SPEC 26315

HVTECK CU 1/C 175TRXLPE CB PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 TRXLPE AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2820.6701750.7307 x 14801.356501.456939
    1190.3220.7101750.77011 x 14801.396501.4961078
    1/0190.3610.7491750.80911 x 14801.435501.5351175
    2/0190.4050.7931750.85311 x 14801.479501.5791296
    3/0190.4560.8441750.90413 x 14801.530601.6501503
    4/0190.5120.9001750.96013 x 14801.586601.7061682
    250370.5580.9541751.01417 x 14801.664601.7841935
    350370.6611.0571751.11721 x 14801.767601.8872385
    500370.7891.1851751.24526 x 14801.895602.0153115
    750610.9681.3741751.43421 x 121102.178602.2984291
    1000611.1171.5231751.58321 x 121102.327752.4775280
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    210.15300.1620.2040.0580.0590.186 + j0.0330.191 + j0.0415458215221
    110.46690.1280.1620.0530.0570.144 + j0.030.149 + j0.0388577245247
    1/010.78440.1020.1280.0490.0550.11 + j0.0290.115 + j0.0368577278275
    2/011.010640.0810.1020.0450.0530.084 + j0.0270.09 + j0.0358577317306
    3/011.513420.0640.0810.0410.0510.063 + j0.0250.069 + j0.03310137357335
    4/011.916920.0510.0650.0380.0490.047 + j0.0240.053 + j0.03210137404369
    25012.420000.0430.0560.0360.0480.038 + j0.0230.044 + j0.03113256456412
    35013.228000.0310.0410.0310.0460.023 + j0.0210.029 + j0.02916376537456
    50014.140000.0220.0300.0270.0430.012 + j0.0190.018 + j0.02720275616497
    75016.060000.0140.0230.0230.0420.005 + j0.0180.011 + j0.02626018706551
    100017.380000.0110.0190.0210.0400.001 + j0.0170.007 + j0.02526018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    277.1617.024.4418.547 x 142.0334.441.2736.981397
    1198.1818.034.4419.5611 x 142.0335.461.2738.001604
    1/0199.1719.024.4420.5511 x 142.0336.451.2738.991749
    2/01910.2920.144.4421.6711 x 142.0337.571.2740.111929
    3/01911.5821.444.4422.9613 x 142.0338.861.5241.912237
    4/01913.0022.864.4424.3813 x 142.0340.281.5243.332503
    2503714.1724.234.4425.7617 x 142.0342.271.5245.312880
    3503716.7926.854.4428.3721 x 142.0344.881.5247.933549
    5003720.0430.104.4431.6226 x 142.0348.131.5251.184636
    7506124.5934.904.4436.4221 x 122.7955.321.5258.376386
    10006128.3738.684.4440.2121 x 122.7959.111.9162.927858
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2256.5423590.53150.670.01770.19360.186 + j0.0330.191 + j0.0415458215221
    1264.1629770.41990.530.01620.18700.144 + j0.030.149 + j0.0388577245247
    1/0271.7837560.33460.420.01490.18040.11 + j0.0290.115 + j0.0368577278275
    2/0279.4047350.26570.330.01370.17390.084 + j0.0270.09 + j0.0358577317306
    3/0292.1059720.21000.270.01250.16730.063 + j0.0250.069 + j0.03310137357335
    4/0302.2675290.16730.210.01160.16080.047 + j0.0240.053 + j0.03210137404369
    250314.9689000.14110.180.01100.15750.038 + j0.0230.044 + j0.03113256456412
    350335.28124600.10170.130.00940.15090.023 + j0.0210.029 + j0.02916376537456
    500358.14178000.07220.100.00820.14110.012 + j0.0190.018 + j0.02720275616497
    750406.40267000.04590.080.00700.13780.005 + j0.0180.011 + j0.02626018706551
    1000439.42356000.03610.060.00640.13120.001 + j0.0170.007 + j0.02526018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC