SPEC 26241

HVTECK CU 3/C 115NLEPR TS PVC AIA PVC 8kV 100% CSA

3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 115 NLEPR AIA 8kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    270.2820.5501150.6106801.876601.9962059
    1190.3220.5901150.6506801.963602.0832322
    1/0190.3610.6291150.68961102.107602.2272744
    2/0190.4050.6731150.73361102.202602.3223118
    3/0190.4560.7241150.78441102.312752.4623652
    4/0190.5120.7801150.84041102.433752.5834216
    250370.5580.8341150.89441102.550752.7004738
    350370.6610.9371150.99731102.772752.9225967
    500370.7891.0651151.12531103.049853.2197804
    750610.9681.2541151.31421253.487853.65710838
    1000611.1171.4031151.46311253.809853.97913652
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    213.915920.1620.2040.0340.0400.572 + j0.5220.204 + j0.0411889172201
    114.520080.1280.1620.0310.0390.534 + j0.4980.162 + j0.0392013197228
    1/015.525340.1020.1280.0280.0370.502 + j0.4760.128 + j0.0372134225257
    2/016.231940.0810.1020.0260.0360.477 + j0.4530.102 + j0.0362270260292
    3/017.240270.0640.0810.0240.0350.456 + j0.4280.081 + j0.0352429297330
    4/018.050780.0510.0650.0210.0340.439 + j0.4030.065 + j0.0342602342372
    25018.960000.0430.0560.0200.0330.428 + j0.380.056 + j0.0332769376410
    35020.484000.0310.0410.0180.0320.407 + j0.3410.041 + j0.0323088460487
    50022.5120000.0220.0300.0150.0300.386 + j0.30.03 + j0.033485556573
    75025.5180000.0140.0230.0130.0290.361 + j0.250.023 + j0.0294071678668
    100027.8240000.0110.0190.0110.0280.342 + j0.2190.02 + j0.0284532798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    277.1613.972.9215.4962.0347.651.5250.703064
    1198.1814.992.9216.5162.0349.861.5252.913456
    1/0199.1715.982.9217.5062.7953.521.5256.574084
    2/01910.2917.092.9218.6262.7955.931.5258.984640
    3/01911.5818.392.9219.9142.7958.721.9162.535435
    4/01913.0019.812.9221.3442.7961.801.9165.616274
    2503714.1721.182.9222.7142.7964.771.9168.587051
    3503716.7923.802.9225.3232.7970.411.9174.228880
    5003720.0427.052.9228.5832.7977.442.1681.7611614
    7506124.5931.852.9233.3823.1888.572.1692.8916129
    10006128.3735.642.9237.1613.1896.752.16101.0720316
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2353.0670840.53150.670.01040.13120.572 + j0.5220.204 + j0.0411889172201
    1368.3089360.41990.530.00940.12800.534 + j0.4980.162 + j0.0392013197228
    1/0393.70112760.33460.420.00850.12140.502 + j0.4760.128 + j0.0372134225257
    2/0411.48142130.26570.330.00790.11810.477 + j0.4530.102 + j0.0362270260292
    3/0436.88179200.21000.270.00730.11480.456 + j0.4280.081 + j0.0352429297330
    4/0457.20225970.16730.210.00640.11150.439 + j0.4030.065 + j0.0342602342372
    250480.06267000.14110.180.00610.10830.428 + j0.380.056 + j0.0332769376410
    350518.16373800.10170.130.00550.10500.407 + j0.3410.041 + j0.0323088460487
    500571.50534000.07220.100.00460.09840.386 + j0.30.03 + j0.033485556573
    750647.70801000.04590.080.00400.09510.361 + j0.250.023 + j0.0294071678668
    1000706.121068000.03610.060.00340.09190.342 + j0.2190.02 + j0.0284532798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.