SPEC 26312
HVTECK CU 1/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA
Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 2 | 7 | 0.283 | 0.761 | 220 | 0.821 | 80 | 1.211 | 50 | 1.311 | 273 | 984 | 3.5 |
| TBA | 1 | 19 | 0.322 | 0.8 | 220 | 0.86 | 80 | 1.25 | 50 | 1.35 | 329 | 1075 | 3.5 |
| TBA | 1/0 | 19 | 0.362 | 0.84 | 220 | 0.9 | 80 | 1.29 | 50 | 1.39 | 400 | 1182 | 3.5 |
| 670965 | 2/0 | 19 | 0.405 | 0.884 | 220 | 0.944 | 80 | 1.468 | 50 | 1.568 | 493 | 1327 | 4 |
| TBA | 3/0 | 19 | 0.456 | 0.934 | 220 | 0.994 | 80 | 1.384 | 50 | 1.484 | 600 | 1466 | 4 |
| 672441^ | 4/0 | 19 | 0.512 | 0.99 | 220 | 1.05 | 80 | 1.574 | 60 | 1.694 | 744 | 1693 | 4.5 |
| TBA | 250 | 37 | 0.558 | 1.044 | 220 | 1.104 | 80 | 1.594 | 60 | 1.714 | 863 | 2007 | 4.5 |
| 671319 | 350 | 37 | 0.661 | 1.147 | 220 | 1.207 | 80 | 1.731 | 60 | 1.851 | 1183 | 2274 | 5 |
| 672047 | 500 | 37 | 0.789 | 1.275 | 220 | 1.335 | 80 | 1.859 | 60 | 1.979 | 1656 | 2856 | 5 |
| 641194 | 750 | 61 | 0.968 | 1.464 | 220 | 1.524 | 110 | 2.108 | 60 | 2.228 | 2443 | 3928 | 6 |
| 672046 | 1000 | 61 | 1.117 | 1.613 | 220 | 1.673 | 110 | 2.257 | 75 | 2.407 | 3226 | 4918 | 6.5 |
| 672445^ | 1000 | 61 | 1.117 | 1.613 | 220 | 1.673 | 110 | 2.257 | 75 | 2.407 | 3226 | 4909 | 6.5 |
| TBA | 1250 | 91 | 1.25 | 1.75 | 220 | 1.81 | 110 | 2.36 | 75 | 2.51 | 4008 | 6075 | 6.5 |
| TBA | 1500 | 91 | 1.37 | 1.87 | 220 | 1.93 | 110 | 2.48 | 75 | 2.63 | 4790 | 6988 | 7 |
| TBA | 2000 | 127 | 1.583 | 2.083 | 220 | 2.143 | 110 | 2.693 | 75 | 2.843 | 6351 | 8783 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 9.2 | 530 | 0.162 | 0.221 | 0.059 | 0.057 | 0.574+j0.459 | 0.222+j0.063 | 2575 | 215 | 221 |
| 1 | 9.5 | 669 | 0.128 | 0.175 | 0.054 | 0.055 | 0.529+j0.442 | 0.176+j0.060 | 2696 | 245 | 247 |
| 1/0 | 9.7 | 844 | 0.102 | 0.139 | 0.05 | 0.053 | 0.494+j0.425 | 0.140+j0.058 | 2820 | 278 | 275 |
| 2/0 | 11 | 1064 | 0.082 | 0.112 | 0.047 | 0.053 | 0.465+j0.408 | 0.113+j0.058 | 2956 | 317 | 306 |
| 3/0 | 10.4 | 1342 | 0.064 | 0.087 | 0.043 | 0.049 | 0.441+j0.390 | 0.088+j0.054 | 3111 | 357 | 335 |
| 4/0 | 11.9 | 1692 | 0.051 | 0.07 | 0.04 | 0.049 | 0.421+j0.370 | 0.071+j0.055 | 3284 | 404 | 369 |
| 250 | 12 | 2000 | 0.043 | 0.059 | 0.037 | 0.047 | 0.409+j0.353 | 0.060+j0.053 | 3452 | 456 | 412 |
| 350 | 13 | 2800 | 0.031 | 0.043 | 0.033 | 0.045 | 0.387+j0.322 | 0.044+j0.051 | 3771 | 537 | 456 |
| 500 | 13.9 | 4000 | 0.021 | 0.03 | 0.029 | 0.043 | 0.367+j0.289 | 0.032+j0.048 | 4167 | 616 | 497 |
| 750 | 15.6 | 6000 | 0.014 | 0.021 | 0.024 | 0.041 | 0.344+j0.249 | 0.023+j0.046 | 4753 | 706 | 551 |
| 1000 | 16.8 | 8000 | 0.011 | 0.018 | 0.022 | 0.039 | 0.329+j0.222 | 0.020+j0.044 | 5215 | 813 | 596 |
| 1000 | 16.8 | 8000 | 0.011 | 0.018 | 0.022 | 0.039 | 0.329+j0.222 | 0.020+j0.044 | 5215 | 813 | 596 |
| 1250 | 17.6 | 10000 | 0.008 | 0.014 | 0.02 | 0.038 | 0.315+j0.201 | 0.016+j0.043 | 5639 | 889 | 632 |
| 1500 | 18.4 | 12000 | 0.007 | 0.014 | 0.018 | 0.037 | 0.305+j0.185 | 0.016+j0.042 | 6011 | 956 | 663 |
| 2000 | 19.9 | 16000 | 0.005 | 0.013 | 0.016 | 0.035 | 0.288+j0.160 | 0.015+j0.040 | 6671 | 1073 | 715 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 2 | 7 | 7.19 | 19.33 | 5.59 | 20.85 | 2.03 | 30.76 | 1.27 | 33.30 | 406 | 1464 | 3.5 |
| TBA | 1 | 19 | 8.18 | 20.32 | 5.59 | 21.84 | 2.03 | 31.75 | 1.27 | 34.29 | 490 | 1600 | 3.5 |
| TBA | 1/0 | 19 | 9.19 | 21.34 | 5.59 | 22.86 | 2.03 | 32.77 | 1.27 | 35.31 | 595 | 1759 | 3.5 |
| 670965 | 2/0 | 19 | 10.29 | 22.45 | 5.59 | 23.98 | 2.03 | 37.29 | 1.27 | 39.83 | 734 | 1975 | 4 |
| TBA | 3/0 | 19 | 11.58 | 23.72 | 5.59 | 25.25 | 2.03 | 35.15 | 1.27 | 37.69 | 893 | 2182 | 4 |
| 672441^ | 4/0 | 19 | 13.00 | 25.15 | 5.59 | 26.67 | 2.03 | 39.98 | 1.52 | 43.03 | 1107 | 2519 | 4.5 |
| TBA | 250 | 37 | 14.17 | 26.52 | 5.59 | 28.04 | 2.03 | 40.49 | 1.52 | 43.54 | 1284 | 2987 | 4.5 |
| 671319 | 350 | 37 | 16.79 | 29.13 | 5.59 | 30.66 | 2.03 | 43.97 | 1.52 | 47.02 | 1760 | 3384 | 5 |
| 672047 | 500 | 37 | 20.04 | 32.39 | 5.59 | 33.91 | 2.03 | 47.22 | 1.52 | 50.27 | 2464 | 4250 | 5 |
| 641194 | 750 | 61 | 24.59 | 37.19 | 5.59 | 38.71 | 2.79 | 53.54 | 1.52 | 56.59 | 3636 | 5846 | 6 |
| 672046 | 1000 | 61 | 28.37 | 40.97 | 5.59 | 42.49 | 2.79 | 57.33 | 1.91 | 61.14 | 4801 | 7319 | 6.5 |
| 672445^ | 1000 | 61 | 28.37 | 40.97 | 5.59 | 42.49 | 2.79 | 57.33 | 1.91 | 61.14 | 4801 | 7305 | 6.5 |
| TBA | 1250 | 91 | 31.75 | 44.45 | 5.59 | 45.97 | 2.79 | 59.94 | 1.91 | 63.75 | 5965 | 9041 | 6.5 |
| TBA | 1500 | 91 | 34.80 | 47.50 | 5.59 | 49.02 | 2.79 | 62.99 | 1.91 | 66.80 | 7128 | 10399 | 7 |
| TBA | 2000 | 127 | 40.21 | 52.91 | 5.59 | 54.43 | 2.79 | 68.40 | 1.91 | 72.21 | 9451 | 13071 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 233.68 | 2359 | 0.5315 | 0.73 | 0.0180 | 0.1870 | 0.574+j0.459 | 0.222+j0.063 | 2575 | 215 | 221 |
| 1 | 241.30 | 2977 | 0.4199 | 0.57 | 0.0165 | 0.1804 | 0.529+j0.442 | 0.176+j0.060 | 2696 | 245 | 247 |
| 1/0 | 246.38 | 3756 | 0.3346 | 0.46 | 0.0152 | 0.1739 | 0.494+j0.425 | 0.140+j0.058 | 2820 | 278 | 275 |
| 2/0 | 279.40 | 4735 | 0.2690 | 0.37 | 0.0143 | 0.1739 | 0.465+j0.408 | 0.113+j0.058 | 2956 | 317 | 306 |
| 3/0 | 264.16 | 5972 | 0.2100 | 0.29 | 0.0131 | 0.1608 | 0.441+j0.390 | 0.088+j0.054 | 3111 | 357 | 335 |
| 4/0 | 302.26 | 7529 | 0.1673 | 0.23 | 0.0122 | 0.1608 | 0.421+j0.370 | 0.071+j0.055 | 3284 | 404 | 369 |
| 250 | 304.80 | 8900 | 0.1411 | 0.19 | 0.0113 | 0.1542 | 0.409+j0.353 | 0.060+j0.053 | 3452 | 456 | 412 |
| 350 | 330.20 | 12460 | 0.1017 | 0.14 | 0.0101 | 0.1476 | 0.387+j0.322 | 0.044+j0.051 | 3771 | 537 | 456 |
| 500 | 353.06 | 17800 | 0.0689 | 0.10 | 0.0088 | 0.1411 | 0.367+j0.289 | 0.032+j0.048 | 4167 | 616 | 497 |
| 750 | 396.24 | 26700 | 0.0459 | 0.07 | 0.0073 | 0.1345 | 0.344+j0.249 | 0.023+j0.046 | 4753 | 706 | 551 |
| 1000 | 426.72 | 35600 | 0.0361 | 0.06 | 0.0067 | 0.1280 | 0.329+j0.222 | 0.020+j0.044 | 5215 | 813 | 596 |
| 1000 | 426.72 | 35600 | 0.0361 | 0.06 | 0.0067 | 0.1280 | 0.329+j0.222 | 0.020+j0.044 | 5215 | 813 | 596 |
| 1250 | 447.04 | 44500 | 0.0262 | 0.05 | 0.0061 | 0.1247 | 0.315+j0.201 | 0.016+j0.043 | 5639 | 889 | 632 |
| 1500 | 467.36 | 53400 | 0.0230 | 0.05 | 0.0055 | 0.1214 | 0.305+j0.185 | 0.016+j0.042 | 6011 | 956 | 663 |
| 2000 | 505.46 | 71200 | 0.0164 | 0.04 | 0.0049 | 0.1148 | 0.288+j0.160 | 0.015+j0.040 | 6671 | 1073 | 715 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A