.1706 | 0.270+j0.090 | 0.075+j0.057 | 4987 | 404 | 369 |
| 250 | 353.06 | 8900 | 0.1411 | 0.19 | 0.0113 | 0.1673 | 0.229+j0.069 | 0.065+j0.055 | 6095 | 456 | 412 |
| 350 | 370.84 | 12460 | 0.1017 | 0.14 | 0.0101 | 0.1575 | 0.190+j0.055 | 0.049+j0.052 | 7203 | 537 | 456 |
| 500 | 373.38 | 17800 | 0.0689 | 0.10 | 0.0088 | 0.1444 | 0.145+j0.040 | 0.037+j0.048 | 9420 | 616 | 497 |
| 750 | 416.56 | 26700 | 0.0459 | 0.07 | 0.0073 | 0.1378 | 0.115+j0.031 | 0.029+j0.045 | 11636 | 706 | 551 |
| 750 | 444.50 | 26700 | 0.0459 | 0.07 | 0.0073 | 0.1411 | 0.115+j0.031 | 0.030+j0.046 | 11636 | 706 | 551 |
| 1000 | 447.04 | 35600 | 0.0361 | 0.06 | 0.0067 | 0.1312 | 0.112+j0.030 | 0.026+j0.043 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC