SPEC 26116
HVTECK CU 1/C 115TRXLPE CB PVC AIA PVC 5kV 133% CSA
Single Conductor, 115 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 115 TRXLPE AIA 5kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.282 | 0.550 | 115 | 0.610 | 7 x 14 | 80 | 1.126 | 50 | 1.226 | 812 |
TBA | 1 | 19 | 0.322 | 0.590 | 115 | 0.650 | 11 x 14 | 80 | 1.166 | 50 | 1.266 | 947 |
TBA | 1/0 | 19 | 0.361 | 0.629 | 115 | 0.689 | 11 x 14 | 80 | 1.205 | 50 | 1.305 | 1041 |
TBA | 2/0 | 19 | 0.405 | 0.673 | 115 | 0.733 | 11 x 14 | 80 | 1.359 | 50 | 1.459 | 1167 |
TBA | 3/0 | 19 | 0.456 | 0.724 | 115 | 0.784 | 13 x 14 | 80 | 1.410 | 50 | 1.510 | 1337 |
TBA | 4/0 | 19 | 0.512 | 0.780 | 115 | 0.840 | 13 x 14 | 80 | 1.466 | 50 | 1.566 | 1511 |
TBA | 250 | 37 | 0.558 | 0.834 | 115 | 0.894 | 17 x 14 | 80 | 1.520 | 60 | 1.640 | 1755 |
588055 | 350 | 37 | 0.661 | 0.917 | 115 | 0.977 | 21 x 14 | 80 | 1.624 | 60 | 1.743 | 2225 |
TBA | 500 | 37 | 0.789 | 1.065 | 115 | 1.125 | 26 x 14 | 80 | 1.775 | 60 | 1.895 | 2850 |
TBA | 750 | 61 | 0.968 | 1.254 | 115 | 1.314 | 21 x 12 | 80 | 1.998 | 60 | 2.118 | 3969 |
TBA | 1000 | 61 | 1.117 | 1.403 | 115 | 1.463 | 21 x 12 | 110 | 2.207 | 60 | 2.327 | 4988 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ/1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 8.5 | 530 | 0.162 | 0.204 | 0.045 | 0.055 | 0.186 + j0.03 | 0.191 + j0.037 | 5458 | 215 | 221 |
1 | 8.8 | 669 | 0.128 | 0.162 | 0.041 | 0.053 | 0.144 + j0.027 | 0.15 + j0.035 | 8577 | 245 | 247 |
1/0 | 9.1 | 844 | 0.102 | 0.128 | 0.037 | 0.051 | 0.11 + j0.025 | 0.116 + j0.033 | 8577 | 278 | 275 |
2/0 | 10.2 | 1064 | 0.081 | 0.102 | 0.034 | 0.051 | 0.084 + j0.024 | 0.089 + j0.032 | 8577 | 317 | 306 |
3/0 | 10.5 | 1342 | 0.064 | 0.081 | 0.031 | 0.049 | 0.063 + j0.023 | 0.068 + j0.03 | 10137 | 357 | 335 |
4/0 | 10.9 | 1692 | 0.051 | 0.065 | 0.028 | 0.047 | 0.047 + j0.021 | 0.053 + j0.029 | 10137 | 404 | 369 |
250 | 11.4 | 2000 | 0.043 | 0.056 | 0.027 | 0.046 | 0.038 + j0.02 | 0.044 + j0.028 | 13256 | 456 | 412 |
350 | 12.3 | 2800 | 0.031 | 0.041 | 0.018 | 0.044 | 0.023 + j0.019 | 0.029 + j0.027 | 16376 | 537 | 456 |
500 | 13.2 | 4000 | 0.022 | 0.030 | 0.020 | 0.042 | 0.012 + j0.017 | 0.018 + j0.025 | 20275 | 616 | 497 |
750 | 14.8 | 6000 | 0.014 | 0.023 | 0.017 | 0.040 | 0.005 + j0.016 | 0.011 + j0.024 | 26018 | 706 | 551 |
1000 | 16.2 | 8000 | 0.011 | 0.019 | 0.015 | 0.039 | 0.001 + j0.015 | 0.007 + j0.023 | 26018 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 7.16 | 13.97 | 2.92 | 15.49 | 7 x 14 | 2.03 | 28.60 | 1.27 | 31.14 | 1208 |
TBA | 1 | 19 | 8.18 | 14.99 | 2.92 | 16.51 | 11 x 14 | 2.03 | 29.62 | 1.27 | 32.16 | 1409 |
TBA | 1/0 | 19 | 9.17 | 15.98 | 2.92 | 17.50 | 11 x 14 | 2.03 | 30.61 | 1.27 | 33.15 | 1549 |
TBA | 2/0 | 19 | 10.29 | 17.09 | 2.92 | 18.62 | 11 x 14 | 2.03 | 34.52 | 1.27 | 37.06 | 1737 |
TBA | 3/0 | 19 | 11.58 | 18.39 | 2.92 | 19.91 | 13 x 14 | 2.03 | 35.81 | 1.27 | 38.35 | 1990 |
TBA | 4/0 | 19 | 13.00 | 19.81 | 2.92 | 21.34 | 13 x 14 | 2.03 | 37.24 | 1.27 | 39.78 | 2249 |
TBA | 250 | 37 | 14.17 | 21.18 | 2.92 | 22.71 | 17 x 14 | 2.03 | 38.61 | 1.52 | 41.66 | 2612 |
588055 | 350 | 37 | 16.79 | 23.29 | 2.92 | 24.82 | 21 x 14 | 2.03 | 41.25 | 1.52 | 44.27 | 3311 |
TBA | 500 | 37 | 20.04 | 27.05 | 2.92 | 28.58 | 26 x 14 | 2.03 | 45.08 | 1.52 | 48.13 | 4241 |
TBA | 750 | 61 | 24.59 | 31.85 | 2.92 | 33.38 | 21 x 12 | 2.03 | 50.75 | 1.52 | 53.80 | 5907 |
TBA | 1000 | 61 | 28.37 | 35.64 | 2.92 | 37.16 | 21 x 12 | 2.79 | 56.06 | 1.52 | 59.11 | 7423 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ/km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 215.90 | 2359 | 0.5315 | 0.67 | 0.0137 | 0.1804 | 0.186 + j0.03 | 0.191 + j0.037 | 5458 | 215 | 221 |
1 | 223.52 | 2977 | 0.4199 | 0.53 | 0.0125 | 0.1739 | 0.144 + j0.027 | 0.15 + j0.035 | 8577 | 245 | 247 |
1/0 | 231.14 | 3756 | 0.3346 | 0.42 | 0.0113 | 0.1673 | 0.11 + j0.025 | 0.116 + j0.033 | 8577 | 278 | 275 |
2/0 | 259.08 | 4735 | 0.2657 | 0.33 | 0.0104 | 0.1673 | 0.084 + j0.024 | 0.089 + j0.032 | 8577 | 317 | 306 |
3/0 | 266.70 | 5972 | 0.2100 | 0.27 | 0.0094 | 0.1608 | 0.063 + j0.023 | 0.068 + j0.03 | 10137 | 357 | 335 |
4/0 | 276.86 | 7529 | 0.1673 | 0.21 | 0.0085 | 0.1542 | 0.047 + j0.021 | 0.053 + j0.029 | 10137 | 404 | 369 |
250 | 289.56 | 8900 | 0.1411 | 0.18 | 0.0082 | 0.1509 | 0.038 + j0.02 | 0.044 + j0.028 | 13256 | 456 | 412 |
350 | 312.42 | 12460 | 0.1017 | 0.13 | 0.0055 | 0.1444 | 0.023 + j0.019 | 0.029 + j0.027 | 16376 | 537 | 456 |
500 | 335.28 | 17800 | 0.0722 | 0.10 | 0.0061 | 0.1378 | 0.012 + j0.017 | 0.018 + j0.025 | 20275 | 616 | 497 |
750 | 375.92 | 26700 | 0.0459 | 0.08 | 0.0052 | 0.1312 | 0.005 + j0.016 | 0.011 + j0.024 | 26018 | 706 | 551 |
1000 | 411.48 | 35600 | 0.0361 | 0.06 | 0.0046 | 0.1280 | 0.001 + j0.015 | 0.007 + j0.023 | 26018 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Revision: 1.000.000
Updated On: Aug. 18, 2023, 2:39 p.m. UTC