SPEC 26125

HVTECK AL 1/C 90NLEPR CB PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 90 NLEPR AIA 5kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2680.486900.5467 x 14651.032501.132583
    1190.2980.516900.5767 x 14801.092501.192650
    1/0190.3360.554900.6147 x 14801.130501.230697
    2/0190.3760.594900.65411 x 14801.170501.270803
    3/0190.4220.640900.70011 x 14801.326501.426877
    4/0190.4740.692900.75211 x 14801.378501.478950
    250370.5200.746900.80613 x 14801.432501.5321052
    350370.6150.841900.90117 x 14801.527601.6471294
    500370.7350.961901.02121 x 14801.671601.7911604
    750610.9081.144901.20417 x 12801.888602.0082152
    1000611.0601.296901.35617 x 121102.100602.2202623
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    27.93980.2670.3360.0310.0550.318 + j0.0270.323 + j0.0355458169176
    18.35020.2110.2660.0280.0530.248 + j0.0250.253 + j0.0325458194198
    1/08.66330.1680.2110.0260.0520.193 + j0.0230.198 + j0.0315458222223
    2/08.87980.1330.1670.0230.0500.149 + j0.0220.155 + j0.038577255250
    3/09.910060.1050.1330.0210.0500.115 + j0.020.12 + j0.0288577290278
    4/010.312690.0840.1050.0190.0480.087 + j0.0190.092 + j0.0278577329309
    25010.715000.0710.0900.0180.0470.072 + j0.0180.077 + j0.02610137370347
    35011.521000.0500.0650.0160.0440.047 + j0.0170.053 + j0.02513256446402
    50012.530000.0350.0460.0130.0420.028 + j0.0150.034 + j0.02316376533451
    75014.045000.0240.0330.0120.0400.015 + j0.0140.021 + j0.02221062631500
    100015.560000.0180.0260.0100.0390.008 + j0.0130.014 + j0.02221062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    276.8112.342.2913.877 x 141.6526.211.2728.75868
    1197.5713.112.2914.637 x 142.0327.741.2730.28967
    1/0198.5314.072.2915.607 x 142.0328.701.2731.241037
    2/0199.5515.092.2916.6111 x 142.0329.721.2732.261195
    3/01910.7216.262.2917.7811 x 142.0333.681.2736.221305
    4/01912.0417.582.2919.1011 x 142.0335.001.2737.541414
    2503713.2118.952.2920.4713 x 142.0336.371.2738.911566
    3503715.6221.362.2922.8917 x 142.0338.791.5241.831926
    5003718.6724.412.2925.9321 x 142.0342.441.5245.492387
    7506123.0629.062.2930.5817 x 122.0347.961.5251.003203
    10006126.9232.922.2934.4417 x 122.7953.341.5256.393903
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2200.6617710.87601.100.00940.18040.318 + j0.0270.323 + j0.0355458169176
    1210.8222340.69230.870.00850.17390.248 + j0.0250.253 + j0.0325458194198
    1/0218.4428170.55120.690.00790.17060.193 + j0.0230.198 + j0.0315458222223
    2/0223.5235510.43640.550.00700.16400.149 + j0.0220.155 + j0.038577255250
    3/0251.4644770.34450.440.00640.16400.115 + j0.020.12 + j0.0288577290278
    4/0261.6256470.27560.340.00580.15750.087 + j0.0190.092 + j0.0278577329309
    250271.7866750.23290.300.00550.15420.072 + j0.0180.077 + j0.02610137370347
    350292.1093450.16400.210.00490.14440.047 + j0.0170.053 + j0.02513256446402
    500317.50133500.11480.150.00400.13780.028 + j0.0150.034 + j0.02316376533451
    750355.60200250.07870.110.00370.13120.015 + j0.0140.021 + j0.02221062631500
    1000393.70267000.05910.090.00300.12800.008 + j0.0130.014 + j0.02221062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC