SPEC 26102

HVTECK CU 1/C 115NLEPR TS PVC AIA PVC 5KV 133% / 8KV 100% CSA

Single Conductor, 115 Mils 5KV 133% /8KV 100% Insulation Level No Lead Ethylene Propylene Rubber (NL-EPR), Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR)
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV / 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    {SQMTR} {CSA} SOUTHWIRE{R} POWER CABLE {NESC} MASTER-DESIGN 1/C XXX AWG CU X.XX mm (115 mils) NL-EPR AIA 5KV 133%/8KV 100% INS LEVEL 25%TS SUN. RES. 105{D}C FT4 HL (-40{D}C) LTGG RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    TBA270.2820.5501150.610650.982501.082689
    TBA270.2820.5501150.610650.982501.082689
    TBA1190.3220.5901150.650651.022501.122772
    TBA1/0190.3610.6291150.689801.091501.191899
    TBA2/0190.4050.6731150.733801.135501.2351019
    TBA3/0190.4560.7241150.784801.186501.2861166
    6472644/0190.5120.7801150.840801.232501.3321367
    TBA250370.5580.8341150.894801.406501.5061517
    TBA350370.6610.9371150.997801.509601.6291939
    647268500370.7891.0421151.102801.614601.7342526
    TBA750610.9681.2541151.314801.850601.9703560
    TBA1000611.1171.4031151.463801.999602.1194465
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    27.55300.1620.2040.0340.0530.558 + j0.5140.205 + j0.0541889215221
    27.55300.1620.2040.0340.0530.558 + j0.5140.205 + j0.0541889215221
    17.86690.1280.1620.0310.0500.52 + j0.4920.163 + j0.0512013245247
    1/08.38440.1020.1280.0280.0490.488 + j0.4710.129 + j0.0492134278275
    2/08.610640.0810.1020.0260.0470.464 + j0.4490.103 + j0.0482270317306
    3/09.013420.0640.0810.0240.0460.444 + j0.4250.082 + j0.0462429357335
    4/09.316920.0510.0650.0210.0460.427 + j0.4000.066 + j0.0462602404369
    25010.520000.0430.0560.0200.0450.417 + j0.3790.057 + j0.0452769456412
    35011.428000.0310.0410.0180.0420.397 + j0.3410.042 + j0.0423088537456
    50012.140000.0220.0300.0150.0400.378 + j0.3000.031 + j0.0403485616497
    75013.760000.0140.0230.0130.0380.355 + j0.2510.024 + j0.0384071706551
    100014.880000.0110.0190.0110.0360.337 + j0.220.02 + j0.0364532813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    TBA277.1613.972.9215.491.6524.941.2727.481025
    TBA277.1613.972.9215.491.6524.941.2727.481025
    TBA1198.1814.992.9216.511.6525.961.2728.501149
    TBA1/0199.1715.982.9217.502.0327.711.2730.251338
    TBA2/01910.2917.092.9218.622.0328.831.2731.371516
    TBA3/01911.5818.392.9219.912.0330.121.2732.661735
    6472644/01913.0019.812.9221.342.0331.291.2733.832034
    TBA2503714.1721.182.9222.712.0335.711.2738.252258
    TBA3503716.7923.802.9225.322.0338.331.5241.382886
    6472685003720.0426.472.9227.992.0341.001.5244.043759
    TBA7506124.5931.852.9233.382.0346.991.5250.045298
    TBA10006128.3735.642.9237.162.0350.771.5253.826645
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2190.5023590.53150.670.01040.17390.558 + j0.5140.205 + j0.0541889215221
    2190.5023590.53150.670.01040.17390.558 + j0.5140.205 + j0.0541889215221
    1198.1229770.41990.530.00940.16400.52 + j0.4920.163 + j0.0512013245247
    1/0210.8237560.33460.420.00850.16080.488 + j0.4710.129 + j0.0492134278275
    2/0218.4447350.26570.330.00790.15420.464 + j0.4490.103 + j0.0482270317306
    3/0228.6059720.21000.270.00730.15090.444 + j0.4250.082 + j0.0462429357335
    4/0236.2275290.16730.210.00640.15090.427 + j0.4000.066 + j0.0462602404369
    250266.7089000.14110.180.00610.14760.417 + j0.3790.057 + j0.0452769456412
    350289.56124600.10170.130.00550.13780.397 + j0.3410.042 + j0.0423088537456
    500307.34178000.07220.100.00460.13120.378 + j0.3000.031 + j0.0403485616497
    750347.98267000.04590.080.00400.12470.355 + j0.2510.024 + j0.0384071706551
    1000375.92356000.03610.060.00340.11810.337 + j0.220.02 + j0.0364532813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC