SPEC 26241

HVTECK CU 3/C 115NLEPR TS PVC AIA PVC 8kV 100% CSA

3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 115 NLEPR AIA 8kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    270.2830.5511150.6111x66801.5061.816601.93685617692.5
    1190.3220.591150.651x66801.591.9602.02102620002.5
    1/0190.3620.631150.691x661101.7362.046602.166124222952.5
    2/0190.4050.6731150.7331x661101.8292.139602.259151026303
    3/0190.4560.7241150.7841x441101.9392.249602.369189530953
    4/0190.5120.781150.841x441102.062.37752.52231836723
    250370.5580.8341150.8941x441102.1772.487752.637269241473.5
    350370.6610.9371150.9971x331102.42.71752.86368853133.5
    500370.7891.0651151.1251x331102.6762.986753.136512369584
    750610.9681.2541151.3141x221253.1143.424853.594755197984.5
    1000611.1171.4031151.4631x111253.4363.746853.9169980124825
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    213.615920.1620.2210.0280.0240.577+j0.5560.221+j0.0411924172201
    114.120080.1280.1750.0260.0220.536+j0.5340.175+j0.0392045197228
    1/015.225340.1020.1390.0240.0210.503+j0.5130.139+j0.0372169225257
    2/015.831940.0820.1120.0220.020.479+j0.4920.112+j0.0362302260292
    3/016.640270.0640.0870.020.0190.457+j0.4680.087+j0.0352460297330
    4/017.650780.0510.070.0180.0170.441+j0.4430.070+j0.0342634342372
    25018.560000.0430.0590.0170.0170.430+j0.4210.059+j0.0332801376410
    3502084000.0310.0430.0150.0150.412+j0.3820.043+j0.0323120460487
    50022120000.0210.030.0130.0140.392+j0.3400.030+j0.0303517556573
    75025.2180000.0140.0210.0110.0130.370+j0.2880.021+j0.0294102678668
    100027.4240000.0110.0180.0090.0120.355+j0.2550.018+j0.0284564798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/kminch
    277.1914.002.9215.521x662.0338.2546.131.5249.17127426332.5
    1198.1814.992.9216.511x662.0340.3948.261.5251.31152729762.5
    1/0199.1916.002.9217.531x662.7944.0951.971.5255.02184834152.5
    2/01910.2917.092.9218.621x662.7946.4654.331.5257.38224739143
    3/01911.5818.392.9219.911x442.7949.2557.121.5260.17282046063
    4/01913.0019.812.9221.341x442.7952.3260.201.9164.01345054653
    2503714.1721.182.9222.711x442.7955.3063.171.9166.98400661713.5
    3503716.7923.802.9225.321x332.7960.9668.831.9172.64548879073.5
    5003720.0427.052.9228.581x332.7967.9775.841.9179.657624103554
    7506124.5931.852.9233.381x223.1879.1086.972.1691.2911237145814.5
    10006128.3735.642.9237.161x113.1887.2795.152.1699.4714852185755
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2345.4470840.53150.730.00850.07870.577+j0.5560.221+j0.0411924172201
    1358.1489360.41990.570.00790.07220.536+j0.5340.175+j0.0392045197228
    1/0386.08112760.33460.460.00730.06890.503+j0.5130.139+j0.0372169225257
    2/0401.32142130.26900.370.00670.06560.479+j0.4920.112+j0.0362302260292
    3/0421.64179200.21000.290.00610.06230.457+j0.4680.087+j0.0352460297330
    4/0447.04225970.16730.230.00550.05580.441+j0.4430.070+j0.0342634342372
    250469.90267000.14110.190.00520.05580.430+j0.4210.059+j0.0332801376410
    350508.00373800.10170.140.00460.04920.412+j0.3820.043+j0.0323120460487
    500558.80534000.06890.100.00400.04590.392+j0.3400.030+j0.0303517556573
    750640.08801000.04590.070.00340.04270.370+j0.2880.021+j0.0294102678668
    1000695.961068000.03610.060.00270.03940.355+j0.2550.018+j0.0284564798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC