SPEC 26225

HVTECK AL 1/C 115NLEPR CB PVC AIA PVC 8kV 100% CSA

Single Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 115 NLEPR AIA 8kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2680.5361150.5967 x 14801.112501.212660
    1190.2980.5661150.6267 x 14801.142501.242696
    1/0190.3360.6041150.6647 x 14801.180501.280744
    2/0190.3760.6441150.70411 x 14801.330501.430862
    3/0190.4220.6901150.75011 x 14801.376501.476927
    4/0190.4740.7421150.80211 x 14801.428501.5281004
    250370.5200.7961150.85613 x 14801.482501.5821107
    350370.6150.8911150.95117 x 14801.577601.6971354
    500370.7351.0111151.07121 x 14801.721601.8411670
    750610.9081.1941151.25417 x 12801.938602.0582229
    1000611.0601.3461151.40617 x 121102.150602.2702708
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    28.43980.2670.3360.0360.0560.318 + j0.0290.323 + j0.0375458169176
    18.65020.2110.2660.0330.0540.248 + j0.0260.253 + j0.0345458194198
    1/08.96330.1680.2110.0300.0520.193 + j0.0250.199 + j0.0335458222223
    2/010.07980.1330.1670.0280.0520.149 + j0.0230.154 + j0.0318577255250
    3/010.310060.1050.1330.0250.0500.115 + j0.0220.12 + j0.038577290278
    4/010.612690.0840.1050.0230.0490.087 + j0.020.092 + j0.0288577329309
    25011.015000.0710.0900.0220.0470.072 + j0.020.078 + j0.02710137370347
    35011.821000.0500.0650.0190.0450.047 + j0.0180.053 + j0.02613256446402
    50012.830000.0350.0460.0160.0430.028 + j0.0160.034 + j0.02416376533451
    75014.445000.0240.0330.0140.0410.015 + j0.0150.021 + j0.02321062631500
    100015.860000.0180.0260.0120.0390.008 + j0.0140.014 + j0.02221062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    276.8113.612.9215.147 x 142.0328.241.2730.78982
    1197.5714.382.9215.907 x 142.0329.011.2731.551036
    1/0198.5315.342.9216.877 x 142.0329.971.2732.511107
    2/0199.5516.362.9217.8811 x 142.0333.781.2736.321283
    3/01910.7217.532.9219.0511 x 142.0334.951.2737.491380
    4/01912.0418.852.9220.3711 x 142.0336.271.2738.811494
    2503713.2120.222.9221.7413 x 142.0337.641.2740.181647
    3503715.6222.632.9224.1617 x 142.0340.061.5243.102015
    5003718.6725.682.9227.2021 x 142.0343.711.5246.762485
    7506123.0630.332.9231.8517 x 122.0349.231.5252.273317
    10006126.9234.192.9235.7117 x 122.7954.611.5257.664030
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2213.3617710.87601.100.01100.18370.318 + j0.0290.323 + j0.0375458169176
    1218.4422340.69230.870.01010.17720.248 + j0.0260.253 + j0.0345458194198
    1/0226.0628170.55120.690.00910.17060.193 + j0.0250.199 + j0.0335458222223
    2/0254.0035510.43640.550.00850.17060.149 + j0.0230.154 + j0.0318577255250
    3/0261.6244770.34450.440.00760.16400.115 + j0.0220.12 + j0.038577290278
    4/0269.2456470.27560.340.00700.16080.087 + j0.020.092 + j0.0288577329309
    250279.4066750.23290.300.00670.15420.072 + j0.020.078 + j0.02710137370347
    350299.7293450.16400.210.00580.14760.047 + j0.0180.053 + j0.02613256446402
    500325.12133500.11480.150.00490.14110.028 + j0.0160.034 + j0.02416376533451
    750365.76200250.07870.110.00430.13450.015 + j0.0150.021 + j0.02321062631500
    1000401.32267000.05910.090.00370.12800.008 + j0.0140.014 + j0.02221062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC